4.
Install the INDRELAY-MS into an open MiniSlot communication bay in the
UPS cabinet.
Figure 21: Industrial Relay Card INDRELAY-MS
5.6.5
MiniSlot interface connections
For MiniSlot accessories and communication devices selection, see
Chapter
6.1 About communication interfaces
. For installation and setup of a MiniSlot
card, please contact your Eaton representative.
To install wiring to the connections:
1.
If not already installed, install the LAN drops.
2.
Open the front door of the UPS.
3.
To remove the MiniSlot cover plate, remove the 2 screws securing the plate.
4.
To install the MiniSlot communication device, push it all the way in.
5.
Secure the MiniSlot communication device with 2 screws.
6.
Route and install the LAN and other cables to the appropriate MiniSlot cards.
The cable route is through the signal cable canal in the top section of the
UPS.
7.
For operator instructions, refer to the manual supplied with the MiniSlot card.
8.
When all the wiring is completed, close the front door and secure it with the
latch.
5.6.6
Installing signal interface connections in a parallel system
The installation of the signal interface connections in a parallel system is done by
following the aforementioned instructors. The signal polarity must be taken into
account when putting signal inputs and EPO wiring in parallel. Signal inputs can
be paralleled between the units, that is, the same contact can be used for several
units’ signal input signaling. This concerns also the EPO signal.
© Eaton Corporation plc 2020. All rights reserved.
Revision: 006
Document ID: P-164000493
69 (126)
Eaton 91PS/93PS UPS 8–40 kW
User’s and Installation Guide