background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-671-IS

 

Issue 3

 

20-08-22

 

 

Sheet 4 of 8

 

 

- -          + +    

External 
Earth  

Internal 
Earth  

2-off ½” NPT thread & 1-off ¾” NPT thread 
 
If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. 
For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 
For  use  in  explosive  gas  atmospheres,  a  minimum  ingress 
protection rating of IP54 must be maintained. 
 
NPT plugs should be greased before insertion. 
 

8)  Cable Connections 

 

Electrical connections are to be made into the terminal blocks 
on the PCBAs located in the enclosures. See section 6 of this 
manual for access to the enclosures.  
 
The Sounder and Beacon are supplied connected by default. 
In order to power the beacon and sounder separately, the link 
wires between the units must be disconnected. 

 

Wires  having  a  cross  sectional  area  between  0.5  mm²  to 
2.5mm²  can  be  connected  to  each  terminal  way.  If  an  input 
and  output  wire  is  required  the  2-off  +/-  terminals  of  the 
beacon  or  3-off  +/-  terminals  of  the  sounder  can  be  used.  If 
fitting  2-off  wires  to  one  terminal  way  the  sum  of  the  2-off 
wires  must  be  a  maximum  cross  sectional  area  of  2.5mm². 
Strip  wires  to  8mm.  Wires  may  also  be  fitted  using  ferrules. 
Terminal screws need to be tightened down with a tightening 
torque  of  0.56  Nm  /  5  Lb-in.  When  connecting  wires  to  the 
terminals great care should be taken to dress the wires so that 
when the cover is inserted into the chamber the wires do not 
exert  excess  pressure  on  the  terminal  blocks.  This  is 
particularly  important  when  using  cables  with  large  cross 
sectional areas such as 2.5mm². 
 

9)  Wiring  

 

The beacon  is  powered  via  factory  installed  wires  connected 
to  the  alarm  horn.  The  wires  connecting  the  alarm  horn  and 
strobe can be removed if the user wishes to power the strobe 
separately.  For  further  wiring  schematics  refer  to  document 
D211-06-651 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 4 Terminals

 

 

 

 

 

 

 

10)  Earthing 

 

The  beacon  bas  has  both  internal  and  external  earth  points, 
(please see fig 5). The sounder PCBA also has earth terminals, 
(see fig 4). 
Internal  earthing  connections  should  be  made  to  the  internal 
earth  point  on  the  beacon,  (please  see  fig  5).  The  earth 
conductor  should  be  at  least  equal  in  size  and  rating  to  the 
incoming  power  conductors.  The  internal  earth  bonding  wires 
connect the covers to the internal earth points in the bases. 
 
External  earth  connections  should  be  made  to  the  M5  earth 
stud,  using a  ring  crimp  terminal to  secure  the earth conductor 
to  the  earth  stud.  The  external  earth  conductor  should  be  at 
least  4mm

2

  in  size.  The  external  earth  crimp  ring  should  be 

located  between  the  two  M5  plain  washers  provided  and 
securely locked down with the M5 spring washer and M5 nut. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 5 Earth locations 

 

11)  End Of Line Monitoring  

 

On  DxC2  DC  units,  dc  reverse  line  monitoring  can  be  used  if 
required. All DC units have a blocking diode fitted in their supply 
input lines. An end of line monitoring resistor can be connected 
across  the  +ve  and  –ve  terminals.  If  an  end  of  line  resistor  is 
used it must have the following values:- 

 

Min. Resistance 

Min. Power 

3.9KΩ 

0.5W 

1KΩ 

2W 

 
The resistor must be connected directly across the +ve and  
-ve terminals of the PCBA, as shown in the following diagrams. 
Whilst keeping its leads as short as possible, a spacing of at 
least 1/16 inch (1.58mm) must be provided through air and over 
surfaces between uninsulated live parts.

 

 

 

 

Fig. 6a End of Line Resistor Forming 

 

 

 

 

 

 

 

 

 

Summary of Contents for D2xC2LD3

Page 1: ...s approved for use as an Audible and Visual Appliance for use in Private Mode Fire Alarm System in accordance with UL464 Tenth Edition CAN ULC S525 Fourth Edition and UL1638 Fifth Edition CAN ULC S526 Fourth Edition See fire instructions D211 00 671 IS SC UL 3 1 ATEX IECEx UKEx certification Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Explosive Atmospheres Equipment General Requirements EN ...

Page 2: ...otection by Enclosure t Rating D2xC2LD3 Ex ec IIC Gc X T4 Ta 40 C to 50 C Ex tc IIIC T75 C Dc X Ta 40 C to 50 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Dust Groups and Temperature Classification When connected to an approved system the D2XC2LD3 LED beacon may be installed in Area Classification Zone 2 Explosive gas air mixture not likely to occur ...

Page 3: ...les in the feet of the base The equipment is not to be mounted with the horn facing upwards Fig 1 Fixing locations 6 2 Access to the Enclosure Warning High voltage may be present risk of electric shock DO NOT open when energised disconnect power before opening Warning Hot surfaces External surfaces and internal components may be hot after operation take care when handling the equipment To access t...

Page 4: ...particularly important when using cables with large cross sectional areas such as 2 5mm 9 Wiring The beacon is powered via factory installed wires connected to the alarm horn The wires connecting the alarm horn and strobe can be removed if the user wishes to power the strobe separately For further wiring schematics refer to document D211 06 651 Fig 4 Terminals 10 Earthing The beacon bas has both i...

Page 5: ... patterns as shown in Table 1 The flash patterns are selected by operation of the flash setting DIP switch on the PCB Fig 10 Fig 9 DIP Switch Location 1 ON 0 OFF Table 1 Switch Positions for Flash Patterns Fig 10 Dip Switch Example shown 01 Flashing 1 33Hz 13 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in a...

Page 6: ...ings Model Nom Voltage Voltage Range Flash Rate Setting Nom operating current Max operating current Beacon Sounder Beacon Sounder D2xC2LD3DC024 24Vdc Regulated 16 33Vdc Flashing 1Hz 153mA 250mA 465mA 250mA Flashing 1 33Hz 189mA 488mA Flashing 1 5Hz 203mA 456mA Flashing 2Hz 248mA 528mA For Public Mode or private mode Fire Alarm or General Signaling use nominal rms current at nominal voltage max rms...

Page 7: ...5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 300Hz Continuous 0 1 1 1 0 0 44 24 35 16 440Hz Continuous 1 1 1 1 0 0 44 24 35 17 470Hz Continuous 0 0 0 0 1 0 44 24 35 18 500Hz Continuous IMO code 2 Low 1 0 0 0 1 0 44 24 35 19 554Hz Continuous 0 1 ...

Page 8: ...3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz Sweeping 1 0 1 0 1 1 57 24 12 55 800 1000Hz 50Hz Sweeping 0 1 1 0 1 1 54 24 12 56 2400 2900Hz 7Hz Sweeping 1 1 1 0 1 1 57 24 12 57 2400 2900Hz 1Hz Sweeping 0 0 0 1 1 1 47 24 12 58 2400 2900Hz 50Hz Swe...

Page 9: ...rol section For fire alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet anechoic room UL464 92 2dB A at 10 feet reverberation room Testing of synchronization requirements of UL1971 UL1638 CAN ULC S526 were conducted by UL using a total of 6 units conne...

Page 10: ... 75 Fig 1 Horizontal dispersion angles for wall mounting Table 1 Horizontal Light Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate Intensity cd at 1 33Hz flash rate Intensity cd at 2Hz flash rate 0 100 38 38 35 87 25 97 5 25 90 34 54 32 28 23 37 30 45 75 28 79 26 90 19 48 50 55 21 11 14 28 14 28 55 45 17 27 11 69 11 69 60 40 15 35 10 39 10 39 65 35 13 43 9...

Page 11: ...nting public mode 75 60 45 30 15 0 90 Fig 2 Vertical dispersion angles for wall mounting Table 2 Vertical Light Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate Intensity cd at 1 33Hz flash rate Intensity cd at 2Hz flash rate 0 100 38 38 35 87 25 97 5 30 90 34 54 32 28 23 37 35 65 24 95 23 32 16 88 40 46 17 65 16 50 11 95 45 34 13 05 12 20 8 83 50 27 10 36...

Page 12: ...8 CAN ULC S526 at worst case min input voltage 3 4 On axis light output rating private mode Table 3 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate Intensity cd at 1 33Hz flash rate Intensity cd at 2Hz flash rate 0 100 38 38 35 87 25 97 5 25 90 34 54 32 28 23 37 30 45 75 28 79 26 90 19 48 50 55 21 11 19 73 14 28 55 45 17 27 16 14 11 69 6...

Page 13: ...ts Model Nom Voltage Voltage Range Flash Rate Setting Init Peak Surge Current A Init RMS Surge Current mA D2xC2LD2DC024 24Vdc Regulated 24 16 33Vdc 1Hz 60fpm 2 73 240 1 33Hz 80 fpm 2 75 214 2Hz 120fpm 2 33 204 5 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 101 2 dB A Reference 90 101 2 dB A 115 3 dB A 68 3 dB A 129 6 dB A 55 6 ...

Page 14: ... 1 Apply power to Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve Stage 4 Apply power to Sounder ve ve Connect Stage 2 and Stage 3 to ve OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED REQUIRED MINIMUM VALUES R1 24VDC 1KΩ MIN 2W MIN OR 3K9Ω MIN 0 5W MIN 48VDC 3 9KΩ MIN 2W MIN OR 15KΩ MIN 0 5W MIN S3 S2 STAGE 3 ...

Page 15: ...therlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 3...

Page 16: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 17: ... Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Com...

Page 18: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Reviews: