Operating instructions for EE310 Humidity / Temperature Transmitter
Ø 12
0.5“
46
1.8“
34 1.3“
85
3.3“
drip water
protection
hanging probe
probe into separation wall
13 0.5“
bow for draining
condense water
temperature gradient along
the probe shall be avoided
sealing
Fig. 16
Mounting the remote probe of EE310-T5
3.3.4 T10-T8: Remote probe up to 180 °C
(356 °F)
• EE310-T10 are transmitters with pressure tight remote probe.
Process pressure range 0.01...20 bar
(0.15...300 psi)
.
• EE310-T8 are transmitter with pressure tight remote probe.
Process pressure range 0.01...100 bar
(0.15...1435 psi)
.
For mounting template of enclosure see chapter
3.1 Mechanical installation /
Fig. 4 Dimensions and mounting template of polycarbonate enclosure in mm (inch)
.
T working range probe:
-40...+180 °C
(-40...356 °F)
cable:
-40...+150
(-40...302 °F)
electronics:
-40...+60 °C
(-40...140 °F)
-20...+50 °C
(-4...122 °F)
(with display)
The probe shall be mounted horizontally or vertically pointing downwards.
For accurate measurement it is of paramount importance to avoid T gradients along the probe. In case
of large T difference between the front and the back of the probe, it is highly recommended to insert the
probe completely into the process. Should this not be possible, place a thermal
isolation layer on the part of the probe outside the process (on the cable side).
code „cable length“
1)
200
(7.87“)
adjustable
min. 23
(1“)
/ max. 164
(6.5“)
∅
12
(0.47“)
L
2)
15
(0.60“)
1/2“ ISO or
1/2“ NPT
∅
13
(0.51”)
1) Refer to ordering guide
2) L = filter length; refer to data sheet „Accessories“
Fig. 17
EE310-T10 probe
General safety instructions for installation
The installation, commissioning and operation of the EE310-T10 may be performed by qualified staff
only. Special attention shall be paid to the correct installation of the probe into the process. In case of
inappropriate installation there is the risk for the probe to be suddenly expulsed due to the pressure in
the process.
Bending over the sensing probe should be avoided under any circumstances!
Make sure that the surface of the probe is not damaged during installation. A damaged probe surface
may lead to damaged seals and consequently to leakage and pressure loss.