620-00082-01-us (en)

ENGLISH

3. Installation

3.2 Battery module connection (Tower)

Caution:

 Before starting the UPS, please connect the internal battery.

Note:  A small amount of arcing may occur when connecting the batteries. 

This is normal and does not damage the UPS or present any safety concern.

B

A

C

-  Remove front panel.

B

 -  Connect the battery module  

(never pull on the wires).

-  Attach the front panel.

3.3 Battery module connection (Rack)

Caution:

 Before starting the UPS, please connect the internal battery.

Note:  A small amount of arcing may occur when connecting the batteries. 

This is normal and does not damage the UPS or present any safety concern.

A

B

C

-  Connect the battery module  

(never pull on the wires).

-  Attach the left-hand side of the 

front panel by sliding it then by 

locking the push button.

-  Attach the center panel.

Summary of Contents for 5P 1150VA RM

Page 1: ...ИНСТРУКЦИЯ Eaton 5P 1150VA RM 9210 5378 ...

Page 2: ...500 5P 850G 5P 1550G Copyright 2012 EATON All rights reserved Service and support Call your local service representative 620 00082 01 us en 1U Rack models 5P 550 R 5P 750 R 5P 1000 R 5P 1500 R 5P 850G R 5P 1550G R Installation and user manual ...

Page 3: ...Page 2 620 00082 01 us en ...

Page 4: ...wed during installation and maintenance of the UPS and batteries The 5P models that are covered in this manual are intended for installation in an environment within 0 to 40 C free of conductive contaminant This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection a...

Page 5: ...der A protection circuit breaker must be installed upstream and be easily accessible The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system For PLUGGABLE EQUIPMENT the socket outlet shall be ...

Page 6: ......

Page 7: ... Rack 15 3 4 Installation of tower models 16 3 5 Installation of rack model for 2 post option 16 3 6 Installation of rack models 550 R 17 3 7 Installation of rack models 17 3 8 Installation of rack model for wall mounting 18 3 9 Communication ports 19 4 Operation 20 4 1 Start up and Normal operation 20 4 2 Starting the UPS on Battery 20 4 3 UPS Shutdown 20 4 4 Operation on Battery Power 20 4 5 Ret...

Page 8: ...rises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear the appropriate identification symbol 01 PET Materials Abbreviations Number in the symbols Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulation...

Page 9: ...233 5P 850G 21 9 9 9 13 6 x 5 9 x 9 1 345 x 150 x 233 5P 1550G 35 2 15 9 17 5 x 5 9 x 9 1 445 x 150 x 233 Rack models H W D Description Weights lb kg Dimensions inch mm D x W x H 5P 550 R 17 80 8 08 14 3 x 17 2 x 1 7 363 x 438 x 43 5P 750 R 30 60 13 88 20 0 x 17 2 x 1 7 509 x 438 x 43 5P 1000 R 32 50 14 72 20 0 x 17 2 x 1 7 509 x 438 x 43 5P 1500 R 43 50 19 72 21 8 x 17 2 x 1 7 554 x 438 x 43 5P 8...

Page 10: ...grammable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Attached 6 ft input power cord for AC power source 5 15P 8 LED indicating site wiring fault SWF alarm 9 Ground screw 1 USB communication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power OFF control 5 Outlets for conn...

Page 11: ...roup 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Attached 6 ft input power cord for AC power source 5 15P 8 LED indicating site wiring fault SWF alarm 9 Ground screw 1 USB communication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power OFF control...

Page 12: ......

Page 13: ... 100 720W 800VA Efficiency 98 Escape Up Down Enter On Off button Rack models Normal mode 100 10min 100 720 W 800VA Efficiency 98 Alarm Indicator red On battery Indicator yellow Power On Indicator green On Off button Up Down Enter Escape The following table shows the indicator status and description Indicator Status Description Green On The UPS is operating normally Yellow On The UPS is on battery ...

Page 14: ...user Equipment is not powered until button is pressed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode No beep The UPS is operating normally but the utility voltage is outside normal mode thresholds The UPS is powering the equipment through a Automatic Voltage Regulation device The equipment is still normally protected On Battery Battery LED is...

Page 15: ...ngs The following table displays the options that can be changed by the user Description Available settings Default settings Local settings Language English Français Deutsch Italiano Português Español Русский Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time LCD settings Modify LCD scr...

