Product Manual DA110
EAE KNX DALI Gateway
DA110 R2.0
©
EAE Technology
www.eaetechnology.com
Page 11 / 21
No
Function
Name
DPT
Length Flags
9
DALI line fault
Feedback
1.005
1 bit
CRT
This object is used for reporting DALI gateway supply fault. Possible causes of the fault are no mains
connection to gateway supply terminal, power supply malfunction or short circuiting DALI line more than
100ms.
-
Object will be activated if “Enable “Fault gateway supply” object” parameter in Feedback tab is selected as
“enable”.
-
Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = gateway supply works properly, value “1” = gateway supply fault)
10
Mains connection fault
Feedback
1.005
1 bit
CRT
This object is used for reporting DALI gateway mains connection fault. Possible causes of the fault are no mains
connection to gateway supply terminal.
-
Object will be activated if “Enable “Mains connection fault” object” parameter in Feedback tab is selected
as “enable”.
-
Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = gateway supply works properly, value “1” = Mains connection fault)
11
Lamp fault
Feedback
1.005
1 bit
CRT
This object is used for reporting whether there is any device that has a fault lamp is present or not.
-
Object will be activated if “Enable “Lamp fault” object” parameter in Feedback tab is selected as “enable”.
-
Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no fault lamp, value “1” = at least one of the DALI devices has a lamp fault)
12
Device fault
Feedback
1.005
1 bit
CRT
This object is used for reporting whether there is any offline or malfunctioned ballast/driver is present or not.
-
Object will be activated if “Enable “Device fault” object” parameter in Feedback tab is selected as “enable”.
-
Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no ballast/driver fault, value “1” = at least one of the DALI ballasts/drivers is offline or
malfunctions)