Network Management Card
– User Manual
34003991EN/EB
Page
86/118
7.2.3 Configuration of the JBUS/MODBUS communication parameters
◗
Use the cord supplied with the card.
◗
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600
baud, 8 bits, no parity, 1 stop bit, and without flow control.
◗
Check that UPS power is on.
◗
Enter the admin password (not modifiable).
Connect the RS232 link
to a terminal
(Microsoft Hyper
terminal)