Page 16: ...tically when mains recovers after a complete battery discharge Enable Energy saving Disable Enable If enabled UPS will shutdown after 5 min of back up time if no load is detected on the output Disable Sleep mode Disable Enable If disabled LCD and communication will turn OFF immediately after UPS is OFF If enabled LCD and communication stays ON 1h30 min after UPS is OFF Disable Remote command Disab...

Page 17: ...6 1U Rack kit ears only for 550 R model 7 Front panel parts 8 2 connection cables for the protected equipments 850G and 1550G models 9 Cable locking systems 1 x 4 outlets 850G R models 1 x 6 outlets 1550G R models Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to facilitate sorting Tower models ...

Page 18: ......

Page 19: ...front panel B Connect the battery module never pull on the wires C Attach the front panel 3 3 Battery module connection Rack Caution Before starting the UPS please connect the internal battery Note A small amount of arcing may occur when connecting the batteries This is normal and does not damage the UPS or present any safety concern A B C A Connect the battery module never pull on the wires B Att...

Page 20: ...6 620 00082 01 us en 3 Installation 3 4 Installation of tower models 3 5 Installation of rack model for 2 post option 4 5 5 3 3 2 2 1 1 Use optional 1U 2 post rail kit Follow steps 1 to 5 for 2 post mounting ...

Page 21: ...lation of rack models Follow steps 1 to 4 for module mounting on the rails 1 1 2 2 3 3 4 4 The rails and necessary hardware are supplied by EATON 3 6 Installation of rack models 550 R Follow steps 1 to 3 for rack mounting 2 3 2 3 1 3 Installation ...

Page 22: ...Page 18 620 00082 01 us en 3 8 Installation of rack model for wall mounting 2 2 2 1 1 1 3 Installation ...

Page 23: ... communication cards optional standard on the Network bundle models 3 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 3 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Characteristics of the optocouplers communication port optional Pins 1 3 4 5 6 10 not used Pin 2 common user Pin 7 low ba...

Page 24: ......

Page 25: ...d See the Cold start setting in ON OFF Settings on page 13 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS cycles through Standby mode to Battery mode The indicator illuminates solid The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices ...

Page 26: ...ut down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below 4 Remote control connection and test 1 Check that the UPS is OFF and disconnected from the AC input source 2 Remove connector 4 3 Connect a normally closed volt free contact 60 V DC 30 V AC max 20 mA max 0 75 mm2 18 AWG cable cross s...

Page 27: ...emove some of the equipment from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the battery life is reached Contact your service representative for battery replacement Event An UPS event occurs Example Remote Power OFF the RPO contact has been activated to shutdown the UPS and now preve...

Page 28: ...removal on tower models This operation must be performed when the UPS is switched OFF A A Remove the front panel B B Disconnect the battery module by separating the town connectors never pull on the wires C C Remove the plastique protection cover in front of the battery one screw D D Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above...

Page 29: ...C Disconnect the battery module by separating the town connectors never pull on the wires D D Remove the metal protection cover in front of the battery two screws E E Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order To ensure safety and high performance use only batteries supplied by EATON Take care to...

Page 30: ......

Page 31: ...ed lead acid maintenance free Standard Tower 2 x 12 V 7 Ah 2 x 12 V 9 Ah 3 x 12 V 9 Ah Rack 2 x 6 V 9 Ah 4 x 6 V 7 Ah 4 x 6 V 9 Ah 6 x 6 V 9 Ah Environment Operating temperature range Storage temperature range Relative humidity Noise level 0 to 35 C 0 to 40 C 15 to 50 C 0 to 90 without condensation 40 dBA 1 The high and low thresholds can be adjusted using UPS settings 2 Up to 40 Hz in low sensiti...

Page 32: ... V 9 Ah Rack 4 x 6 V 9 Ah 6 x 6 V 9 Ah Environment Operating temperature range Storage temperature range Relative humidity Noise level 0 to 35 C 0 to 40 C 15 to 50 C 20 to 90 without condensation 40 dBA 1 The high and low thresholds can be adjusted using UPS settings 2 Up to 40 Hz in low sensitivity mode programmable using UPS settings 3 Adjustable to 200 208 220 230 240 V must be set to the ident...

Page 33: ...r is low and that the user must take action in light of the imminent break in the supply of power to the load Normal AC input The AC power line supplying the UPS under normal conditions Percent load Ratio of the power effectively drawn by the load to the maximum output of the UPS Personalisation It is possible to modify certain UPS parameters set in the factory Certain UPS functions can also be mo...