Zone 1 

explosive gas air mixture likely to occur in 
normal operation. 

 

Zone 2 

explosive gas air mixture not likely to occur, 
and if it does, it will only exist for a short time. 

 

Be used with gases in groups: 

 

 

 

Group A 

Propane 

 

Group B 

Ethylene 

 

 

Having a temperature class of: 

 

T1 

450ºC 

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

T5 

100ºC  (Pi 

 600mW) 

T6 

  85ºC  (Pi 

 300mW) 

 
If the IS-pA1 sounder is installed in an aplication requiring 
temperature class  of T5 or T6, the safety parameter Pi is 
reduced as shown above. 

 
2.3  Terve and -ve 

Power is supplied to the sounder via the +ve  and  –ve 
terminals which have the following input safety parameters: 
 
 

Ui 

40V 

 

Ii 

660mA 

 

Pi 

 

1.3W     (T4) 

 

 

 

 

600mW (T5) 

 

 

 

 

300mW (T6) 

 
 

Ci = 32.5nF  Li = 0 

 
The IS-pA1  sounder  must  be powered from an  ATEX  or 
IECEx  certified  zener barrier or galvanic isolator  having 
output parameters  equal to or less than 40V, 660mA and 
1.3W(T4) / 600mW(T5) / 300mW(T6), The cable parameters 
stated on the selected zener barrier or galvanic isolator 
certificate must be observed. 
 
 

3)  Installation 
 

IS-pA1  sounders should only be  installed by trained 
competent personnel. 

 
3.1 Mounting and Wiring

 

The  IS-pA1  panel mount sounder is design to be mounted 
into a 28mm diameter hole in a control panel. The control 
panel must have an IP rating suitable for the environment into 
which it is being installed. 
 
Electrical connections to the sounder are made using 6.3mm 
insulated spade connectors to the rear of the unit. 
 

  

 

4)  Electrical System Design For Installation In 

Hazardous Areas Using Zener Barriers

 

 
The  IS-pA1 sounder may be powered by a zener barrier 
having output parameters within the limits specified in section 
2.3, which has been certified Ex ia by an accredited Notified 
Body.  If the control switch is in the positive supply, or the 
power supply is being turned on and off, only a single 
channel zener barrier is required as shown in Fig 1. This 
circuit may also be used if the sounder is being controlled by 
a mechanically activated switch on the hazardous area side 
of the barrier. 

 

Safe Area

Hazardous Area

+

-

0V

+

Power
Supply

Barrier

On/Off

28V 93mA

Positive

IS-pA1

Sounder

 

Fig 1  Zener barrier. 

 
 

5)  Electrical System Design For Installation In 

Hazardous Areas Using Galvanic Isolators

 

 

Galvanic isolators  do not require a high integrity earth 
connection. For small systems where a high integrity earth is 
not already available, the use of galvanic isolators often 
reduces the overall installation cost and simplifies design. 

 

The IS-pA1 sounder may be powered by any galvanic isolator 
having output parameters within the limits specified in section 
2.3, which has been certified Ex ia by an accredited Notified 
Body.  The sounder may be controlled by turning the galvanic 
isolator on and off, or by a mechanically activated switch on 
the hazardous area side of the isolator. 

Safe Area

Hazardous Area

+

-

-

+

Galvanic 
Isolator

Power

IS-pA1

Sounder

 

Fig 2  Galvanic isolator. 

 

 