European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D211-00-671-IS
Issue 3
20-08-22
Sheet 6 of 8
14) Electrical Ratings
14.1
Operating current Consumption
Table 6 – Electrical Ratings
Model
Nom.
Voltage
Voltage
Range
Flash Rate Setting
Nom. operating
current
#
Max. operating
current
##
Beacon
Sounder
Beacon
Sounder
D2xC2LD3DC024
24Vdc
Regulated
(16-33Vdc)*
Flashing 1Hz
153mA
250mA
465mA
250mA
Flashing 1.33Hz
189mA
488mA
Flashing 1.5Hz
203mA
456mA
Flashing 2Hz
248mA
528mA
* For Public Mode or private mode Fire Alarm or General Signaling use
# nominal rms current at nominal voltage
## max. rms current at worst-case voltage in voltage range.