EC5000

112

 -

113

 -

The diagnosis and the exclusion for the abnormalities

7

 

EEPROM error 

      (EPF)

Fault  

Description

detail

error correction

AC drive control

Component error.

Try the function of

"A01 factory 

defaults",if it is still 

unable eliminated,

please contact us.

EPF

7.1.2 

List of Alarm Display 

Pressure enduring 

test

Radiator overheat

Over rotation moment 

of force test

Outside BB

Right/opposite 

running order error

RS485 transmission 

waiting

AC drive overheat 

alarm

RS485 transmission 

error

Overvoltage in 

stopping

Not enough voltage tested when AC drive stops.

Select test in environment of radiator tempera-

ture≥OH1 test standard, AC drive continue 

running.

When the output current of AC drive is>C24

(over rotation moment of force test standard),

select over rotation moment of force, AC drive 

continue running.

External BB order input from control circuit 

terminal.

It is OFF when right/opposite running order

input over 500ms.

In circumstance of A03(operation mode sellec-

tion)

4, AC drive can not receive data flow 

from RS485 when power is on.
AC drive overheat alarm signal is input from 

control circuit terminal.

Sellect continue running when RS485 

transmission error data transmition break down.

Main circuit EDC voltage surpass overvoltage 

test standard when AC drive stops.

display

Content 

illustration

Uu

OH1

Ol3

BB

EF

CALL

OH3

CE

OU

EC5000

EF2~8

Error from

terminal  

RS485 general 

data wire

Error in external control 

circuit

Check the input 

external,if the error 

happen in the 

terminal is 

unconnect,change 

the AC drive. 

SPI

Current 

Fluctuate too  

much

The input power of AC drive

 is lack phase or have 

unstable in input voltage

Check power in 

voltage.

Re-tighten the 

input terminal 

screw.Or adjusted 

basis SPI  

 

SPo

Output lack 

phase

AC drive

 output lack phase.

1.Check output 

wire and check 

motor impedance.

2.Re-tighten the 

output terminal 

screw.

3.Adjust the SPO 

standard

Fault 

Description

detail

error correction

CE

MEMOBUS 
transmition 
error

RS485 control data not 
received normally.

 

Check transmition 

equipment 

 or signal

 

rH

Braking 
reactor 
component 
overheat

 

Exceed the braking reactor 
Temperature 

 

Low down load 
capacity.

 

The connection between AC 

drive and digital operator 

can’t bulid in 5 seconds after

power is on. MPU external 

component error(initial).

Input digital operator,

connector.

check control circuit 

wire.

change control insert 

board.

Control circuit 

error 1

(

ERR

)

Err

The diagnosis and the exclusion for the abnormalities

Summary of Contents for EC5000 Series

Page 1: ...low information before use Installation and Wire Layout Operation and inspection Operation keypad Panel Description of Functional Parameter MODBUS Communication Protocol The diagnosis and the exclusion for the abnormalities Maintenance inspection Appendix V2 5 Website www eacon cc ...

Page 2: ... adjustment is done by professional motor engineers and the content marked as Danger Notice etc in this manual must be read carefully If you have any questions please contact with the agents of our company and our technicians are ready to serve you The matters that specially need attention are as follows 1 The power supply must be turned off when laying the wires 2 When the AC power supply is cut ...

Page 3: ...y to be punctured and damaged by high voltage 2 The circuit board of the driver has CMOS IC which is extremely easy to be damaged by static electricity thus please do not touch the circuit board with your hand before taking anti static electricity measures 3 Even if the motor is inactive the main loop terminal of the driver may still have dangerous high voltage 4 Only the qualified motor professio...

Page 4: ...s that sold you the product Description of the label of package Read below information before use Catalogue 6 2 2 Function Code and Data Content 6 3 Error Value 6 4 Communication Protocol and Digital Address Definition Chapter 7 The Diagnosis and the Exclusion for the Abnormalities 7 1 List of Protective Actions 7 1 1 List of Fault Display 7 1 2 List of Alarm Display 7 2 Reset Alarm 7 3 The Causes...

