D221-95-001-IS_Issue_A - 09/03/2021

1000Hz PFEER Toxic Gas
1200/500Hz @ 1Hz DIN /PFEER P.T.A.P.

1000Hz @ 0.5Hz(1s on, 1soff) PFEER Gen. Alarm

1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s NF C 48-265

544Hz(100mS)/440Hz (400mS) NF S 32-001

1500/500Hz - (0.5s on , 0.5s off) x3 + 1s gap AS4428

500-1500Hz Sweeping 2 sec on 1 sec off AS4428

500/1200Hz @ 0.26Hz (3.3son, 0.5s off) Netherlands - 
NEN 2575
1000Hz (1s on, 1s off)x7 + (7s on, 1s off) IMO Code 1a

1000Hz (1s on, 1s off)x7 + (7s on, 1s off) IMO Code 1a

420Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal 
Pattern

1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal 
Pattern

422/775Hz - (0.85 on, 0.5 off) x3 + 1s gap NFPA - 
Temporal Coded

1000/2000Hz @ 1Hz Singapore

300Hz Continuous
440Hz Continuous
470Hz Continuous
500Hz Continuous IMO code 2 (Low)
554Hz Continuous
660Hz Continuous
800Hz IMO code 2 (High)
1200Hz Continuous
2000Hz Continuous 
2400Hz Continuous
440Hz @0.83Hz (50
cycles/minute) Intermittent
470Hz @0.9Hz - 1.1s Intermittent
470Hz @5Hz - (5
cycles/second) Intermittent
544Hz @ 1.14Hz - 0.875s Intermittent
655Hz @ 0.875Hz Intermittent
660Hz @0.28Hz - 1.8sec
on, 1.8sec off Intermittent
660Hz @3.34Hz - 150mS
on, 150mS off Intermittent
745Hz @ 1Hz Intermittent
800Hz - 0.25sec on, 1 sec off Intermittent 
800Hz @ 2Hz IMO code 3.a
(High) Intermittent
1000Hz @ 1Hz Intermittent
2400Hz @ 1Hz Intermittent
2900Hz @ 5Hz Intermittent
363/518Hz @ 1Hz Alternating
450/500Hz @ 2Hz Alternating
554/440Hz @ 1Hz Alternating
554/440Hz @ 0.625Hz Alternating
561/760Hz @0.83Hz (50
cycles/minute) Alternating

800/1000Hz @ 0.875Hz Alternating
2400/2900Hz @ 2Hz Alternating
500/1200Hz @ 0.3Hz Sweeping
560/1055Hz @ 0.18Hz Sweeping
560/1055Hz @ 3.3Hz Sweeping

660/1200Hz @ 1Hz Sweeping
800/1000Hz @ 1Hz Sweeping
800/1000Hz @ 7Hz Sweeping
800/1000Hz @ 50Hz Sweeping
2400/2900Hz @ 7Hz Sweeping
2400/2900Hz @ 1Hz Sweeping
2400/2900Hz @ 50Hz Sweeping
2500/3000Hz @ 2Hz Sweeping
2500/3000Hz @ 7.7Hz Sweeping
800Hz Motor Siren
1200Hz Motor Siren
2400Hz Motor Siren

Stage 1
Set DIP
SW 1
Tone No.

Tone Description

Tone Visual

Stage 1 & 2
DIP SW 1/2

 Settings

1 2 3 4 5 6

Stage 3
Set DIP

SW 1

(S3)

Stage 4
Set DIP

SW 1

(S2 + S3)

0 0 0 0 0 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15
16
17
18
19

20
21
22
23
24

25

26

27

28
29

30

31

32
33

34

35
36
37
38
39
40
41

46
47
48
49
50

52
53
54
55
56
57
58
59
60
61
62
63

42

1 0 0 0 0 0

0 1 0 0 0 0

1 1 0 0 0 0

0 0 1 0 0 0

1 0 1 0 0 0

0 1 1 0 0 0

1 1 1 0 0 0

0 0 0 1 0 0

1 0 0 1 0 0

0 1 0 1 0 0

1 1 0 1 0 0

0 0 1 1 0 0

1 0 1 1 0 0

0 1 1 1 0 0

1 1 1 1 0 0

0 0 0 0 1 0

1 0 0 0 1 0

0 1 0 0 1 0

1 1 0 0 1 0

0 0 1 0 1 0

1 0 1 0 1 0

0 1 1 0 1 0

1 1 1 0 1 0

1 1 0 1 1 0
0 0 1 1 1 0

0 1 1 1 1 0

0 0 0 0 0 1

0 1 0 0 0 1

1 1 0 0 0 1

0 0 1 0 0 1

1 0 1 0 0 1

0 1 1 0 0 1

1 1 1 0 0 1 

0 0 0 1 0 1 

0 1 0 1 0 1

1 0 1 1 0 1
0 1 1 1 0 1
1 1 1 1 0 1
0 0 0 0 1 1
1 0 0 0 1 1

0 1 0 0 1 1

1 1 0 0 1 1
0 0 1 0 1 1
1 0 1 0 1 1
0 1 1 0 1 1
1 1 1 0 1 1
0 0 0 1 1 1
1 0 0 1 1 1
0 1 0 1 1 1
1 1 0 1 1 1
0 0 1 1 1 1
1 0 1 1 1 1
0 1 1 1 1 1

0 0 0 1 1 0

1 0 0 1 1 0

0 1 0 1 1 0

1 1 1 1 1 0

1 0 0 0 0 1

1 0 0 1 0 1

1 0 1 1 1 0

1000Hz

1200Hz

500Hz 1s

1000Hz

1s

1s

1600Hz

1400Hz

1s

0.5s

544Hz 0.1s

0.4s

440Hz

0.5s

1500Hz

500Hz

0.5s 0.5s

0.5s 0.5s

1s

2s 1s

3s

0.5s

1500Hz

500Hz

1200Hz

500Hz

1000Hz

1s

1s

1s

1s

1s

1s

1s

1s

1s

1s

1s

1s

1s

1s

7s

7s

420Hz 0.5s

0.5s

0.5s

0.5s

0.5s

1s

1000Hz 0.5s

0.5s

0.5s

0.5s

0.5s

1s

1200Hz

500Hz

0.85 0.5s

0.85 0.5s

0.85

2000Hz

1000Hz

1s

f(Hz)

a(s)

b(s)

(f=440, a=0.6, b=0.6)

(f=470, a=0.55, b=0.55)

(f=470, a=0.1, b=0.1)

(f=470, a=0.43, b=0.44)
(f=655, a=0.57, b=0.57)

(f=660, a=1.8, b=1.8)

(f=660, a=0.15, b=0.15)

(f=745, a=0.5, b=0.5)

(f=800, a=0.25, b=1)

(f=800, a=0.25, b=0.25)

(f=1000, a=0.5, b=0.5)
(f=2400, a=0.5, b=0.5)

(f=2900, a=0.1, b=0.1)

f1(Hz)

a(s)

f(Hz)

f1(Hz)

a(s)

a(s)

f(Hz)

(f=363, f1=518, a=0.1)

(f=450, f1=500, a=0.25)

(f=440, f1=554, a=0.5)
(f=440, f1=554, a=0.8)

(f=561, f1=760, a=0.6)

0 0 1 1 0 1

1 1 0 1 0 1

43

44

45

780/600Hz @ 0.96Hz Alternating

800/1000Hz @ 2Hz Alternating

970/800Hz @ 2Hz Alternating

64

Simulated Bell

1 1 1 1 1 1

f1(Hz)

a(s)

a(s)

f(Hz)

(f=800, f1=1000, a=0.57)

(f=2400, f1=2900, a=0.25)

f1(Hz)

a(s)

a(s)

f(Hz)

(f=800, f1=1000, a=0.25)

f1(Hz)

a(s)

a(s)

f(Hz)

(f=600, f1=780, a=0.52)

f1(Hz)

a(s)

a(s)

f(Hz)

(f=800, f1=970, a=0.25)

(f=500, f1=1200, a=3.34)

(f=560, f1=1055, a=5.47)

(f=560, f1=1055, a=0.3)

f1(Hz)

a(s)

f(Hz)

51

600/1250Hz @ 0.125Hz Sweeping

(f=600, f1=1250, a=8)

f(Hz)

a(s)

(f=800, a=1.6)

(f=1200, a=2)

(f=2400, a=1.7)

1450Hz

0.25s

0.69ms

(f=660, f1=1200, a=1)
(f=800, f1=1000, a=1)

(f=800, f1=1000, a=0.14)
(f=800, f1=1000, a=0.02)

(f=2400, f1=2900, a=0.14)

(f=2400, f1=2900, a=1)

(f=2400, f1=2900, a=0.02)

(f=2500, f1=3000, a=0.5)

(f=2500, f1=3000, a=0.13)

(f=300)
(f=440)
(f=470)
(f=500)
(f=554)
(f=660)
(f=800)

(f=1200)
(f=2000)

(f=2400)

f(Hz)

0.5s

2

3

2

24

19

44

44

24

34

34

1

1

1

3

44

44

44

24
24

24

24

24
24

24

24
24
24
8
8
24
8

24
24
24
24
24

24
24
24
24
24
24
24
24
24
24
24
24

8

8

24

8

21

24

24
24
24
24
24
24
24
24
3
20

44

44

44

1

1

1

1

35

1

1

8

8

8

35

8

8

8

8
8

8

8

8
8

19

19
19
19
19
19
19
19

19

19

19

19

19
19
12
12
12

12

12
12
12
12
12
12
12
12
12

12

12

12

1
1
8
8
8
35
35
35
35
35

f1(Hz)

a(s)

f(Hz)

Summary of Contents for D1xC1X05RDC024-D

Page 1: ...0 60Hz D1xC2X05FAC230 D 230Vac P2 P3 157 246mA 220 240Vac 50 60Hz Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The current levels shown above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electrical Ratings 2 Warnings CAUTION TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES DISCONNECT FROM SUPPLY ...

Page 2: ...Installation must be carried out in compliance with the National Electric Code D1xC units have been tested and found suitable for use in atmospheres containing the following chemicals in accordance with UL1203 Acetone Ammonium Hydroxide Diethyl Ether Ethyl Acetate Ethylene Dichloride Furfural n Hexane Methyl Ethyl Ketone Methanol 2 Nitropropane Toluene 4 Specific Conditions of Installation The cab...

Page 3: ...cessing the enclosure To access the Ex d chamber loosen the M4 grub screw on the cover Open the enclosure by turning the cover counterclockwise and remove the cover On completion of the installation the flameproof threaded joint should be inspected to ensure that they are clean and that they have not been damaged during installation Ensure the O ring seal is in place and undamaged When fitting the...

Page 4: ...quired then a suitable sealing washer must be fitted under the cable glands or blanking plugs A minimum ingress protection rating of IP6X must be maintained for installations in explosive dust atmospheres To maintain the ingress protection rating and mode of protection the cable entries must be fitted with suitably rated cable entry and or blanking devices during installation If entries are fitted...

Page 5: ...fferent tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP switch 2 see fig 10 on the PCB for stage 1 and stage 2 respectively Default Switch 2 S2 Tone 1 0 0 0 0 0 0 Default Switch 1 S1 Tone 44 1 1 0 1 0 1 ON 1 OFF 0 Fig 10 DIP switch configuration The sounder can also be switched to sound the thir...

Page 6: ... 06 305 for AC Schematic Diagrams 9 End of Line Monitoring DC Units 9 1 Standard DC End Of Line Monitoring All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber If an end of line resistor is used it must have a minimum resistance value of 3...

Page 7: ... 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0...

Page 8: ...ge 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve WIRING LINKING BEACON SOUNDER FACTORY FITTED 6 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Single Stage Con...

Page 9: ...D D190 06 301 6 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 2 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve ...

Page 10: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF 3 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 WIRING LINKING BEACON SOUNDER FACTORY FITTED OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM V...

Page 11: ... Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve ve IN ve IN D190 06 301 6 4 R2 ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Single Stage Configuration Config 5a Line Monitoring Set to p...

Page 12: ...2 R1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 6 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve Stage 1 ve Stage 2 Apply P...

Page 13: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 6 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Independent Sounder Beacon Activatio...

Page 14: ...L SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED WIRING LINKING BEACON SOUNDER FACTORY FITTED 2 Earth Earth Stage 2 Stage 3 Common L N L N N N L L E N N L L E C S2 S3 Live IN Live OUT Neutral IN Neutral OUT Stage 1 Li...

Page 15: ...SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 2 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 2 Stage 1 Live IN Stage 1 Live OUT Stage 1 Neutral IN Stage 1 Neutral OUT Earth Live IN Live OUT Neutral IN Neutral OUT Earth Stage 2 Stage 3 Common N N L L E N N L L E C S2 S3 Single Stage Configuration Config 2a ...

Page 16: ...Page left Intentionally blank ...

Reviews: