reset the LINK LED, and reset the DCD output on the DB9 RS232 port and reset the DIO
output (if configured).
During normal operation, if there has been no radio activity for a period (called the “link
check” period), the master unit will transmit a “check” message to check the radio path. The
link check period is user-configurable (S-Register S6). If the slave doesn’t receive any
messages within the configured link check timeout (Configuration Setting \T), it will drop the
radio link, and turn off the LINK LED, and reset the DIO and DCD signals (if configured).
Successful Communications
Source Module
Destination Module
Serial data is received
Serial LED flashes
Listen to ensure channel is clear
If clear, transmit message
Radio TX LED flashes
----------------->
Receive message
Radio RX LED flashes
Check system and destination
address
If OK, check error-check
Radio RX LED flashes
<-----------------
If message okay, transmit back
an ACK message.
Radio TX LED flashes
Acknowledgment received okay -
communication complete
Serial data is output
Serial LED flashes
Unsuccessful Communications
Source Module
Destination Module
Listen to ensure channel is clear
If clear, transmit message
TX LED flashes
----------------->
Receives message
RX LED flashes
Check system and destination
address
If incorrect, transmit no message
and no serial output.
No ACK received
Retry multiple times (Configure With
S-Register S30)
----------------->
If no ACK message received after
all attempts
“NO CARRIER” message sent to
host
DCD signal and DCD LED reset