Page 5: ...cant should be put in the packing bag 3 When the storage period is longer than 3 months the surrounding temperature should not exceed 30 because the electrolytic condenser is stored with power off and it will easily degrade if the temperature is high Read below information before use Read below information before use 1 Voltage class 23 represents three phase 220V 43 represents three phase 400V Cap...

Page 6: ...with power off for a long term Please do not store the electrolytic condenser with power off for more than one year 1 4 Considerations for Choices of AC Drives 1 Use large capacity above 600 kva electric current transformer and capacitor into phase voltage input side surge current is too large that could undermine the input side of ac motor drives At the moment the input side must be installed an ...

Page 7: ...shall be installed vertically with screws and shall not be installed upside down obliquely or horizontally on a firm structure When the AC drive is running it will generate heat To ensure that the cooling air path is as shown in figure b There is a certain space in the design and the heat generated will be emitted upward therefore do not install it under the heat resistant equipment When the AC dr...

Page 8: ...503D7G23C EC5000 Installation and Wire Layout EC5000 Installation and Wire Layout 8 9 Frame20 EC505D5G23B Frame30 EC507D5G23B EC50011G23B unit mm Frame40 EC50015G23B EC518D5G23B EC50022G23B Frame50 EC50030G23B EC50037G23B 2 ...

Page 9: ...out 10 11 Frame80 EC50110G23B EC50132G23B EC5000 Frame60 EC50045G23B EC50055G23B Installation and Wire Layout Frame70 EC50075G23B EC50090G23B 2 unit mm 2 3 2 400V Installation dimension of AC drive Frame10 EC50D75G43C EC501D5G02D2P43C ...

Page 10: ...037P43B EC50037G0045P43B Frame40 EC518D5G0022P43B EC50022G0030P43B unit mm Frame30 EC50011G0015P43C EC50015G18D5P43C EC5000 Installation and Wire Layout Frame11 EC502D2G03D0HP43C EC503D0G04D0P43C EC504D0G05D5P43C Frame20 EC505D5G07D5P43C EC507D5G0011P43C unit mm ...

Page 11: ...43B Frame70 EC50075G0090P43B EC50090G0110P43B Frame80 EC50110G0132P43B EC50132G0160P43B FrameA0 EC50250G0280P43B EC50280G0315P43B EC50315G0350P43B EC50350G0400P43B FrameB0 EC50400G0450P43B EC50450G0500P43B EC50500G0560P43B EC50560G630P43B Notice The base is optional Notice The base is optional Notice The base is optional Notice The base is optional Notice The base is optional ...

Page 12: ...ring the selection of the specification of wire diameter should be in accordance with the standards of electrical engineering for safety The screws of the terminals should be tightened preventing the sparks caused by loose screws due to vibration The standard wire layout figure for EC5000 AC drive is shown below Notice Installation and Wire Layout 2 EC5000 unit mm Dimension of the installation hol...

Page 13: ... rotation run stop Reverse rotation run stop External failure Reset Multi speed instruction 1 Multi speed instruction 2 Multi speed instruction 3 Inching instruction Default settings The default setting is theindication of the completion of the preparation work ofAC motor driver Main analog quantity instruction 0 10V 4 7K Power supply for frequency setting 12V 20mA Brake resistor optional componen...

Page 14: ... Layout 2 EC5000 Installation and Wire Layout Note 1 SW1 Input signal selection switch V Voltage 0 10 V I Current 0 20mA 2 FV B14 0 voltage input SW1 to V factory default 3 FI B14 1 B15 1 current input SW1 to 1 PID open feedback signal terminal used in combination with SW1 2 4 2 Control Terminal Connections 1 Frequency set by an external analog input voltage command Value 0 10V DC 0 100 antiaction...

Page 15: ...the interference caused by the analog signal follower or the AC drive will lead to misoperation in such conditions the capacitor and the magnetic core of ferrite may be connected to the external analog follower as shown below Analog input terminals FS FV FI FC 22 23 FV FI FC C Go through in phase and encirle 3 loops or above Ferrite magnetic ring Input terminals of contact S1 S8 While controlling ...

Page 16: ...nstallation and Wire Layout EC5000 Installation and Wire Layout 24 25 The main wiring diagram of EACN AC DRIVE Motor KW Diameter of main wire mm Diameter of control wire mm Air breaker A Input Voltage KW Type 2 ...

Page 17: ... DC reactor Improve power factor and reduce AC pulse of DC bus EG For safty and small noise AC drives ground terminal EG should be well grounded R L1 S L2 T L3 Input end of commercial power supply single phase 3 phase AC drives output connected with 3 phase inductionmotor 15KW with brake component which is connected to terminal P1 PR To improve the brake moment of force an outside brake resistance...

Page 18: ...nal FWD REV or RUN STOP button on the control panel to start and stop AC drive If you must use main power supply ON OFF switch to start and stop do it no more than 1 time within one hour Do not connect the 3 phase power supply machine with the single phase power supply Output terminals of AC drive U T1 V T2 W T3 Connect AC drive output terminal to 3 phase motor according to correct phase order If ...

Page 19: ...the ground terminal E G is grounded well Confirm there is no short circuit within every terminal and electricitied naked part Confirm all terminals connection and joints are tight and not loose Ensure that the motor isn t connected with loaded machine Before turning the power on ensure that all the switches are in the disconnected state to guarantee that the AC drive won t start or operate abnorma...

Page 20: ...d setting the frequency 4 1 1Appearance of the Keypad Panel of Nixie Tube REV This LED indicator light will be on when the motor is in positive rotation FWD This LED indicator light will be on when the motor is in reverse rotation RUN This LED indicator light will be on when the motor is running 6 bit LED nixietubes display FAL This LED indicator light will be on when the frequency converter has f...

Page 21: ...id AC drive time select by Pr C31 total running or in power Control panel edition NO 0 1 2 3 4 5 6 7 8 9 10 11 LED dispaly F OUT 50 00 F SET 50 00 V OUT 380 0 A OUT 11 0 KVA 7 EDC 540 TEP 37 S1 8 111 Y1 Y4 11 HOU 103 VER 2 00 Item illustration Select data Pr A27 that needs amending Amending the content of Pr A27 Select and amended the twinkling digit Confirm data amended and exit plus manu Cancel ...

Page 22: ...l are arranged in the menu and sub menu and the general operation can be conducted in the following way Setting of main frequency of panel e g the main frequency is altered to 30 00Hz The frequency set The frequency set Press enter under the initial screen to the frequency setting screen In the frequency setting screen Press the keys to select the modify bit and change the frequency from 5 to 3 ac...

Page 23: ...function Users can not modify these parameters or view Only in the maintenance of the course or need to replace the control panel by the manufacturer to modify professionals S 7 0 Y2 0 S 8 0 Y3 0 Y1 0 Y4 0 S 1 1 X 4 0 S 2 0 X 5 0 S 3 1 X 6 0 Second screen 1 data setting Operations like parameter setting operation data maintenance information fault information data copy Under the initial screen pre...

Page 24: ... Default Page Address Accele ration and decele ration time setting A18 Acceleration time 1 A19 Deceleration time 1 A20 Acceleration time2 A21 Deceleration time2 Unit 0 1s 1s for 1000s and above Unit 0 1s 1s for 1000s and above Multi functional contact input selec tion or choose to accel time 2 in a stop method choice or internal con trol section s speed more effective same as A18 set Multi functio...

Page 25: ...2 Step 2 A43 Step 3 A44 Step 4 A45 Step 5 A46 Step 6 A47 Step 7 Example F 2 100 100 pace running time 100S 2 pace accelerate retard time 2 F pace motor running direction F is CCW R is CW Function Parameters Name Description Setting range Default Page Address JOG accele ration and decele ration time A48 JOG acceleration A49 JOG deceleration JOG acceleration time the max frequency 100 Unit 0 1S JOG ...

Page 26: ...ency test release width setting G P Selection B24 G P Selection 0 constant torque of G the coefficient of over load is 150 1min 1 fan type pumps of P the coefficient of over load is 120 1min Function Parameters Name Description Setting range Default Page Address Carrier frequency adjustment C01 Carrier frequency The setting value 1 2 4 6 The carrier frequency The setting value x 2 5KHz The setting...

Page 27: ... frequency D17 PID feedback value 2 The time exceed D18 The AC drive stops output and be in sleep mode D18 Stopping Time Function Parameters Name Description Setting range Default Page Address Constant pressure water supply parameters D19 Wake up standard The AC drive is in sleep mode When the water consumption is increasing the pressure of the pump will reduce accordingly When meet the following ...

Page 28: ...dard C24 is longer than testing time C25 over torque moment of force testing function works Function Parameters Name Description Setting range Default Page Address Input Output phase loss detection C26 Input phase loss detection level SPI Unit 1 When setting is 100 this function is disabled DC400V 200V grade and DC800V 400Vgrade to be 100 C27 Input phase loss detection delay time C28 Output phase ...

Page 29: ...age selection 0 Display Chinese 1 Display English Function Parameters Name Description Setting range Default Page Address Auxiliary function Pr F15 LED Display selection Only LED manipulator has this functional code 0 seven items for monitoring Fset Fout Vout Aout KVA EDC PID 1 increase two external terminals S1 8 and Y1 4 for monitoring the input and the output 2 increase three items for monito r...

Page 30: ...actory default 0 Special industry application A01 Data select setting limit 0 7 factory default 0 0 changeable data 1 fixed data user s data is ok it can be protected without change 2 6 reserve 7 initialization setting change to factory defaults If operator adjust the data with mistake just change data to press ENTER key to initialise all the data then reset A02 Control mode sel setting limit 0 1 ...

Page 31: ...requency frequency start of DC brake Deceleration tim Run instruction Stop the DC braking time ON OFF In running order OFF in right and opposite direction motor retards in retard time 1 A19 and brakes to stop by direct current If short brake time and big inertia capacity there will be over voltage OU error during retarding In such circumstances just extend retard time or install an optional brake ...

Page 32: ...oltage Calculate fixed V F mode voltage A10 A11 A15 A17 It is 2 times for 400V grade EC5000 SETTING3 slide to stop with second retard time Select increase decrease speed 2 example Deliver running order during retard to stop AC drive will not reaction AC drive will start only after retarding time is over But if retarding times is setting below Min BB time C04 running order during BB time is invalid...

Page 33: ...mits 50 00Hz 400 00Hz factory default 50 00Hz A12 Max voltage setting limits 0 1V 255 0V factory default 200 0V 1 A13 standard Fre setting limits 0 20Hz 400 00Hz factory default 50 00Hz A14 middle Fre setting limits 0 10Hz 399 99Hz factory default 3 00Hz A15 middle voltage setting limits 0 1V 255 0V factory default 12 0V 1 A16 lowest Fre setting limits 0 10Hz 10 00Hz factory default 1 50Hz A17 low...

Page 34: ...ng limits 0 00 Hz 400 00Hz factory default 0 00Hz A30 Frequency4 setting limits 0 00 Hz 400 00Hz factory default 0 00Hz A31 Frequency5 setting limits 0 00 Hz 400 00Hz factory default 0 00Hz A32 Frequency6 setting limits 0 00 Hz 400 00Hz factory default 0 00Hz A33 Frequency7 setting limits 0 00 Hz 400 00Hz factory default 0 00Hz Select multi pace frequency 1 7 by ON OFF combination of terminal func...

Page 35: ...A46 Step 6 mode setting limits F1 R4 0 4000S factory default F1 0S A47 Step 7 mode setting limits F1 R4 0 4000S factory default F1 0S Mode running inner simple PLC logic control 0 run according to common control way 1 inner control multi speed this mode stops after running for one week AC drive runs with the inner data step by step when run order is given It stop running automatically one week lat...

Page 36: ...peed order 1 SS1 Multi speed order 2 SS2 Multi speed order 4 SS4 Name Illustration Set 10 11 12 13 Jog running Accelerate retard time selection 1 RT1 Name Illustration Set 27 28 17 18 19 20 21 22 23 24 25 26 Searching order from max Fre Searching order from setting Fre Speed searching order signal Data setting permitted frobidden Select permitted forbidden set by digital operator or parallel commu...

Page 37: ... to running way selection A03 ON run according to the transmitted Frequency order and running order Set 9 10 11 Frequency set by external joint input terminal and multi Frequency pre set by A27 A29 Select 3 input terminal and their function data set to be 9 11 then multi frequency can be selected by ON OFF combination It can offer 8 target value easily through external terminal in OFF multi garge ...

Page 38: ... When input terminal is OFF the simulate Fre value is kept Set 27 UP DOWN order set B07 27 Only input the effective order the AC drive acclerate retard when input UP DOWN order to control circuit terminal S7 and S8 without changing Frequency order This makes AC drive runs at anticipated speed When UP DOWN order is appointed by B07 all the function set by data B06 is invalid and terminal S7 changes...

Page 39: ...23 factory default 2 B11 Terminal Y4 sel setting limits 0 23 factory default 3 BB base level blockade switch off when AC drive output is off running mode switch off when select panel operation or frequency order AC drive run ready switch off when AC drive has no error and can run timer function automatic restart switch off during error and restart Ol overload alarm Frequency Given lost transmissio...

Page 40: ...election of given current input 0V 4mA 10V 20mA Setting 3 setting example of any frequency unamious signal EC5000 Detection width output frequency Expected consistent frequency signal Released width Detection result of expected frequency ON 2HZ B26 B12 ON delay setting limits 0S 25 5S factory default 0 0S B13 OFF delay setting limits 0S 25 5S factory default 0 B14 main simulate value setting limit...

Page 41: ...3V 3V 0 3 B21 SET VALUE B22 frequency test setting limit 0 00Hz 400 00Hz factory default 0Hz B23 FAR value setting limit 0 00Hz 25 00Hz factory default 2Hz It is valid when multi function joint input set to be Fre test set value 4 OR 5 Frequency test frequency test is functioning when output frequency is over or lower than frequency test standard B22 FAR value frequency test release width Examples...

Page 42: ... 2 5KHz 83 3Hz 208 3Hz 1 0KHz 2 5KHz 41 8Hz 104 1Hz 1 0KHz 2 5KHz 27 7Hz 69 4Hz Notice EC5000 B22 2Hz ON ON Discharge rate Output frequency Frequency detection signal Detection result of frequency 0 constant torque of G the coefficient of over load is 150 1min 1 fan type pumps of P the coefficient of over load is120 1min When change this parameters C18 will change following this When 0 change to 1...

Page 43: ...ff Notice C03 SpdSrch Current setting limits 0 200 factory default 110 C04 Min Baseblock t setting limits 0 5S 5 0S factory default 3 This order restart the sliding motor This function enable motor to shift smoothly between working frequency and inverted frequency Search speed search speed is setting current grade AC drive rated current is 100 Block time during speed searching set in dealing insta...

Page 44: ...pensation factory setting C12 1 0 Rotation moment of force need to be adjusted when connection wire between AC drive and motor is too long or motor vibrating Increase compensation to increase motor moment of force But there will be problems if increase too much AC drive run in unstable status because of motor over current Motor overheat or vibration Check motor current when increasing moment of fo...

Page 45: ...st grade with unit of 1 AC drive rated C28 SPO standard setting limits 1 100 factorydefault 0 Over rotation moment of force test standard set over rotation moment of force testing current standard with unit of 1 C24 rotation moment of force standard setting limits 30 200 0 factory default 160 current to be 100 EC5000 Electronic overheat protection is monitoring motor temperature to protect it form...

Page 46: ...0 10 select A03 to be 2 or 3 to set running direction 2 frequency order data A27 A34 select A03 to be 0 or 1 to set running direction combination of multi function joint multi pace speed order and jog start order Set feedback value Use current signal 4 20mA or voltage signal 0 10V of control circuit terminal to set feedback value 1 Current signal of control circuit terminal FI select B15 to be 1 t...

Page 47: ...e the pump control D13 Rotation time setting limits 0 10000min factory default 60min When the two auxiliary pumps only one work in order to average the time of working for every pump the working time for one pump is D13 and then change to work another one D14 Interlock time setting limits 0 250S factory default 5S This is the time of the two auxiliary pumps all stopping D15 High speed working sett...

Page 48: ... lower limit value Frequency 6HZ 255V E03 E04 60HZ For 400V grade this value is 2 time of 200V Notice Set average power calculating time in energy saving mode E05 calculating time setting limits 1 200 factory default 1 E06 voltage limits value setting limits 0 100 factory default 0 E07 100 anti jump setting limits 0 1 10 0 factory default 0 5 E08 5 anti jump setting limits 0 1 10 0 factory default...

Page 49: ...L REMOTE key function invalid 1 LOCAL REMOTE key function valid F08 L R function setting limits 0 1 factory default 0 0 When LOCAL REMOTE shifting re run is valid when stop order is inputed 1 When LOCAL REMOTE shifting re run is valid at once F09 L R sellection setting limits 0 1 factory default 0 F10 enter key setting limits 0 1 factory default 1 0 STOP key is always valid in any operating mode 1...

Page 50: ...efault 0 Set the input voltage of the AC drive According to this set value the AC drive can switch the voltage protection level 0 Free running 1 Running at A16 start freq 2 Running at Zero speed F17 Zero speed increase Pr_F16 setting limits 0 100 factory default 50 According to the rating current of 100 set the output current at zero speed F18 Motor tuning Pr_F17 setting limits 0 2 factory default...

Page 51: ...ly factory default NC G02 fault history2 setting limits read only factory default NC G03 fault history3 setting limits read only factory default NC G04 fault history4 setting limits read only factory default NC G05 fault EDC setting limits read only factory default NC G06 fault voltage setting limits read only factory default NC G07 fault current setting limits read only factory default NC G08 fau...

Page 52: ...CII codes twenty data LRC CHK Hi LRC CHK Lo LRC Check Code 8 bit check code consisting of 2 ASCII codes END Hi END Lo Ending Character END Hi CR 0DH END Lo LF 0AH 6 1 Communication Data Structure EC5000 1 7N2 For ASCII F03 0 7 data bits Character String 10 bits Character Frame Length Start bit 0 1 2 3 4 5 6 Stop bit Stop bit 2 7E1 For ASCII F03 1 Even parity 7 data bits Character String 10 bits Ch...

Page 53: ...n 03H Number of data count by byte 04H 17H Content of data address 001DH 70H 00H Content of data address 001EH 00H CRC CHK Low FEH CRC CHK High 5CH 6 2 2 Function Code Function and Data Content Data Characters 03H Read the register 06H Write data to the register 08H Loop detection 10H Write several data in succession 03H Read several data to register Function Code 03H Read register maximally twent...

