600 A 15/25 kV Class T-OP II connector assembly installation instructions

1

INSTALLATION INSTRUCTIONS

   MN650048EN   May 2017

 DANGER

All associated apparatus must be de-energized during 

any hands-on installation or maintenance .

 WARNING 

The 600 A T-OP II Connector System is designed to be 

operated in accordance with normal safe operating 

procedures . These instructions are not intended to 

supersede or replace existing safety and operating 

procedures . The elbow connector should be installed 

and serviced only by personnel familiar with good 

safety practices and the handling of high-voltage 

electrical equipment .

 WARNING 

Optional Capacitive Test Point Operating Instructions: 

Use only voltage indicating instruments specifically 

designed for test points . Use of conventional voltage 

sensing devices may provide false “No Voltage” 

indications .

The test point must be dry and free of contaminant’s 

when checking for voltage . After indication is taken: 

clean, dry, and lubricate the test point cap with silicone 

grease and assemble to the test point .

The capacitive test point is not sufficiently accurate, 

nor is it intended for, actual voltage measurements or 

phasing operations . 

A reading of no voltage from the test point should not 

be the only indication of a de-energized circuit obtained 

before touching the connector . Other procedures can 

include direct conductor voltage testing or grounding 

using a live-line tool .

Product information

Introduction

Eaton’s Cooper Power series 600 A 15/25 kV Class T-OP 

II Deadbreak Connectors are used to terminate high-

voltage underground cable on deadfront apparatus such 

as transformers, switches, and switchgear. They are fully 

shielded, submersible, and meet the requirements of IEEE 

Std 386™ standard – “Separable Insulated Connector 

Systems”. Eaton’s Cooper Power series 600 A Deadbreak 

Connectors are fully interchangeable with all other 

manufacturers that also certify compliance with IEEE Std 

386™ standard. The T-OP II is rated for 900 A when used 

with all copper current carrying components.

Figure 1 .  Line illustration of typical 15 kV T-OP II 

connector assembly

Read this manual first

Read and understand the contents of this manual and follow 

all locally approved procedures and safety practices before 

installing or operating this equipment.

Additional information

These instructions cannot cover all details or variations 

in the equipment, procedures, or process described nor 

provide directions for meeting every possible contingency 

during installation, operation, or maintenance. For additional 

information, contact your representative.

Acceptance and initial inspection

Each T-OP II Deadbreak Connector is in good condition 

when accepted by the carrier for shipment. Upon receipt, 

inspect the shipping container for signs of damage. Unpack 

the connector and inspect it thoroughly for damage incurred 

during shipment. If damage is discovered, file a claim with 

the carrier immediately.

Handling and storage

Be careful during handling and storage of the T-OP II 

Deadbreak Connector to minimize the possibility of damage. 

If the connector is to be stored for any length of time prior 

to installation, provide a clean, dry storage area.

Standards

ISO 9001Certified Quality Management System

Summary of Contents for 600 A 15 kV class T-OP II

Page 1: ...600 A 15 25 kV class T OP II connector assembly installation instructions COOPER POWER SERIES Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 S600 12 3...

Page 2: ...POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL N...

Page 3: ...III SAFETY INFORMATION III Safety instructions iii PRODUCT INFORMATION 1 Introduction 1 Read this manual first 1 Additional information 1 Acceptance and initial inspection 1 Handling and storage 1 St...

Page 4: ...lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with high voltage will cause death or severe personal injury Follow all locally approve...

Page 5: ...eak Connectors are used to terminate high voltage underground cable on deadfront apparatus such as transformers switches and switchgear They are fully shielded submersible and meet the requirements of...

Page 6: ...al cable If cable is not concentric neutral metallic tape shielded longitudinally corrugated wire shielded or UniShield use Eaton s Cooper Power series SA series adapter kit with the same cutback dime...

Page 7: ...ust be between 6 1 2 and 7 1 4 CA625 PLACE FIRST CRIMP HERE COMPRESSION CONNECTOR 61 2 71 4 165 mm 184 mm CHECK DIMENSION AFTER CRIMPING Figure 6 Install compression connector Step 6 Install DT625 T B...

Page 8: ...ng stud installation Step 9 Install the T OP II assembly on the apparatus bushing Clean and lubricate mating interfaces of the apparatus bushing and T body with the lubricant supplied Push the T OP II...

Page 9: ...ure 12 Line illustration of protective cap installation Step 11 Ground system Refer to figure 13 Connect tie off tabs of LRTP and T body with an uninsulated drain wire to cable concentric neutral wire...

Page 10: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 6 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 11: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 7 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 12: ...nited States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN650048EN May 2017 Eaton is a registered trademark All trademarks are property of their respectiv...

Reviews: