15
User Manual EE600 Differential Pressure Sensor
Registers ...
... with these
assigned measurands ...
... map to registers ...
... mirrored from
source registers
Dec
Hex
Meas.
Unit
Type
Dec
1)
Hex
2)
Dec
1)
Hex
2)
Function code 0x10
Function code 0x03 / 0x04
6001
0x1770
∆
P
Pa
INT16
3001
0xBB8
4108
0x100B
6002
0x1771
V'
m
3
/h
FLOAT32
3002
0xBB9
1055
0x41E
FLOAT32
3003
0xBBA
1056
0x41F
6003
0x1772
v
m/s
FLOAT32
3004
0xBBB
1041
0x410
FLOAT32
3005
0xBBC
1042
0x411
1) Register number starts from 1.
2) Protocol address starts from 0.
Tab. 11 Custom Modbus map example
5.2.7 Device Status Indication
If a critical error occurs, all Modbus values are set to NaN (according to IEEE754 for data type
FLOAT32) or to 0x8000 (INT16). It is possible to read out all status and error information via Modbus
register 602 (0x259). Errors are displayed in bit-coded form. If an event is present, the corresponding bit
is set to 1.
Measured values outside the measuring range are limited with the corresponding limit value.
Error Bits Description
Recommended action
Bit 0 Error: Sensor not adjusted
1. Carry out zero point adjustment
2. Return to factory adjustment
2. Return the faulty unit to E+E for service
Bit 1 Error: Pressure measurement faulty
1. Check the installation and clean the device
2. Carry out zero point adjustment
3. Return the faulty unit to E+E for service
Bit 2 Error: Faulty display communication
1. Check the display connection
Bit 3 Error: Auto-zero did not work
1. Carry out zero point adjustment
2. Return the faulty unit to E+E for service
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
Bit 8 -
Bit 9 -
Bit 10 -
Bit 11 -
Bit 12 -
Tab. 12
Device status indication register
5.3 Display Settings
5.3.1 Analogue Version with DIP Switch Settings
See chapter 5.1 Analogue Version for the configuration options.
5.3.2 Analogue Version with PCS Settings or Digital Version
The factory setting of the display (if present) shows the measured differential pressure in Pascal [Pa].
With the PCS10 Product Configuration Software and the optional USB configuration adapter HA011066,
the user can change the display layout and the visualised parameter according the selected application:
Differential pressure measurement
Unit: Pa, kPa, mbar, mm H
2
O, inch WC,
Layout: one line with limit bar