Page 54: ... 00H 17H Data 70H CRC CHK Low 8EH CRC CHK High 0EH ADR 01H CMD 08H 00H Data 00H 17H Data 70H CRC CHK Low 8EH CRC CHK High 0EH Function Code 06H Write data to register For example as for Driver with Address 01H write 6000 1770H to the internal setting parameter of driver 001DH 1 ASCII Mode Inquiry Message Format Response Message Format 2 RTU Mode Inquiry Message Format Response Message Format Addre...

Page 55: ... first 8 bit byte message instruction and lower 16 bit CRC register and save the value obtained to CRC register Step 3 Right Shift CRC register and set the most significant bit with 0 ADR 01H CMD 10H 00H Data Starting Address 1DH 00H Data Quantity Word 02H Data 04H 13H First Data 88H 0FH Second Data A0H CRC Check Low B2 CRC Check High 1C 1 ASCII Mode Inquiry Message Format Response Message Format ...

Page 56: ...register or Exclusive OR A001H and CRC register and then save the result to CRC register Step 5 Repeat Step 3 Step 4 finish the operation of all 8 bit Step 6 Repeat Step 2 Step 5 take the next 8 bit message instruction until all message instructions have been calculated Finally the CRC register value is the check code of CRC Note The check code of CRC must be put in the check code of message instr...

Page 57: ...for input when the frequency input 2103H Bit13 15 Reserved 2104H Setting Frequency 2105H Output Frequency 2106H Output Current 2107H Output Voltage 2108H Output Power 2109H EDC Voltage 210AH PID Feedback 210BH Radiator Temperature 210CH ROM Version 210DH L Fault History1 210DH H Fault History2 210EH L Fault History3 Monitoring of AC Drive Status 210EH H Fault History4 Definition Parameter Word Add...

Page 58: ...ng Bit6 7 Reserved Monitoring of AC Drive Status 2103H Bit8 Running Mode Bit0 Definition Parameter Word Address Function Description Definition Parameter Word Address Function Description 0FH EF2 010H EF3 012H EF4 013H EF5 014H EF6 015H SP 016H Spo 017H CE 018H rr 019H Rh 2100H 01AH oPr Pre warning Code Bit0 UuWarning Bit1 ouWarning Bit2 OH1Warning Bit3 OL3Warning Bit4 BBWarning Bit5 EFWarning Bit...

Page 59: ...rolong accelerating time EFLn Error from RS485 general data wire Error in control circuit Check external control circuit 7 1List of Actions to Protect 7 1 1 List of Fault Display EC5000 Low voltage in main circuit Low voltage of main circuit during running Test voltsge about 190V or lower for 200V grade 380V or lower for 400V grade Low voltage in control circuit Low voltage of control circuit duri...

Page 60: ...ct continue running when RS485 transmission error data transmition break down Main circuit EDC voltage surpass overvoltage test standard when AC drive stops display Content illustration Uu OH1 Ol3 BB EF CALL OH3 CE OU EC5000 EF2 8 Error from terminal RS485 general data wire Error in external control circuit Check the input external if the error happen in the terminal is unconnect change the AC dri...

Page 61: ...e power line 2 Environment setup measures AC drive is a device made up of electronic parts and its admissible environment is described in the specifications in detail If the regulations EC5000 114 115 The diagnosis and the exclusion for the abnormalities 7 7 3 The Causes and Solutions for AC Drive s Faults Notice EC5000 The setting of the input multifunction function is incorrect V F data setting ...

Page 62: ...e electronic parts rust and bad contact and what s more insulation will be decreased due to moisture absorption and cause short circuit accidents Regular measure is treating with paint and dust proof and in strict conditions inner pressure suited for clean air or self protective whole sealing structures are adopted 3 The temperature of the around environment should be appropriate the life span and...

Page 63: ...well as cooling fans and relays and so on These parts aren t permanently durable and cannot be used forever Even if used under normal environment once the life period has exceeded faults are easily to occur Therefore preventive periodic check is necessary in order to find out the parts with poor quality or those fall short of the standard and eliminate the causes for AC drive malfunction At the sa...

