User Manual EE600 Differential Pressure Sensor

Registers ...

... with these  

assigned measurands ...

... map to registers ...

... mirrored from  

source registers

Dec

Hex

Meas.

Unit

Type

Dec

1)

Hex

2)

Dec

1)

Hex

2)

Function code 0x10

Function code 0x03 / 0x04

6001

0x1770

P

Pa

INT16

3001

0xBB8

4108

0x100B

6002

0x1771

V'

m

3

/h

FLOAT32

3002

0xBB9

1055

0x41E

FLOAT32

3003

0xBBA

1056

0x41F

6003

0x1772

v

m/s

FLOAT32

3004

0xBBB

1041

0x410

FLOAT32

3005

0xBBC

1042

0x411

1) Register number starts from 1.

2) Protocol address starts from 0.

Tab. 11  Custom Modbus map example

5.2.7  Device Status Indication

If a critical error occurs, all Modbus values are set to NaN (according to IEEE754 for data type 

FLOAT32) or to 0x8000 (INT16).  It is possible to read out all status and error information via Modbus 

register 602 (0x259). Errors are displayed in bit-coded form. If an event is present, the corresponding bit 

is set to 1.
Measured values outside the measuring range are limited with the corresponding limit value.

Error Bits Description

Recommended action

Bit 0 Error: Sensor not adjusted

1. Carry out zero point adjustment

2. Return to factory adjustment

2. Return the faulty unit to E+E for service

Bit 1 Error: Pressure measurement faulty

1. Check the installation and clean the device

2. Carry out zero point adjustment

3. Return the faulty unit to E+E for service

Bit 2 Error: Faulty display communication

1. Check the display connection

Bit 3 Error: Auto-zero did not work

1. Carry out zero point adjustment

2. Return the faulty unit to E+E for service

Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
Bit 8 -
Bit 9 -

Bit 10 -

Bit 11 -

Bit 12 -

Tab. 12 

Device status indication register

5.3  Display Settings

5.3.1  Analogue Version with DIP Switch Settings

See chapter 5.1 Analogue Version for the configuration options.

5.3.2  Analogue Version with PCS Settings or Digital Version

The factory setting of the display (if present) shows the measured differential pressure in Pascal [Pa].

With the PCS10 Product Configuration Software and the optional USB configuration adapter HA011066, 

the user can change the display layout and the visualised parameter according the selected application:

Differential pressure measurement

Unit: Pa, kPa, mbar, mm H

2

O, inch WC,

Layout: one line with limit bar

Summary of Contents for EE600

Page 1: ...BA_EE600 v1 6 Modification rights reserved User Manual EE600 Differential Pressure Sensor...

Page 2: ...and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the...

Page 3: ...5 1 5 Select the Output Signal with S8 10 5 1 6 Select the Source of Settings with S9 Auto zero Version Only 11 5 1 7 Outputs 11 5 2 Digital Version 11 5 2 1 RS485 Digital Interface Settings 11 5 2 2...

Page 4: ...Avoid any unnecessary mechanical stress and inappropriate use Installation electrical connection maintenance and commissioning shall be performed by qualified personnel only Use the EE600 only as int...

Page 5: ...y device may only be investigated and possibly repaired by qualified trained and authorised staff If the fault cannot be fixed the device shall be removed from the process Service operations other tha...

Page 6: ...ressure connection nipples 2 DIP switches RS485 addressing 3 Terminals screw 4 Push buttons for zero point and span point adjustment 5 Status LED 6 Slide switch termination resistor 7 Service interfac...

Page 7: ...al EE600 operates normally the measured data is within the selected measuring range One flash 2s Confirms adjustment or return to factory settings Off No power supply or electronics failure Fast flash...

Page 8: ...the push buttons in order to prevent unintentional trigger of the span or zero point adjustment Close tightly the cable gland This is essential for the compliance with the IP65 NEMA 4X protection rati...

Page 9: ...r to the chapters below 5 1 Analogue Version Each EE600 is delivered with the following factory settings all switches on 0 Measurement range 100 of the full scale 1 000 Pa or 10 000 Pa Response time 5...

Page 10: ...600 HV53A7 S1 S2 Pa mbar inch WC kPa 0 0 10000 100 40 10 1 0 7500 75 30 7 5 0 1 5000 50 20 5 1 1 2500 25 10 2 5 Tab 1 DIP switch settings Measurement range 5 1 2 Select the Response Time with S3 and S...

Page 11: ...re and the USB configuration adapter code HA011066 The device address can be overruled by setting the DIP switches see chapter 5 2 1 RS485 Digital Interface Settings Settings that can be changed with...

Page 12: ...set via 1 PCS10 Product Configuration Software and the USB configuration adapter HA011066 2 Modbus protocol in the register 60001 0x00 and 60002 0x01 See Application Note Modbus AN0103 available on ww...

Page 13: ...pressure kPa 1217 0x4C0 Differential pressure inch WC 1219 0x4C2 Air velocity m s 1041 0x410 Air velocity ft min 1043 0x412 Volume flow m3 h 1055 0x41E Volume flow l s 1057 0x420 Volume flow m3 s 105...

Page 14: ...ode Byte count Register 1 value Hi Register 1 value Lo Register 2 value Hi Register 2 value Lo CRC Response Hex 2B 04 04 FB A5 43 F8 61 F3 For decoding of float values stored according standard IEEE75...

Page 15: ...ed action Bit 0 Error Sensor not adjusted 1 Carry out zero point adjustment 2 Return to factory adjustment 2 Return the faulty unit to E E for service Bit 1 Error Pressure measurement faulty 1 Check t...

Page 16: ...o lines without limit bar 5 4 PCS10 Product Configuration Software Only available with analogue version with auto zero and digital version For performing adjustment or changes in EE600 settings please...

Page 17: ...in four different units m3 h m3 s ft3 min l s The default air density 20 value at standard conditions is defined as follows Air density 20 1 204 kg m3 T 20 C 68 F p 1 013 mbar 14 7 psi If the air den...

Page 18: ...p soft cloth to remove deposits of dust or dirt from the exterior of the device and from the display Do not attempt to clean the interior of the device Do not use any solvents alcohol or abrasive clea...

Page 19: ...seconds indicate that the span point adjustment did not succeed In this case repeat b f The span point adjustment b may not succeed because of a deviation higher than 5 of the original full scale of t...

Page 20: ...2 s 4 s selectable with DIP switches Configurable in the range from 0 05 to 30 s with PCS10 Configurable in the range from 0 5 to 30 s with PCS10 Auto zero interval 24 h factory setting Configurable...

Page 21: ...wer supply class III USA Canada Class 2 supply necessary max voltage 30 V DC 15 35 V DC or 24 V AC 20 Current consumption typ 0 Pa 0 psi 24 V DC Analogue output Digital interface Without display 23 mA...

Page 22: ...pluse fr E E Elektronik Germany Obere Zeil 2 61440 Oberursel Tel 49 6171 69411 0 E mail info epluse de E E Elektronik India 801 Sakhi Vihar Road 400072 Mumbai Tel 91 990 440 5400 E mail info in epluse...

Reviews: