7.3. Cable Glands, Blanking Elements & Adapters 

 
Follow the minimum temperature ratings of cables and cable 
glands according to the approvals applied. 

 
ATEX / IECEx & UKEx Requirements

 

 
For  high  ambient  temperatures  the  cable  entry 
temperature  may  exceed  70ºC  or  the  cable  branching 
point  temperature  may  exceed  80ºC  and  therefore 
suitable heat resisting cables and cable glands must be 
used, with a rated service temperature at least as stated 
below: 

 

 

Table 2: ATEX / IECEx & UKEx Min. Ratings of Cables & 

Cable Glands. 

 

NEC / CEC Requirements Only 
 
For  high  ambient  temperatures  the  cable  entry 
temperature  may  exceed  60ºC  or  the  cable  branching 
point  temperature  may  exceed  60ºC  and  therefore 
suitable heat resisting cables and cable glands must be 
used, with a rated service temperature at least as stated 
below: 

 

 

Table 3: NEC / CEC Min. Ratings of Cables & Cable Glands. 

 

Cable Glands & Blanking Plugs 

 

Appropriate cable glands to be customer supplied. 

 

ATEX / IECEx & UKEx Requirements Only 
 
The cable entries have an M20 x 1.5 – 6H entry thread. 
Only suitably rated and ATEX / IECEx & UKEx certified 
cable glands must be used. They must be suitable for the 
type of cable being used and also meet the requirements 
of  the  current  installation  standards  EN  60079-14  / 
IEC60079-14. 

 

If the installation is made using conduit, openings must 
have a sealing fitting connected as close as practical to 
the wall of the enclosure, but in no case more than the 
size of the conduit or 50mm, whichever is the lesser. 

 
Any unused cable entries must be closed with suitably 
rated and ATEX / IECEx & UKEx certified blanking plugs. 
 
NEC / CEC Requirements Only 
 
The cable entries have an M20 x 1.5 – 6H entry thread. 
If  the  installation  is  made  using  cable  glands,  only 
suitably rated and certified cable glands must be used. 
They must be suitable for the type of cable being used 
and  also  meet  the  requirements  of  the  current  NEC  / 
CEC installation standards. 
 
If the installation is made using conduit, openings must 
have a sealing fitting connected as close as practical to 
the wall of the enclosure, but in no case more than the 
size of the conduit or 50mm, whichever is the lesser. 
 
For  use  in  Class  I  Division  II  locations,  in  order  to 
maintain the db type protection, flameproof conduit seals 
and/or cable glands must be used. 
 
Any unused cable entries must be closed with suitably 
rated and certified blanking plugs. 

 

Ingress Protection 

 
Follow instructions according to the approvals applied. 
 

ATEX / IECEx & UKEx Requirements Only 
 
If a high IP (Ingress Protection) rating is required, then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 
 
For combustible dust applications, the cable entry device 
and  blanking  elements  shall  be  in  type  of  explosion 
protection and shall have an IP 6X rating. 
 
NEC / CEC Requirements Only 
 
If a high IP (Ingress Protection) rating is required then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 

 

Adapters 

 
The STEx Beacon Range can be supplied with the following 
types of adapters: 
 

M20 to 1/2” NPT 
M20 to 3/4” NPT 
M20 to M25 

 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated and

 

certified 

adapters. 
 
 
 
 
 
 
 
 
 

Summary of Contents for STExB2X05

Page 1: ...4Vdc 145mA 150mA STExB2X05AC115 115Vac 110 120Vac 50 60Hz 140mA 200mA STExB2X05AC230 230Vac 220 240Vac 50 60Hz 70mA 100mA STExB2X10DC024 24Vdc 20 28Vdc 605mA 710mA STExB2X10DC048 48Vdc 42 54Vdc 230mA...

Page 2: ...C Db Ta 50 C to 70 C STExB2 X10AC115 X10AC230 Ex db IIC T4 Gb Ta 50 C to 70 C Ex tb IIIC T128 C Db Ta 50 C to 70 C STExB2 X15DC024 X15DC048 Ex db IIC T4 Gb Ta 50 C to 70 C Ex tb IIIC T127 C Db Ta 55...

Page 3: ...Suitable The certification approval has validated continuous use up to 38 C ambient and are for transient use up to 70 C ambient Installation must be carried out in compliance with the National Elect...

Page 4: ...unit STExB2X21 models shall not be mounted with the lamp down The STEx beacons should be securely bolted to a flat surface using 9 0mm diameter bolt holes in the base of the unit See figure 2 Figure...

Page 5: ...rical engineer who has the necessary training 7 2 Cable Selection and Connections When selecting the cable size consideration must be given to the input current that each unit draws see table 1 the nu...

Page 6: ...certified blanking plugs NEC CEC Requirements Only The cable entries have an M20 x 1 5 6H entry thread If the installation is made using cable glands only suitably rated and certified cable glands mu...

Page 7: ...a minimum resistance value of 3k3 ohms and a minimum wattage of 0 5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W The resistor must be connected directly across the ve and ve...

Page 8: ...nd any dust layer removed prior to opening the unit Repair of the flameproof threaded joints and cemented joints is not permitted Potential electrostatic charging hazard Clean only with a damp cloth 1...

Page 9: ...Page left Intentionally blank...

Page 10: ...R DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT S...

Page 11: ...NGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO...

Page 12: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Page 13: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 14: ...0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T85 C T137 C Db IP6...

Page 15: ...nd Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Page 16: ...Page left Intentionally blank...

Reviews: