Fig. 4b Beacon AC Terminals 

 

12.  DC Wiring 

 

 

Fig. 5a DC Terminals 

 

 

Fig. 5b Beacon DC Terminals 

 
 
 
 
 
 
 
 
 
 
 

12.1 Stage Switching Polarity (DC Units Only)

 

 

The BExS110D DC sounders have the facility to use ve 
or –ve switching to change the tone to the second and third 
stages.  Negative  switching  is  the  default  setting.  For  –ve 
switching connect the two headers on the pcb to the left-hand 
(marked –ve) and centre pins. For +ve switching connect the 
headers to the right hand (ve) and the centre pins. 
(Refer to Fig. 6) 

 

 

 
 
 
 
 
 
 
 
 
 

 
 

 

 

Fig. 6 Stage Switching Polarity 

12.2 Line Monitoring

 

 

On  BExS110D  DC  units,  dc  reverse  line  monitoring  can  be 
used if required. All DC sounders have a blocking diode fitted 
in their supply input lines. An end of line monitoring diode or 
an end of line monitoring resistor can be connected across the 
+ve and –ve terminals. If an end of line resistor is used it must 
have  a  minimum  resistance  value  of  3k3Ω  and  a  minimum 
power  rating  of  0.5  watts  or  a  minimum  resistance  value  of 
500Ω and a minimum power rating of 2 watts. 
 
The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor 
leads should be kept as short as possible.  
 

 

Fig. 7 End of Line Resistor Placement 

 

13.  Wiring the combined sounder/beacon for 

simultaneous operation 

 

The sounder and beacon sections can be wired to the same 
input supply so that they operate simultaneously or they can 
be wired to separate input supplies so they can be operated 
independently (see wiring diagrams D210-06-601 & D210-06-
605). 

 

 

If the sounder and beacon sections are connected to the same 
input supply. The incoming cables should be connected to the 
input  terminals  on  the  beacon  board  and  the  two  link  wires, 
that are supplied with the unit, should be used to link the supply 
from the interconnecting terminals on the beacon board down 
to the supply terminals on the sounder board. 

 

 

End of Line Resistor

Volume Control 

DIP Switch 

DC Terminals 

Stage Headers 

Negative Switching 

Positive Switching 
A ti t d

Header Pin Location 

Header Pin Location 

S2
S3

+

 

 

+

 

 

+

 

 

 

+  

 

Interconnecting Terminals 
to sounder PCB 
(simultaneous 
mode of operation) 

 

 

N  

 

Interconnecting Terminals 
to sounder PCB 
(simultaneous 
mode of operation) 

Summary of Contents for BExCS110-05

Page 1: ...05DPAC230 BExCS110 05DPAC230 R 230Vac 56mA 55mA 253V Max Tone 4 Nom Tone 44 The table shows the input current taken by the various units The current levels shown above are for the 440Hz Continuous to...

Page 2: ...air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Temperature Classification for Gas Application...

Page 3: ...it cannot move in service Fig 1a Fixing Location for Combined Flare Fig 1b Fixing Location for Combined Radial 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexago...

Page 4: ...section of the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal ear...

Page 5: ...m power rating of 0 5 watts or a minimum resistance value of 500 and a minimum power rating of 2 watts The resistor must be connected directly across the ve and ve terminals as shown in the following...

Page 6: ...sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units Refer to wiring schematics D210 06 601 DC or D210 06 605 AC Default To...

Page 7: ...Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive at...

Page 8: ...mittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 0 2 5 19 1400Hz to 1600Hz sweeep up over 1s 0 1 0 0 1 0 2 5 1600Hz to 1400Hz sweep down over 0 5s 20 Continuous 660Hz 1 1 0 0 1 0 2 5 21 Alternating 554 440Hz...

Page 9: ...Page left Intentionally blank...

Page 10: ...ER SUPPLIED 500 MIN 2W MIN OR 3K3 MIN 0 5W MIN MINIMUM VALUES R1 Single Stage Configuration Config 1a Line Monitoring Set to negative switching default Stage 1 Apply Power to Stage 1 ve Stage 1 ve Two...

Page 11: ...RFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 605 R S RAIT B...

Page 12: ...cation Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Ne...

Page 13: ...te and Place of Issue London 21 05 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 14: ...X2639X Notified Body for Quality Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane E...

Page 15: ...nd Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Page 16: ...Page left Intentionally blank...

Reviews: