background image

600 A 15/25 kV class T-OP II connector  

assembly installation instructions

COOPER POWER

SERIES

Deadbreak Apparatus 

Connectors 

MN650048EN

Effective May 2017
Supersedes April 2008 (S600-12-3)

Summary of Contents for 600 A 15 kV class T-OP II

Page 1: ...600 A 15 25 kV class T OP II connector assembly installation instructions COOPER POWER SERIES Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 S600 12 3...

Page 2: ...POSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL N...

Page 3: ...III SAFETY INFORMATION III Safety instructions iii PRODUCT INFORMATION 1 Introduction 1 Read this manual first 1 Additional information 1 Acceptance and initial inspection 1 Handling and storage 1 St...

Page 4: ...lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with high voltage will cause death or severe personal injury Follow all locally approve...

Page 5: ...eak Connectors are used to terminate high voltage underground cable on deadfront apparatus such as transformers switches and switchgear They are fully shielded submersible and meet the requirements of...

Page 6: ...al cable If cable is not concentric neutral metallic tape shielded longitudinally corrugated wire shielded or UniShield use Eaton s Cooper Power series SA series adapter kit with the same cutback dime...

Page 7: ...ust be between 6 1 2 and 7 1 4 CA625 PLACE FIRST CRIMP HERE COMPRESSION CONNECTOR 61 2 71 4 165 mm 184 mm CHECK DIMENSION AFTER CRIMPING Figure 6 Install compression connector Step 6 Install DT625 T B...

Page 8: ...ng stud installation Step 9 Install the T OP II assembly on the apparatus bushing Clean and lubricate mating interfaces of the apparatus bushing and T body with the lubricant supplied Push the T OP II...

Page 9: ...ure 12 Line illustration of protective cap installation Step 11 Ground system Refer to figure 13 Connect tie off tabs of LRTP and T body with an uninsulated drain wire to cable concentric neutral wire...

Page 10: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 6 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 11: ...600 A 15 25 kV Class T OP II connector assembly installation instructions 7 INSTALLATION INSTRUCTIONS MN650048EN May 2017 This page intentionally left blank...

Page 12: ...nited States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN650048EN May 2017 Eaton is a registered trademark All trademarks are property of their respectiv...

Reviews: