European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. D202-00-001-IS           Issue 1        25-04-2022                         Sheet 5 of 7                                                                                            

 

capacitance of 6.33pF according to EN/IEC60079-0, clause 
7.5. 
 
Caution do not change factory applied finishes 
 
NEC / CEC Installations: 
 
The equipment must only be installed by suitably qualified 
personnel in accordance with the latest issues of the relevant 
standards: 
 
The installation of the units must also be in accordance with 
any local codes that may apply and should only be carried 
out by a competent electrical engineer who has the 
necessary training. 
 
The equipment must not be installed with any obstruction to 
the flanged flameproof joint any closer than permitted as per 
the NEC/CEC. 
 
For high ambient temperatures the cable entry temperature 
may 60ºC or the cable branching point temperature 
may exceed 60ºC and therefore suitable heat resisting cables 
and cable glands must be used, with a rated service 
temperature of at least the values stated below: 
 
For Single Switch model GNExCP7-BG-S: 

Max. 
ambient 
temperature 
ºC 

35 40 45  50 55 60 65 70 

req. Cable / 
Cable 
Gland 
rating: ºC 

61 66 71  76 81 86 91 96 

 
For Dual Switch model GNExCP7-BG-D: 

Max. 
ambient 
temperature 
ºC 

20 25 30 35 40 45 50 55  60  65  70 

req. Cable / 
Cable 
Gland 
rating: ºC 

60 65 70 75 80 85 90 95 100 105 110 

 
For use in Class I Division II locations, in order to maintain 
the db type protection, flameproof conduit seals and/or cable 
glands must be used. 
 
The cable gland entries have an M20 x 1.5 entry thread. Only 
suitably rated and certified cable glands which must be 
suitable for the type of cable being used and also meet the 
requirements of the current Ex ‘db’ and Ex ‘tb’ flameproof and 
NEC/CEC installation standards (tightening torque 10Nm). 
 
When only one cable entry is used the other entries must be 
closed with suitably rated and certified blanking plugs that 
meet the requirements of the current Ex ‘db’ and Ex ‘tb’ 
flameproof and NEC/CEC installation standards (tightening 
torque 10Nm). 
 
All Installations: 
 
To access the Ex d chamber, remove the four off M6 x 60 
stainless steel A4-70 Cap Head cover bolts. 
 
If the installation is made using conduit, openings must have 
a sealing fitting connected as close as practical to the wall of 
the enclosure, but in no case more than the size of the 
conduit or 2” of enclosure, whichever is the lesser. 

 
Electrical connections are to be made into the PCB / terminal 
blocks / DIN rail provided. 
 
Internal earthing connections should be made to the Internal 
Earth terminal on the PCBA. The earth conductor should be 
at least equal in size and rating to the incoming power 
conductors. 
 
On completion of the installation the flameproof joint surfaces 
should be inspected to ensure that they are clean and that 
they have not been damaged during installation. Flamepaths 
are not intended to be repaired. 
 
When fitting the flameproof cover ensure the cover is sitting 
flat and correctly positioned on the base. Insert the M6 x 60 
stainless steel A4-70 Cap Head cover bolts and fully tighten 
down (tightening torque 3.5Nm), ensuring no gap is visible 
between the cover and base of the enclosure.   
 
If a high IP (Ingress Protection) rating is required then a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. 
 
The enclosure is non-conducting and may generate an 
ignition-capable level of electrostatic charges under certain 
extreme conditions. The user should ensure that the 
equipment is not installed in a location where it may be 
subjected to external conditions that might cause a build-up 
of electrostatic charges on non-conducting surfaces.  

 

The M12 Cap fitted to the top side of the unit is not a user 
serviceable part and must not be removed during installation 
and maintenance. 
 
The GNExCP7 Call Point range can be supplied with the 
following types of adapters: 
M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 

It is important to note that stopping plugs cannot be fitted 
onto adapters, only directly onto the M20 entries. 

 

Any other adapters used must be suitably rated and ATEX / 
IECEx / UKEx or NEC/CEC certified adapters. 
 
 
 

12) Cable & Wiring Connections 

 
Wiring methods shall be in accordance with CSA C22.1, 
Canadian Electrical Code, Part I, Safety Standard for 
Electrical Installations, Section 32; and CAN/ULC-S524, 
Standard for Installation of Fire Alarm Systems. 
 
The units come with two options for the terminal block. 
A DIN rail version which has 8-way connection and allows for 
limited wiring of EOL devices, or a 6 Way terminal block. 
 
The PCB Terminal Version has a 6-way connector but is 
designed to allow for full configuration with Series and EOL 
devices in a number of wiring configurations. 
 
For full wiring details see wiring diagrams D202-06-211 
 
For EOL and Series device limitations and configurations see 
Section 15. Fitting can be requested by E2S at the order 

Summary of Contents for GNE CP7-BG-D Series

Page 1: ... 1 0A Max 24Vdc Max 3 33A Max Class Div Zone 5 0 Max ATEX IECEx UKEx Table 1 Electrical Ratings 2 Warnings WARNINGS USE COVER BOLTS CLASS A4 70 DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS FOR INDOOR OR OUTDOOR USE TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES CONDUIT RUNS MUST HAVE A SEALING FITTING CONNECTED WITHIN 2 INCHE...

Page 2: ...to 70 C Class Zone Ratings for US NEC Model No Rating GNExCP7 BG S Class I Zone 1 AEx db IIC T6 Gb Ta 55 C to 70 C Zone 21 AEx tb IIIC T110 C Db Ta 55 C to 70 C GNExCP7 BG D Class I Zone 1 AEx db IIC T5 Gb Ta 55 C to 70 C Class I Zone 1 AEx db IIC T6 Gb Ta 55 C to 65 C Zone 21 AEx tb IIIC T135 C Db Ta 55 C to 70 C Class Zone Ratings for Canada CEC Model No Rating GNExCP7 BG S Ex db IIC T6 Gb X Ta ...

Page 3: ...sive dust atmospheres 5 Specific Conditions for Safe Use The stainless steel lift flap is not earthed and may generate an ignition capable level of electrostatic charges It has a max capacitance of 6 33pF according to CSA C22 2 NO 60079 0 UL 60079 0 2017 clause 7 5 or EN IEC60079 0 clause 7 5 Equipment is permitted to be wall mounted only in vertical position The enclosure base is permitted in two...

Page 4: ...tion of Cable Cable Glands Blanking Elements Adapters ATEx IECEx UKEx Installations The equipment must only be installed by suitably qualified personnel in accordance with the latest issues of the relevant standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive g...

Page 5: ...d as close as practical to the wall of the enclosure but in no case more than the size of the conduit or 2 of enclosure whichever is the lesser Electrical connections are to be made into the PCB terminal blocks DIN rail provided Internal earthing connections should be made to the Internal Earth terminal on the PCBA The earth conductor should be at least equal in size and rating to the incoming pow...

Page 6: ... sectional areas such as 2 5mm 13 Testing unit operation The break glass unit can be tested without the need to break replace the frangible glass element A test key Plastic Key Supplied with unit is used to mechanically drop the glass down activating the switch The test key is inserted in the test cam and rotated clockwise by an angle of 90º the glass element will visibly drop down in the viewable...

Page 7: ...The following table 2 shows limitations for all possible variations EOL End of line device resistor ExxxR diode ED1 zener ExxxZ Series In line device resistor SxxxR diode SD1 zener SxxxZ LED Microswitch 1 M S 1 Microswitch 2 M S 2 Table 2 EOL and Series Devices limits The unit can be wired with a maximum of 4 module devices see wiring diagram D202 06 211 Note The maximum voltage stated must not be...

Page 8: ...in Operated condition Terminals 4 5 7 8 closed Terminals 4 5 6 open COM N O N C EOL SER NOTE These can be fitted either by customer or pre installed by E2S at point of order When fitting diodes or zener diodes polarity across devices must be observed Resistor polarity is unimportant SERIES EOL Wiring option shown with EOL series devices acting in parallel 3A Circuit as shown in Unoperated conditio...

Page 9: ... 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 COM N O N C COM N O N C COM N O N C COM N O N C Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condit...

Page 10: ... M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condition Terminals 1 4 M S 1 and 5 8 M S 2 closed Terminals 1 3 M S 1 and 5 7 M S 2 open N C N O COM N C SER EOL SER EOL 4A Circuit as shown in Unoperated condition Ter...

Page 11: ...1 2 3 1 2 3 M S 1 M S 2 5B Circuit as shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed R N POTTS Optional Single or Double Microswitch Circuit shown with Double Microswitch Unit un operated GNExCP7 PCB Version Devices selected only as example On M S 1 Series resistor and EOL Zener diode On M S 2 EOL resistor with no series device GNExCP7 S...

Page 12: ...quipment II 2G Ex d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use ...

Page 13: ... d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain hazard...