9-1
EATON
Powerware
®
9315 UPS (200–300 kVA) Operation Manual
S
164201036 Rev F
powerware.com
Chapter 9
Product Specifications
The UPS systems are housed in freestanding, double-front cabinets with safety shields
behind the doors. The UPS systems are available in 50/60 Hz with various output power
ratings. Smaller models within a system may be upgraded in the field to larger models:
Table 9-1. Model Numbers
System
Models
Notes
Powerware 9315 300
225 and 300 kVA
60 Hz only
Powerware 9315 250
200 and 250 kVA
50/60 Hz (400V models only)
Powerware 9315 225
225 kVA
60 Hz only
Powerware 9315 200
200 kVA
50/60 Hz (400V models only)
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
Table 9-2. System Input
Operating Input
Voltage
(N10/–15%)
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)
Operating Input
Frequency Range
3 Hz of nominal (50 Hz or 60 Hz)
Operating Input
Current
Battery Charge
125% of full load for ov battery charge
Actual load + 25% of full load for battery charge with 0.8 pF
output units
115% of full load for ov battery charge
Actual load + 15% of full load for battery charge with 0.9 pF
output units
Reduced for Generator
Adjustable, set to 102%
Input Current
Harmonic Content
10% THD at full load (with input filter option installed)
Power Walk-In
Adjustable 3–60 second rectifier ramp-up to full utility load
Power Factor
Minimum 0.95
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4