Use cable cross section and protective device specification
Model
6000H
6000HXL
10000H
10000HXL
Input L,N,
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
Input L,N breaker (A)
32A, 250VAC
50A, 250VAC
Input fuse (A)
30A, 250VAC
60A, 250VAC
Output L,N,
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
External Battery Cabinet Positive
Pole(+), Neutral pole, Negative pole(-),
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
External Battery Cabinet Fuse (A) in
Positive pole(+),Neutral pole,
Negative pole(-).
30A, 240VDC
50A, 240VDC
External Battery Cabinet breaker (A) in
Positive pole(+),Neutral pole,
Negative pole(-).
30A, 240VDC
50A, 240VDC
Backfeed protection device
A 2-pole disconnection device with 60A/250VAC,
less than 15s break time and min. 1.4mm clearance
will be used in final installation for backfeed
protection.
Protective Earthing conductor[m
㎡
]
Min.2.5 Min.6.0
Torque for fixing above terminals
3.95~4.97Nm
(35~44 1bf· in)