F u n c t i o n C o d e T a b l e
EC670
EC670
F u n c t i o n C o d e T a b l e
A2
-
02
S3 terminal
function
6: Coast to stop 7: Emergency stop
8: Fault reset (RESET)
9: Normally open (NO) input of external
fault
10:Terminal UP 11:Terminal DOWN
12:UP and DOWN setting clear (terminal,
operation panel)
13:Speed control/Torque control switchover
14:Torque control prohibited
15:Speed search start enable
16:Multi-reference terminal 1
17:Multi-reference terminal 2
18:Multi-reference terminal 3
19:Multi-reference terminal 4
20:Terminal 1 for acceleration/decele-
ration time selection
21:Terminal 2 for acceleration/decele-
ration time selection
22:Acceleration/Deceleration prohibited
23:PID ctrl diaable
24:PID pause 25:PID integral pause
26:Reverse PID action direction
27:PID parameter switchover
28:PID target value switchover terminal1
29:PID target value switchover terminal2
30:PID target value switchover terminal3
31:PID feedback value switchover terminal1
32:PID feedback value switchover terminal2
33:PID feedback value switchover terminal3
34:PLC pause 35:PLC status reset
36:Swing enable 37:Swing pause
38:Swing reset
39:Frequency source switchover terminal1
40:Frequency source switchover terminal2
41:Frequency source switchover terminal3
42:Frequency source switchover terminal4
43:Command source switchover terminal 1
44:Command source switchover terminal 2
45:Counter input
47:Length count input
48:Length reset
49:Immediate DC braking
50:terminal pre flux
51: User-defined fault1
52: User-defined fault2
53:UPS mode active
2
1202H
A2
-
08
Characteristic
selection of
terminals S1-4
0000
~
1111
LED-Bits0: S1 terminal
0: effective closing 1: effective opening
LED-Bits1: S2 terminal
0: effective closing 1: effective opening
LED-Bits2: S3 terminal
0: effective closing 1: effective opening
LED-Bits3: S4 terminal
0: effective closing 1: effective opening
0000
1208H
A2
-
03
S4 terminal
function
16
1203H
A2
-
04
S5 terminal
function
17
1204H
A2
-
05
S6 terminal
function
18
1205H
A2
-
06
S7 terminal
function
19
1206H
A2
-
07
S8 terminal
function
53
1207H
A2
-
09
S1-S4 terminal
filtering time
0.00
~
60.00s
This parameter is defined as the size of
filtering the input signal to eliminate the
interference signal. The longer the fil-
tering time is, the stronger the anti-
interference ability is, but the slower the
response speed is; the shorter the filtering
time is, the weaker the anti-interference
ability is, but the faster the response
speed is.
0.10s
1209H
0000
A2
-
10
120AH
0000
~
1111
LED-Bits0: S5 terminal
0: effective closing 1: effective opening
LED-Bits1: S6 terminal
0: effective closing 1: effective opening
LED-Bits2: S7 terminal
0: effective closing 1: effective opening
LED-Bits3: S8 terminal
0: effective closing 1: effective openin
Characteristic
selection of
terminals S5-8
0.10s
A2
-
11
120BH
S5-S8 terminal
filtering time
0
.
00
~
60.00s
Same as P4-08
3
A2
-
12
120CH
Terminal
control
operation mode
0
~
3
0: the terminal with two-wire system 1
terminal set as 1 is in forward running,
terminal set as 2 is in reverse running,
1:the terminal with two-wire system 2
terminal set as 1 is in starts running,
terminal set as 2 is switch forward and
reverse
2:the terminal with three-wire system 1
terminal set as 1 is in forward running,
terminal set as 2 is in reverse running,
terminal set as 3 is stop running,
3: the terminal with three-wire system 2
terminal set to 1 starts running,
terminal set as 2 is switch forward and
reverse,
terminal set as 3 is stop running,
37
A2
-
13
120DH
Y1 terminal
function
0
~
39
0 :No output
1 :AC drive Forward running
2 :AC drive Reverse running
3 :Fault output1(no output at auto reset
period )
4 :Fault output2(output at auto reset
period )
5 :Ready for RUN
6 :Frequency reached
7 :Frequency-level detection FDT1 output
8 :Frequency-level detection FDT2 output
9 :Frequency upper limit reached
10:Frequency lower limit reached
11:Current 1 reached
12:Current 2 reached
13:Zero current state