Operating instructions for EE310 Humidity / Temperature Transmitter
Model
Supply Input
Terminals
Voltage/Frequency
EE310 with option AM5
Indoor and Outdoor use:
100 to 240 Vac, 50/60 Hz
L1 –
N
Outputs
Model
Type
Ratings
Terminals
EE310 with option AM5
Out 1
0-1V
0-5V
0-10V
0-20mA
4-20mA
(SELV Limited Energy source)
Out 1 (4) –
GND (3)
Out 2
0-1V
0-5V
0-10V
0-20mA
4-20mA
(SELV Limited Energy source)
Out 2 (5) –
GND (3)
Model
Type
Ratings
Terminals
EE310 with options
AM5 and J5
Modbus RTU
0-5V
(SELV Limited Energy source)
RS485 A (=D+) (4) –
RS485 B (=D-) (2) –
GND RS485 (5)
Tab. 9
Electrical connection for integrated power supply module AM5
3.2.8 Connection diagram for alarm outputs AM2
For indoor use, surface mounted according NFPA 79 applications only.
NO
NC
C
NC
6
NO
4
C
5
NC
3
NO
1
C
2
NO
NC
C
Standard
Inverted
REL 1
REL 2
RELA
Y 2
RELA
Y 1
Wire size:
18-16AWG
Type:
CU
Terminal torque
USA:
7 Lb In.
CANADA: 0.8 Nm
Model
Supply Input
Terminals
Voltage/Frequency
EE310 with option AM2
Relay 1:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
C (5) -
NO (4)
C (5) -
NC (6)
EE310 with option AM2
Relay 2:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
C (2) -
NO (1)
C (2) -
NC (3)
Cable gland torque:
USA
18 Lb ln.
CANADA
2 Nm
Cable diameter:
Min.
0.16ʺ (4 mm)
Max.
0.31ʺ (8 mm)