9
— To avoid overloading the building's main fuse, the
Easee Equalizer can be used for dynamic load
balancing. The maximum current value can also be
set as required during configuration.
Special notes for Easee Home and Easee Charge
— In addition to the integrated residual current device
(RCD), an overload protection is integrated in the
Charging Robots.
— Several Charging Robots can also be connected
in parallel, as each Charging Robot has its own
protective devices.
— The Charging Robots can handle a maximum short-
circuit current (Ipk, max) of 10 kA. When surveying
the installation, it must be checked whether further
protection should be provided.
— If the charging infrastructure includes more
than one Charging Robot, the backplate that is
configured first becomes the master of its circuit.
— If more than 2 units are installed, the master unit
should be located in the middle of the installation (if
possible) for an optimal Easee Link communication.
Technical notes for Easee Home
— The circuit with one or more Charging Robots can
be fused up to 40 A as long as the maximum short-
circuit current (Ipk, max) of 10 kA is not exceeded.
— A maximum of 3 Charging Robots on the same
circuit (fuse) is supported with Easee Home.
Technical notes for Easee Charge
— The circuit with one or more Charging Robots can
be fused up to 80 A as long as the maximum short-
circuit current (Ipk, max) of 10 kA is not exceeded.
— A maximum of 101 Charging Robots on the same
circuit (fuse) is supported with Easee Charge.
—
Site Key:
During installation, a Site Key must be
used to assign the Charging Robots to the correct
location inside the Easee Cloud. A Site Key can be
obtained by creating a new charging site at
.
Your house, power grid and EV
The Charging Robot will never be the bottleneck. It
automatically adapts to the power grid, the electric car
and the capacity of your house. In the diagrams below
you can see what charging effect you can achieve in
your installation and situation. The table below is only
meant as a guide.
NOTICE!
The type of installation as well as cable cross-
sections must be determined by a qualified electrician
in accordance with valid local, regional and national
regulations for electrical systems.
1
Protection limit based on max 80% of the fuse rating can be set in
the WiFi interface.
2
Example for 400 V TN, deviating values for other grid types.
Rated
circuit fuse
size
Max
continuous
fuse load
1
400 V TN
2
Ampere (A)
Ampere (A)
1 phase
(kW)
3 phase
(kW)
10
8
1.4
4.2
16
13
3.0
8.9
20
16
3.7
11
25
20
4.6
13.8
32
25
5.8
17.3
40
32
7.4
22