warning signals
2S
ALERTALARM RANGE
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
DATE
APPROVED
CHECKED
DATE
DATE
DRAWN
WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL
SHEET
SCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
10
9
G
F
E
7
8
6
5
D
C
1
3
4
2
A
B
D190-06-201
R.S.RAIT
B.ISARD
R.N.POTTS
OF
NTS 1
Stage 1 +ve IN
Stage 1 +ve OUT
Common -ve IN
Common -ve OUT
Stage 2 +ve
Stage 1 +ve IN
Stage 1 +ve OUT
Common -ve IN
Common -ve OUT
Stage 2 +ve
Stage 3 +ve
WIRING LINKING BEACON & SOUNDER
FACTORY FITTED
6
-
+
-
+
-
+
R1
+
-
-
+
R1
+
-
-
+
S2
S3
R1
+
-
-
+
S2
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
RECOMMENDED MINIMUM VALUES:
R1
Stage 1 +ve IN
Stage 1 +ve OUT
Stage 1 -ve IN
Stage 1 -ve OUT
Single Stage Configuration
Config.: 1a
Line Monitoring
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Two Stage Configuration
Config.: 1b
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve & Common -ve
Three/Four Stage Configuration
Config.: 1c
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve & Common -ve
Stage 3: Apply Power to Stage 3 +ve & Common -ve
Stage 4: Apply Power to Stage 2 +ve, Stage 3 +ve & Common -ve
Linked Sounder & Beacon Activation (Default)
MOD No.
REASON - INITIAL - DATE
ISSUE
+
-
+
-
+
-
+
-
+
-
+
-
INTRODUCTION
1
RSR - 19/01/2021
19/01/2022
19/01/2022
19/01/2022
D1xC1X / D1xC2X / STExC1X DC SOUNDER /
XENON WIRING DIAGRAMS