Application 

The energy-meters are used to measure single-phase applications like residential, utility and Industrial. The unit 
measures and displays various important electrical parameters. It equipped with a white back-lighted LCD screen 
for prefect reading. As well as a RS485  communication port for remote reading and monitoring. Bi-directional 
energy measurement makes it a good choice for solar PV energy metering.  The  compact design and din rail 
installation provides an easy and economical solution for your metering demand. 

PART 1

 

Specification 

 

General Specifications 

Voltage AC (Un)       

 

         230V 

Voltage Range         

 

         176~276V AC 

Base Current (Ib)      

 

         5A 

Power consumption     

 

<2W/10VA 

Frequency             

 

         50/ 60Hz(±10%) 

AC voltage withstand     

 

4KV for 1 minute 

Impulse voltage withstand     

6KV-1.2uS waveform 

Overcurrent withstand   

 

20Imax for 0.5s 

Pulse output 1  

 

 

 

0.001/0.01/0.1/1 kWh/imp (configurable) 

Pulse output 2            

 

        1000imp/kWh (default) 

Display   

 

 

 

 

LCD with white backlit 

Max. Reading   

 

 

 

999999 kWh 

 

Accuracy 

Voltage      

 

 

 

        0.5% of range maximum 

Current     

 

 

 

         0.5% of nominal 

Frequency      

 

 

 

0.2% of mid-frequency 

Power factor    

 

 

 

1% of Unity 

Active power   

 

 

 

1% of range maximum 

Reactive power 

 

 

 

1% of range maximum 

Apparent power   

 

 

1% of range maximum 

Active energy   

 

 

        Class 1 IEC62053-21 

                                                              Class B EN50470-1/3 
Reactive energy    

 

 

Class 2 IEC62053-23 

 
 

Environment  

Operating temperature    

 

 

        -25

 to +55

 

Storage and transportation temperature   -40

 to +70

 

Reference temperature   

 

 

 

23

℃±

2

 

Summary of Contents for SDM120CTM

Page 1: ...axing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com SDM120CTM Single Phase Multifunction DIN Rail Meter Measures kWh kVArh kW kVAr kVA PF Hz dmd V A etc Bi directional meas...

Page 2: ...y and economical solution for your metering demand PART 1 Specification General Specifications Voltage AC Un 230V Voltage Range 176 276V AC Base Current Ib 5A Power consumption 2W 10VA Frequency 50 60...

Page 3: ...export kWh or kVArh The pulse constant can be set to generate 1 pulse per 0 001 0 01 0 1 1 kWh kVArh Pulse width 200 100 60ms Pulse output 2 is non configurable It is fixed to total kWh The constant i...

Page 4: ...e meter After initialization and self checking program the meter display the measured values The default page is total kWh If the user wants to check other information he needs to press the scroll but...

Page 5: ...n Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 6 Active power W 7 Frequency F 8 Power factor PF 9 Modbus Address ID Default 001 10 Baud rate Default 2400bps 1...

Page 6: ...SET menu pressing the button again for 3 seconds enter into the CT1 setting mode Under this menu long press the button for 3 seconds enter to the set up mode The rightmost digit will flash press the...

Page 7: ...r Manual Zhejiang Eastron Electronic Co Ltd Tel 0086 573 83698881 Fax 0086 573 83698883 Add No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com Inst...

Reviews: