EAE KNX Motion Detector  

 

Product Manual MD100 

 

 

 

 

 

 

  
  
  
  

 

Order Number: 48018 

 

  

 

 

Summary of Contents for MD100

Page 1: ...EAE KNX Motion Detector Product Manual MD100 Order Number 48018...

Page 2: ...t 1 General 2 1 1 Technical Data 2 1 2 Operation and Display 4 1 3 Scale Drawings 5 2 Communication Object Information 6 2 3 Communication Object Table 6 2 4 Communication Object Description 8 3 Param...

Page 3: ...er movement no action Stay on time can be changed the by end user Air conditioning and ventilation systems can be controlled by independent HVAC channel Presence information can be sent to presence mo...

Page 4: ...guideline and low voltage Application program Communications objects Number of addresses max 44 255 NOTE Device default physical address is 15 15 255 In order to configure KNX Motion detector ETS app...

Page 5: ...r in meter of the different areas for different installation heights M Detection range 1 2 Operation and Display Figure 1 Surface mounted MD 100 Table 1 Motion M A B C D 5 0m 12 18 3 0 4 0m 10 15 2 3...

Page 6: ...hnology com Page 5 21 Product Manual MD100 EAE KNX Motion Detector MD100 PM R1 0 Figure 2 Flush mounted MD100 1 KNX connection terminal 2 Programming button 3 Blue movement LED 1 3 Scale Drawings Figu...

Page 7: ...Flags 0 General In operation DPT 1 002 1 bit CWT 1 General Presence slave 1 DPT 1 001 1 bit CRW 2 General Presence slave 2 DPT 1 001 1 bit CRW 3 General Presence slave 3 DPT 1 001 1 bit CRW 4 General...

Page 8: ...24 Group 2 output Dimming level DPT 5 001 8 bit CRT 25 Group 2 input Switch light DPT 1 001 1 bit CW 26 Group 2 input Dimming level DPT 5 001 8 bit CW 27 Group 2 input Dimming light DPT 3 007 4 bit C...

Page 9: ...tion objects by master sensor Slave sensors send the value 1 when movement is present otherwise send value 0 These values are processed in OR gate by master sensor If the output value is 1 master sens...

Page 10: ...ue Sensor will calculate the calibration factor according to new lux value automatically Subsequent detections will be calculated with new calibration factor 12 Constant Light External Brightness DPT...

Page 11: ...to output object at detected movement and stays ON until t adjusted time runs out Current Lighting stay ON time can be read from the object or a new Lighting stay ON time can be written to the object...

Page 12: ...ng a telegram through this object has an alterable behaviour according to Light level control parameter in the Constant light level parameter window Disable constant light and dim It remains disabled...

Page 13: ...re enables the constant light control and switches the lighting OFF Don t disable and no action No action receiving a telegram through Group 1 input object 3 Parameters Parameters chapter describes E...

Page 14: ...ble HVAC no yes Parameter enables brightness parameters and objects Overwrite settings for download yes no This parameter is used to decide whether settings stated below are overwritten or not by down...

Page 15: ...ter detecting first movement Detector waits for selected number of movements during Presence switch ON delay time in order to send that the presence information is ON Presence stay ON time sec 1 10 25...

Page 16: ...d with the value 0 and re enabled with value 1 Behaviour disable lighting no action Light ON Light OFF This parameter is used for selecting whether to send a telegram from the presence output object b...

Page 17: ...ration factor This parameter is used select calibration method of the brightness sensor inside the detector There are two options in order to calibrate the brightness sensor Via object Calibration val...

Page 18: ...rightness on off control Lighting groups are only controlled by switch object according to set point value If measured brightness value is greater than the set point value switch object is set to the...

Page 19: ...point value 100 95 90 etc Transmit next dimming value after 0 5s 1s 2s 3s 5s This parameter is used to specify the time interval between two sending dimming value After sending a dimming value 60 nex...

Page 20: ...f lighting Automatically ON and OFF Lighting group is controlled automatically by detector according to presence information If person is present in the room ON command is sent to the lighting group i...

Page 21: ...value OFF and enabled with the value ON Behaviour disable lighting no action Light ON Light OFF This parameter is used for selecting whether a telegram is sent to lighting group before disabling ligh...

Page 22: ...d Stay ON time objects are not visible Disable light level control no ON for disabling OFF for enabling OFF for disabling ON for enabling This parameter determines the value type for disabling enablin...

Page 23: ...etechnology com Page 22 21 Product Manual MD100 EAE KNX Presence Detector MD100 PM R1 0 Light ON After enabling the HVAC output it is set to the value ON Light OFF After enabling the HVAC output it is...