User Manual EE600 Differential Pressure Sensor
4 Mounting and Installation
Mount the EE600 onto a vertical, smooth surface.
Important
:
The pressure connection nipples must point downwards.
Avoid installation close to heaters and sources of strong electromagnetic interference.
Insert the cable for supply voltage and output signal through the cable gland and connect it to the
spring terminals according to the wiring diagram (Fig. 3 Connection diagram).
Important: Make sure that the connecting cable or wires do not impact with the push buttons in order
to prevent unintentional trigger of the span or zero point adjustment.
Close tightly the cable gland. This is essential for the compliance with the IP65 / NEMA 4X protection
rating of the EE600 enclosure.
Fig. 6
Mounting orientation
4.1 Pressure Connection
Fig. 7
Pressure connection
2x Ø2.2
Ø
6.5
80
18.5
60∞
Ø16
Ø7
Ø
7.3
Fig. 8
Dimension of pressure connection nipples
Install first the pressure connection nipples (included in the scope of supply) onto the duct.
Use a Ø7.5 mm drill.
Connect the pressure hose (included in the scope of supply) first to the EE600 and then to the
nipples at the duct. Route the pressure hose for avoiding sharp bends which might lead to the hose