Network Management Card
– User Manual
34003991EN/EB
Page
40/118
4.2.6 Measurements
Click on "Measurements" in the menu
◗
The next window shows the measurements for a mono phases UPS.
The following measurements are saved and time-stamped (env. 430):
◗
"AC Normal : Voltage": Value of the utility voltage supplying the UPS
◗
"AC Normal : Frequency": Value of the utility frequency supplying the UPS
◗
"AC Output : Voltage": Value of the output voltage of your UPS
◗
"AC Output : Frequency": Value of the output frequency of your UPS
◗
"AC Output : Power (kVA)": Value of the output power of your UPS
◗
"AC Output : Load level (%)": Value of the percentage of load at UPS output
◗
"Battery : Capacity (%)": Percentage of charge available in the battery
◗
"Battery : Remaining time (mn)": Estimation of the remaining backup time
◗
The save frequency of these values is defined in the
"System"
page (60 seconds by default). Approximately 435
time-stamps are stored permanently on the card. The oldest time-stamps are automatically deleted.
◗
"Save Log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type
spreadsheets)
◗
"Clear Log" enables deletion of all records. Enter the login/password to validate this action.