3
1.5
Storage:
★
The UPS must be stored in the location where it is ventilated and dry.
★
If the batteries are stored in temperate climatic areas, they should be charged for 1-2
hours every three months. You should shorten the charging intervals to two months at
locations subject to high temperature.
1.6
Safety caution:
Warning:
For all models:
★
See installation instructions before connecting to the supply.
★
Do not remove the enclosure. This system is to be serviced by qualified service
personnel only.
★
Remove the protective panel only after disconnecting the terminal connections.
★
Equipment powered more than one source.
★
High leakage current, earth connection essential before connecting supply.
★
Indiscriminate operation of switches may cause output loss or damage to equipment.
Refer to instruction before conducting any control.
For 6000H/6000HXL/10000H/10000HXL:
★
Before working on this circuit: isolate uninterruptible power system (ups).
★
The external parallel cable which connects to the parallel port should be reinforced
insulation.
★
The UPS can not be moved in all modes (after installation and wiring completed). Please
switch the breaker of the castors in OFF position to ensure that the UPS can not be
moved. Before the UPS being moved, all external wires must be completely
disconnected, and then the breaker should be switched in ON position.