10
5) Communication
The unit provides access to the internal registered values using the Modbus Protocol.
The diagram below shows the recommended connections to the Phoenix connectors on
the back of the unit for either half-duplex or full-duplex (RS485).
Note: The termination resistor is not included above and the user needs to connect this
resistor as needed by the wiring configuration.
The Modbus address registers defined below are input register type (Function Code 04)
using two’s complement representation for the signed integers.
Address
Description
Data type
30000
Status Register : Bits 0 - 9 Alarms, Bit 15 Run Status
Unsigned 16 bit integer
30001 - 30006
Absolute Values for Channels 1 – 6
Signed 16 bit integer
30007 - 30009
Differential Values for channels 1 & 2, 3 & 4, 5 & 6
Signed 16 bit integer
30010 - 30015
High Alarm Setting for Channels 1 - 6
Signed 16 bit integer
30016 - 30018
High Alarm Setting for Differentials 1 & 2, 3 & 4, 5 & 6
Signed 16 bit integer
30019 - 30024
Low Alarm Settings for Channels 1 - 6
Signed 16 bit integer
30025 - 30027
Low Alarm Settings for Differentials 1 & 2, 3 & 4, 5 & 6
Signed 16 bit integer
30028
RPM
Unsigned 16 bit integer
30029
Hour meter
Unsigned 16 bit integer