38
Er 64
Er 65
Er 66
Er 74
Calibration
error
Press on reset button.
If error is continuing after reset inform E.C.A.
authorized service.
Locking
Er 67
Ion base value
invalid
Ion base value outside factory
limits or saved incorrectly.
Press on reset button.
If error is continuing after reset
inform E.C.A. authorized service
Locking
Electronic
Er 30
Er 31
Parameter
CRC error
Press on reset button.
If error is continuing after reset inform E.C.A.
authorized service.
Locking
Er 32
230V Supply
low-limit
Arises when mains voltage is
beyond the range of 170 Vac
and 255 Vac.
Unless the voltage turns to its normal value,
the systems remains blocked and temperature
requirements are not met.
Blockage
Er 36
EK production
failure
Inform E.C.A. authorized service.
Blockage
(Permanent)
Er 95
Programming
mode
The system is in programming
mode.
Press on reset button.
If error is continuing after reset inform E.C.A.
authorized service.
Blockage
Er 96
Remote reset
supervision
Arises as the result of
continuous reset repeated in a
short while.
Inform E.C.A. authorized service.
Blockage
Er 97
Unknown
error
Press on reset button.
If error is continuing after reset inform E.C.A.
authorized service.
Blockage
Er 88
Er 98
Er 99
Other SCOT
ERRORS
Press on reset button.
If error is continuing after reset inform E.C.A.
authorized service.
Blockage /
Locking
Boiler Chip Card (BCC)
Er 34
BCC in
compatible
BCC is not compatible with PCB
(Firmware or Parameter)
Inform E.C.A. authorized service.
Blockage /
Locking
Er 35
No BCC (not
inserted)
If BCC is inserted and removed,
this error arises.
Inform E.C.A. authorized service.
Blockage /
Locking
Er 37
BCC
Update error
BCC Update Process was not
successfulor BCC update not
started by user (Timeout error)
Inform E.C.A. authorized service.
Blockage /
Locking
Table 4