POWERCUBE User Manual
25
4 Use, maintenance and troubleshooting
4.1 Battery system usage and operation instructions
After completing the electrical installation, follow these steps to start the battery system.
1
Press the ON/OFF button to the ON position, press and hold the SW button for 3
seconds.
After the indicator self-test, the RUN indicator will light and the SOC indicator will
be on (100% SOC status in the Figure 4-1).
Figure4-1
Note:
After pressing the power button, if the battery status indicator on the front panel
of battery module continues to be red, please refer to the "4.2 Alarm description
and processing ". If the failure cannot be eliminated, please contact the dealer
timely.
2
Use a voltmeter to measure whether the voltage of circuit breaker battery access
terminal is greater than 42V, and check whether the voltage polarity is consistent
with the inverter input polarity. If the circuit breaker battery input terminal has a
voltage output and is greater than 42V, then the battery has started normal work.
3
After confirming that the battery output voltage and polarity are correct, turn off
the battery, set the DIP switch to the correct mode, then turn on the battery
system, and connect the communication line to the inverter.
4
Turn on the inverter and close the circuit breaker switch between the battery
system and the inverter.
5
Check whether the inverter and battery connection are normal (If the battery
access status indicator on the inverter is normal), and whether the communication
between the battery and the inverter is normal. If it is normal, the connection
between the battery and the inverter is completed. If the indicator light is
abnormal, please refer to the inverter manual for the cause or contact the dealer.
6
After confirming the normal state, install the front cover of the cabinet.
SW
SOC
ALM
CAN/485
IN
OUT
DRY CONTACT
RUN