Universal Output Connection as Digital Output
Remarks: Universal Output as Digital Output
Only DC power source can be use. If AC power source it will damage the controller. Max DC power source
is 24VDC.
Max load for Universal Output as Digital Output is 200mA.
Refer below table for software configurations of UO as DO. A Digital Output Block must be used.
EasyIO FS32
Physical Universal Output
Digital Output Block Channel
UO1
DO 9
UO2
DO 10
UO3
DO 11
UO4
DO 12
UO5
DO 13
UO6
DO 14
UO7
DO15
UO8
DO 16