background image

iii

INSTALLATION INSTRUCTIONS

   MN650048EN   May 2017

The instructions in this manual are not intended as a 

substitute for proper training or adequate experience in the 

safe operation of the equipment described. Only competent 

technicians who are familiar with this equipment should 

install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
•  Is trained in industry-accepted high- and low-voltage safe 

operating practices and procedures.

•  Is trained and authorized to energize, de-energize, clear, 

and ground power distribution equipment.

•  Is trained in the care and use of protective equipment 

such as flash clothing, safety glasses, face shield, hard 

hat, rubber gloves, hotstick, etc.

Following is important safety information. For safe  

installation and operation of this equipment, be sure to read 

and understand all cautions and warnings.

Safety instructions

Following are general caution and warning statements that 

apply to this equipment. Additional statements, related to  

specific tasks and procedures, are located throughout 

the manual.

Safety for life

!

SAFETY

FOR LIFE

!

SAFETY

FOR LIFE

Eaton’s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We 

actively promote safe practices in the use and maintenance of our products through our service literature, instructional 

training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing 

and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around 

high-voltage lines and equipment and support our “Safety For Life” mission.

Safety information

DANGER

Hazardous voltage . Contact with high voltage will 

cause death or severe personal injury . Follow all locally 

approved safety procedures when working around  

high- and low-voltage lines and equipment . 

G103 .3

WARNING 

Before installing, operating, maintaining, or testing this 

equipment, carefully read and understand the contents 

of this manual . Improper operation, handling, or 

maintenance can result in death, severe personal injury, 

and equipment damage . 

G101 .0

WARNING 

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply may result in death, severe personal 

injury, and equipment damage . 

G102 .1

WARNING 

Power distribution and transmission equipment must be 

selected for the intended application . It must be installed 

and serviced by competent personnel who have been 

trained and understand proper safety procedures . These 

instructions are written for such personnel and are not 

a substitute for adequate training and experience in 

safety procedures . Failure to properly select, install or 

maintain power distribution and transmission equipment 

can result in death, severe personal  

injury, and equipment damage . 

G122 .3

This manual may contain four types of hazard statements:

DANGER 

Indicates an imminently hazardous situation which, if 

not avoided, will result in death or serious injury .

WARNING 

Indicates a potentially hazardous situation which, if not 

avoided, could result in death or serious injury .

CAUTION 

Indicates a potentially hazardous situation which, if not 

avoided, may result in minor or moderate injury .

CAUTION

Indicates a potentially hazardous situation which, if not 

avoided, may result in equipment damage only .

Hazard Statement Definitions

Summary of Contents for 600 A 15 kV class T-OP II

Page 1: ...600 A 15 25 kV class T OP II connector assembly installation instructions COOPER POWER SERIES Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 S600 12 3...

Page 2: ...POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL N...

Page 3: ...III SAFETY INFORMATION III Safety instructions iii PRODUCT INFORMATION 1 Introduction 1 Read this manual first 1 Additional information 1 Acceptance and initial inspection 1 Handling and storage 1 St...

Page 4: ...lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with high voltage will cause death or severe personal injury Follow all locally approve...

Page 5: ...eak Connectors are used to terminate high voltage underground cable on deadfront apparatus such as transformers switches and switchgear They are fully shielded submersible and meet the requirements of...

Page 6: ...al cable If cable is not concentric neutral metallic tape shielded longitudinally corrugated wire shielded or UniShield use Eaton s Cooper Power series SA series adapter kit with the same cutback dime...

Page 7: ...ust be between 6 1 2 and 7 1 4 CA625 PLACE FIRST CRIMP HERE COMPRESSION CONNECTOR 61 2 71 4 165 mm 184 mm CHECK DIMENSION AFTER CRIMPING Figure 6 Install compression connector Step 6 Install DT625 T B...

Page 8: ...ng stud installation Step 9 Install the T OP II assembly on the apparatus bushing Clean and lubricate mating interfaces of the apparatus bushing and T body with the lubricant supplied Push the T OP II...

Page 9: ...ure 12 Line illustration of protective cap installation Step 11 Ground system Refer to figure 13 Connect tie off tabs of LRTP and T body with an uninsulated drain wire to cable concentric neutral wire...

Page 10: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 6 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 11: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 7 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 12: ...nited States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN650048EN May 2017 Eaton is a registered trademark All trademarks are property of their respectiv...

Reviews: