8.  Selection of Cable. Cable Glands, Blanking 

Elements & Adapters 

 

When selecting the cable size, consideration must be given to 
the input current  that each unit  draws  (see  table  above),  the 
number  of  sounders  on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity  to  provide  the  input  current  to  all  of  the  sounders 
connected to the line.  

 

For  ambient  temperatures  over  +40ºC  the  cable  entry 
temperature  may  exceed  +70ºC  and  therefore  suitable  heat 
resisting cables and cable glands must be used, with a rated 
service temperature of at least 110ºC 

 

The dual cable gland entries have an M20 x 1.5 entry thread. 
To  maintain  the  ingress  protection  rating  and  mode  of 
protection, the cable entries must be fitted with suitably rated 
ATEX / IECEx or UKEx certified cable glands and/or suitably 
rated ATEX / IECEx or UKEx certified blanking devices during 
installation according to EN / IEC60079-14. 

 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs.  

 

For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 

 

The  BEx  combined  sounder/beacon  range  can  be  supplied 
with the following types of adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any  other  adapters  used  must  be  suitably  rated  and  ATEX / 
IECEx or UKEx certified adapters. 

 

9.  Earthing 

 

Both AC and DC sounder units must be connected to an earth. 
The  units  are  provided  with  internal  and  external  earth 
terminals  which  are  both  located  on  the  terminal  chamber 
section of the unit. 

 

Fig. 3 Internal View of Cover 

 

When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure.  

 

Internal earthing connections should be made to the Internal 
Earth  terminal  in  the  base  of  the  housing  using  a  ring  crimp 

terminal to secure the earth conductor under the earth clamp. 
The earth conductor should be at least equal in size and rating 
to the incoming power conductors. Tighten M4 Earth screw to 
1Nm. 

 

External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth conductor 
to  the  earth  stud.  The  external  earth  conductor  should  be  at 
least 4mm² in size.

 

Tighten the Earth nut to 3Nm. Please firmly 

tighten the external grounding terminal so that the stud does 
not  become  loose  and  lay  the  ground  wire  so  that  it  is  not 
caught by twisting and sagging. 

 

10.  Cable Connections 

 

The  combined  sounder  beacon  unit  BExCTS110-05D  has 
separate  printed  circuit  boards  in  the  sounder  and  beacon 
sections.  The  terminals  for  the  incoming  power  supply  and 
telephone signal are on the printed circuit board in the sounder 
section  and  the  terminals  for  the  beacon  are  on  the  printed 
circuit board in the beacon section (see figures 5a, 5b, 7a and 
7b). See section 7 of this manual for access to the enclosure. 
See  section  11  and  12  for  AC  and  DC  wiring  diagrams 
respectively.  
 
Wires  having  a  cross  sectional  area  between  0.5  mm²  to 
2.5mm² can be connected to each terminal way. If an input and 
output wire is required, the 2-off Live/Neutral or +/- terminals 
can be used. If fitting 2-off wires to one terminal way, the sum 
of the 2-off wires must be a maximum cross sectional area of 
2.5mm².  Strip  wires  to  8mm.  Wires  may  also  be  fitted  using 
ferrules.  Terminal  screws  need  to  be  tightened  down  with  a 
tightening torque of 0.45 Nm / 5 Lb-in. When connecting wires 
to the terminals great care should be taken to dress the wires 
so that when the cover is inserted into the chamber the wires 
do  not  exert  excess  pressure  on  the  terminal  blocks.  This  is 
particularly  important  when  using  cables  with  large  cross 
sectional areas such as 2.5mm². 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

External Earthing 

Internal 
Earthing 

Internal 
Bonding 
Wire 
Terminal 

2-off M20 
Cable 
Entries 

Summary of Contents for BExCTS110-05D-P

Page 1: ...126V BExCTS110 05DPAC230 BExCTS110 05DPAC230 R 230Vac 56mA 55mA 253V Max Tone 4 Nom Tone 44 The table shows the input current taken by the various units The current levels shown above are for the 440H...

Page 2: ...s air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Temperature Classification for Gas Applicati...

Page 3: ...it cannot move in service Fig 1a Fixing Location for Combined Flare Fig 1b Fixing Location for Combined Radial 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexago...

Page 4: ...the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a...

Page 5: ...g Diagram Fig 5a Sounder AC Terminals Fig 5b Beacon AC Terminals 12 DC Wiring Four connections must be made to the BExCTS110 05D DC unit A power supply input cable should enter the enclosure via one o...

Page 6: ...cb see figures 5a 7a The Telephone Selection Table on page seven shows the switch positions 1 4 for the country setting and switch 5 for the beacon continuous or pulse mode and switch 6 for the sounde...

Page 7: ...ixtures 15 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN6...

Page 8: ...etting 1 2 3 4 5 6 Australia Ireland New Zealand Singapore South Africa UK 0 0 0 0 Belgium Canada Cyprus Hong Kong Spain Turkey USA 1 0 0 0 Czech Republic Finland France Germany Greece Italy Luxemburg...

Page 9: ...mittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 0 2 5 19 1400Hz to 1600Hz sweeep up over 1s 0 1 0 0 1 0 2 5 1600Hz to 1400Hz sweep down over 0 5s 20 Continuous 660Hz 1 1 0 0 1 0 2 5 21 Alternating 554 440Hz...

Page 10: ...DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210...

Page 11: ...ISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 685 R S RAIT B ISARD R...

Page 12: ...cation Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Ne...

Page 13: ...te and Place of Issue London 21 05 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 14: ...X2639X Notified Body for Quality Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane E...

Page 15: ...nd Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Page 16: ...Page left Intentionally blank...

Reviews: