Product Manual DA110
EAE KNX DALI Gateway
DA110 R2.0
©
EAE Technology
www.eaetechnology.com
Page 12 / 21
No
Function
Name
DPT
Length Flags
13
Mains power failure status
Feedback
1.005
1 bit
CRT
This object is used for reporting a misconnection of mains to the DALI line.
-
Object will be activated if “Enable “Fault mains connected” object” parameter in Feedback tab is selected
as “enable”.
-
Feedback will be sent only after a request if "transmit mode" parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no misconnection, value “1” = mains connected to DALI line)
NOTE:
Overvoltage sense circuitry on the DALI line is triggered on voltages above 40V. So any voltage
above 40V is considered as mains.
14
Scene 8 bit
Scene
17.001
1 byte CW
This object is used to recall up to 16 scenes that are available on the gateway device.
-
Object is always enabled.
-
Even devices which is not shown on ETS parameters can be controlled via scenes properly.
NOTE: Scene save function is not available.
Bit numbers and data which they represented is explained below;
7
6
5
4
3
2
1
0
Byte Bit Field Description
1
Bit 0 - 3
Scene number - 1 [0 – 15 for scenes 1 - 16]
Bit 4 - 7
Reserved and should be 0
Example of recall byte codes for scenes;
Scene
Recall
Scene
Recall
Hexadecimal
Decimal
Hexadecimal
Decimal
1
0x00
0
9
0x08
8
2
0x01
1
10
0x09
9
3
0x02
2
11
0x0A
10
4
0x03
3
12
0x0B
11
5
0x04
4
13
0x0C
12
6
0x05
5
14
0x0D
13
7
0x06
6
15
0x0E
14
8
0x07
7
16
0x0F
15