Page 64: ...urn with hand must cut off the power Please wipe the pollutional areas with chemically neutral cleaning cloth Sweep the dust with electric cleaner Notice With eye survey With eye survey Is it stained with dust or defacement Is there distortion crack to overheat and aging in the machine and insulation damage or color changedue EC5000 Inspection Items Inspection Method Spot Check Period Cheeck site ...

Page 65: ... 1 0 3 2 0 4 EC50D75G23 0 75 3 7 2 0 6 4 6 17 5 0 75 3 7 EC501D5G23 1 5 5 5 18 5 11 30 55 2 4 9 1 29 18 47 82 8 25 80 49 130 224 1 5 5 5 18 5 11 30 55 EC502D2G23 EC503D7G23 EC505D5G23 EC507D5G23 EC50011G23 EC50015G23 EC518D5G23 EC50022G23 EC50030G23 EC50037G23 EC50045G23 EC50055G23 EC50075G23 2 2 7 5 22 45 15 37 75 3 7 12 35 67 23 58 109 11 33 96 183 64 160 300 2 2 7 5 22 45 15 37 75 Model Input V...

Page 66: ... Overload Protection Electronic thermal overload relay protection Performance EC5000 Appendix 124 125 Appendix A 2 Product Technical Indexes 9 EC5000 Appendix Model Input Voltage Power G P KW Output Capacity KVA Output Current G P A Suited Motors G P KW Three Phase 400V 50Hz Three Phase 400V 50Hz Three Phase 400V 50Hz Three Phase 400V 50Hz Three Phase 400V 50Hz Three Phase 400V 50Hz Three Phase 40...

Page 67: ...en the output voltage of rectifier drops down to 190V 200V grade 380V 400V grade or lower Instantaneous Power Failure Compensation Instant stop when instantaneous power failure lasts for 15ms or longer Default setting According to standard setting if the power failure is shorter than 2 seconds continue operation Heat Radiator exceeds 105 Speed Loss Protection Speed loss protection during accelerat...

Page 68: ...tallation Dimension Drawing Structure70 EC50075G0090P43B EC50090G0110P43B Structure80 EC50110G0132P43B EC50132G0160P43B Structure90 EC50160G0185P43B EC50185G0220P43B EC50220G0250P43B StructureA0 EC50250G0280P43B EC50280G0315P43B EC50315G0350P43B EC50350G0400P43B 128 129 9 ...

Page 69: ...50P43B EC50450G0500P43B EC50500G0560P43B EC50560G0630P43B Appendix B 3 Braking Resistor Braking Resistor Selection schedule AC Drive Model Resistor Specifications Power W Braking Torque Suited Motor KW Model G Suited Motor KW Model P Resistance Ω 130 131 9 ...

Page 70: ...al potentiometer terminals A B C usually choose 5 10K potentiometer we can adjust terminal C to judge the potentiometer Use the resistance of the multimeter to measure any two terminals A B C the biggest resistance is terminal A B the left one is the terminal C which can judge the potentiometer 2 Parameter setting Choose the operation mode A03 2 the max frequency A11 the corresponding frequency of...

Page 71: ...n frequency of the panel and the external terminals at the start LED panel When F12 0 the frequency is setted by A27 B01 1 choose the operation mode A03 1 F23 2 When F12 1 the frequency is setted by panel potentiometer B01 1 A03 1 F23 2 LCD panel B S2 A S1 SC Forward run Reverse run 1 2 The frequency is setted by A27 B01 1 A03 1 F23 2 3 Action description When trigger S1 the inverter starts trigge...

Page 72: ...fter purchase Product failure and damage caused by obstacles other than products such as external equipment factors Product failure and damage caused by gas corrosion salt corrosion metal dust and requirements of the user manual 4 In case of any fault or damage to the product please fill in the contents of the warranty card correctly 5 The service fee shall be calculated accroding to the actual co...

Reviews: