Document No. D190-00-351-IS

 

Issue 1

 

21-03-2022

 

Sheet 3 of 6

 

6)

Product Mounting and Access

6.1 

Mounting 

30 

 1.

18 

in.

 

117.3  4.62 in. 

30 

 1.

18 

in.

 

338.6  13.33 in. 

145 

 5.

71 

in.

 

30 

 1.

18 

in.

 

186.5  7.34 in. 

30 

 1.

18 

in.

 

145 

 5.

71 

in.

 

181.

64 

 7.

15 

in.

 

30 

 1.

18 

in.

 

236.    .33 in. 

30 

 1.

18 

in.

 

145 

 5.

71 

in.

 

21 .

 8.

64 

in.

 

407.8  16.06 in. 

458.2  18.04 in. 

122 

 4.

80 

in.

 

Fig 1: Mounting Locations 

The Equipment must not be installed with the horn facing upwards 
of horizontal. 

The D1x unit may be secured to any flat surface using at least two 
of the three or four 7mm fixing holes. The enclosure provides IP66 
protection  and  is  suitable  for  installation  in  exterior  locations 
providing it is positioned so that water cannot collect in the horn, 
and the cable entry is sealed. 

6.2 

Installation procedure 

a. 

Secure  the  D1x  unit  to  a  flat  surface  via the  three  7mm 

fixing holes in the mounting    bracket.  

b.

Remove  the  explosionproof  cover  of  the  alarm  horn  by
unscrewing  it,  taking  care  not  to  damage  the 

explosionproof  threads  in  the  process  (Refer  to  section 
6.4). 

c.

Fit an M20/NPT suitably rated cable gland or conduit entry
into the hole in the enclosure and connect the field wiring 

to the appropriate alarm horn terminals as shown in D190-

06-305  (AC)  or.  D190-06-301  (DC).  The  power  supply 
terminals are duplicated so that units may be connected 

in parallel. An end of line monitoring resistor may be fitted 

to DC units only (see section 10). If the second and third 
M20/NPT  entries  are  not  used,  suitably  rated  stopping 

plugs must always be fitted. 

d.

Replace the explosionproof cover of the unit, taking care
not to damage the explosionproof threads. Tighten fully. 

6.3 

Hornless Variants

 

The D1x  unit is also available as a variant with no horn fitted in 
the factory. The Horn threaded nose portion has a fitment thread 
of  1-3/8”  –  18  UNF  (to  BS1580  or  ANSI  B1.1).  The customer  is 
responsible for sourcing and correctly fitting a suitable horn that 
meets all of the relevant safety requirements. 

6.4  Access to the Explosionproof Enclosure 

Fig 2: Accessing the enclosure

 

To access the Ex d chamber, loosen the M4 grub screw on the 
cover. Open the enclosure by turning the cover counterclockwise and 
remove the cover. 

On completion of the installation the flameproof threaded joint should 
be inspected to ensure that they are clean and that they have not 
been damaged during installation.  

Ensure the O-ring seal is in place and undamaged. 

When fitting the flameproof cover ensure the thread is engaged 
correctly. Fully tighten the cover all the way, ensure no gap is visible 
between the cover and base of the enclosure. 

7) Installation Requirements

7.1 

Safe Installation Requirements 

Warning 

– High voltage may be 

present, risk of electric shock. 
DO NOT open when energised, 
disconnect power before opening. 

The  sounder  must  only  be  installed  by  suitably  qualified 
personnel in accordance with the latest issues of the relevant 
standards. 

The product must only be installed by suitably qualified personnel 
in accordance with the latest issues of the relevant standards. 

The installation of the units must also be in accordance with the 
NEC and any local regulations and should only be carried out by 
a competent electrical engineer who has the necessary training. 

7.2  Cable Selection and Connections 

Electrical connections are to be made into the terminal blocks on the 
PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or stranded wire, 
sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation needs to be stripped 
8mm. Wires may be fitted securely with crimped ferrules. Terminal 
screws need to be tightened down with a tightening torque of 0.45 
Nm / 3.5 Lb-in. 

When selecting the cable size, consideration must be given to the input 
current that each unit draws (see table 1), the number of sounders on 
the line and the length of the cable runs. The cable size selected must 
have  the  necessary  capacity  to  provide  the  input  current  to  all  the 
sounders connected to the line.  

AC: 1.0 - 2.5mm

2

 / AWG18 - AWG12 

DC: 0.2 - 2.5mm

2

 / AWG24 - AWG12 

Figure 3: Wire Preparation.

When connecting wires to the terminals great care should be taken to 
dress the  wires so that  when  the cover is  inserted  into the  chamber 
the wires do not exert excess pressure on the terminal blocks. This is 
particularly  important  when  using  cables  with  large  cross-sectional 
areas such as 2.5mm². 

D1xC1-R & D1xC2-R 

D1xC1-F 

D1xC2-F 

8mm 

Summary of Contents for D1xC1X05RDC024-D

Page 1: ...0 60Hz D1xC2X05FAC230 D 230Vac P2 P3 157 246mA 220 240Vac 50 60Hz Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The current levels shown above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electrical Ratings 2 Warnings CAUTION TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES DISCONNECT FROM SUPPLY ...

Page 2: ...Installation must be carried out in compliance with the National Electric Code D1xC units have been tested and found suitable for use in atmospheres containing the following chemicals in accordance with UL1203 Acetone Ammonium Hydroxide Diethyl Ether Ethyl Acetate Ethylene Dichloride Furfural n Hexane Methyl Ethyl Ketone Methanol 2 Nitropropane Toluene 4 Specific Conditions of Installation The cab...

Page 3: ...cessing the enclosure To access the Ex d chamber loosen the M4 grub screw on the cover Open the enclosure by turning the cover counterclockwise and remove the cover On completion of the installation the flameproof threaded joint should be inspected to ensure that they are clean and that they have not been damaged during installation Ensure the O ring seal is in place and undamaged When fitting the...

Page 4: ...quired then a suitable sealing washer must be fitted under the cable glands or blanking plugs A minimum ingress protection rating of IP6X must be maintained for installations in explosive dust atmospheres To maintain the ingress protection rating and mode of protection the cable entries must be fitted with suitably rated cable entry and or blanking devices during installation If entries are fitted...

Page 5: ...fferent tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP switch 2 see fig 10 on the PCB for stage 1 and stage 2 respectively Default Switch 2 S2 Tone 1 0 0 0 0 0 0 Default Switch 1 S1 Tone 44 1 1 0 1 0 1 ON 1 OFF 0 Fig 10 DIP switch configuration The sounder can also be switched to sound the thir...

Page 6: ... 06 305 for AC Schematic Diagrams 9 End of Line Monitoring DC Units 9 1 Standard DC End Of Line Monitoring All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber If an end of line resistor is used it must have a minimum resistance value of 3...

Page 7: ... 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0...

Page 8: ...ge 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve WIRING LINKING BEACON SOUNDER FACTORY FITTED 6 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Single Stage Con...

Page 9: ...D D190 06 301 6 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 2 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve ...

Page 10: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF 3 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 WIRING LINKING BEACON SOUNDER FACTORY FITTED OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM V...

Page 11: ... Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve ve IN ve IN D190 06 301 6 4 R2 ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Single Stage Configuration Config 5a Line Monitoring Set to p...

Page 12: ...2 R1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 6 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve Stage 1 ve Stage 2 Apply P...

Page 13: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 6 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Independent Sounder Beacon Activatio...

Page 14: ...L SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED WIRING LINKING BEACON SOUNDER FACTORY FITTED 2 Earth Earth Stage 2 Stage 3 Common L N L N N N L L E N N L L E C S2 S3 Live IN Live OUT Neutral IN Neutral OUT Stage 1 Li...

Page 15: ...SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 2 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 2 Stage 1 Live IN Stage 1 Live OUT Stage 1 Neutral IN Stage 1 Neutral OUT Earth Live IN Live OUT Neutral IN Neutral OUT Earth Stage 2 Stage 3 Common N N L L E N N L L E C S2 S3 Single Stage Configuration Config 2a ...

Page 16: ...Page left Intentionally blank ...

Reviews: