9) End of Line Monitoring (DC Units)
All DC units have a blocking diode fitted in their supply input
lines. An end of line monitoring diode or an end of line
monitoring resistor can be connected across the +ve and
–
ve
terminals in the flameproof chamber. If an end of line resistor
is used it must have a minimum resistance value of 3k3 ohms
and a minimum wattage of 0.5W or a minimum resistance
value of 500 ohms and a minimum wattage of 2W.
The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor
leads should be kept as short as possible. See D190-06-201
for details.
Figure 10: End of Line Resistor placement.
10) Interchangeable & Spare Parts
The beacon lens is interchangeable, contact European Safety
Systems Ltd for a replacement lens available in various
colours.
The guard is an integral part of the protection and must be
reassembled exactly the same way as it was disassembled.
To change the lens, unscrew the M5 socket head screws and
remove the M5 screws, M5 spring & flat washers.
Figure 11: Removal of Lens.
Remove the guard and replace the old lens with the new lens.
Figure 12: Changing of Lens
Fit the guard back on to the lens and casting, align the holes
of the guard, lens and casting. To reattach the lens, the fixings
MUST be in the order shown in figure 13.
Figure 13: Lens & Guard Fixings Order.
11) Maintenance, Overhaul and Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19/IEC60079-19
Explosive atmospheres
–
Equipment repair, overhaul and
reclamation
EN 60079-17/IEC60079-17
Explosive atmospheres
–
Electrical installations inspection
and maintenance
Flameproof threaded joints and cemented joints are not
permitted to be repaired.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.
Potential electrostatic charging hazard - Clean only with a
damp cloth.
Warning
–
Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.