Step 3:
The
Thermal Bulb must be positioned and
clamped to the suction tube as shown in the
example illustrated in Figure 10. The
Thermal Bulb and suction tube must be horizontal
regardless
of the cased coil application (vertical or horizontal).
The Thermal Bulb must be positioned at the 3:00, 4:00, 8:00 or 9:00 positions on the suction tube, as
illustrated in Figure 10.
Figure 10. Thermal Bulb Positioning
Step 4:
Clamp the thermal bulb firmly against the
clean suction tube
extension and parallel to it, as
shown in Figure 11.
Isolate the Thermal Bulb from with a cold wet cloth while Nitrogen brazing the joints on the suction line.
After the suction line has cooled, apply the supplied cork tape insulation around the Thermal Bulb to
completely isolate it from the surrounding air, as shown in Figure 12.