Product Manual DA110
EAE KNX DALI Gateway
DA110 R2.0
©
EAE Technology
www.eaetechnology.com
Page 16 / 21
Allow switch on via brightness value
*yes
no
Allow switch off via brightness value
*yes
no
Allow switch on via relative dimming
*yes
no
Allow switch off via relative dimming
*yes
no
“Switch on” and “Switch off” conditions can be defined for brightness value and relative dimming commands
separately. If these parameters are selected “no”, then it is not possible to switch “on” or “off” the lighting
fixtures via brightness value (1 byte) or relative dimming (4 bit) objects of the group.
Fade time
(switch, brightness value and dim commands)
jump to…
1 s
…90
s
These parameter defines the fade time for switch, brightness value and relative dimming commands per
device.
Brightness value when switch on
Last switch on value, 5% (13) …*
100% (255)
This parameter defines the brightness value when a “switch on” command is received over Switch
communication object.