Location & Mounting of Indoor Unit (QLC)
Preparation of Suspended Ceiling
The ceiling tiles and suspension framework must be cut away and re-supported to suit the size of the unit such that the grille assembly,
when fitted to the chassis, will cover all raw edges.
Unit Fixing
The unit should be suspended by four off M10 drop rods secured to the unit supporting angles held in place by M10 nuts and washers.
The unit should be suspended 1 to 2mm off the ceiling tile face and must be absolutely level in both directions (use spirit-level to check).
Note 1:
In order to reduce the weight of the unit during installation the fan assembly may be easily removed as follows (refer to
diagram on page 7 for reference).
(i) Disconnect the motor loom from the unit terminal block.
(ii) On the QLC 10 slacken the two screws at one end of the fan tray and slide the tray towards the screws to disengage the other end
then raise the fan tray assembly clear of the chassis – the fixing screws will pass through the keyhole slots.
(iii) On the QLC 15/20 remove the two screws at one end of the fan tray. Slide the fan tray assembly towards the screws to disengage
the opposite end and then raise the fan tray assembly to clear the joggle strips in the slots at the screw ends.
Note
When lifting the fan tray do not insert hands into the fan scroll. This can cause the fan
impellors to become unbalanced.
Fascia Assembly (Note: leave Fascia in protective wrapping until fitted)
The Fascia is comprised of an inlet grille (2) and a louvred outlet air assembly (3). The inlet grille (2) is attached to outlet assembly by
2 off latch fixings which locate in the air outlet assembly side frame holes.
Fascia Fixing
Fit the outlet air assembly (3) to the unit chassis by inserting the two slots along one long side behind the two corresponding capture
screw heads on the inner chassis side. Lift the other side of the outlet air assembly to match the two swing bolts on the opposite chassis
side. Clamp with the swing bolts and tighten the other two captive screws.
SPECIAL NOTES :
ENSURE THE INDOOR UNIT IS INSTALLED LEVEL TO PREVENT DRAINAGE PROBLEMS
CHECK IF ANY OPTION KITS REQUIRE SITE FITTING BEFORE INSTALLING THE UNITS.
Eaton-Williams
Low Temperature DX Cassette
Page 5
QLC/ICU
Document 0412124
Issue 2.1 05/06