99.827.08 1.0/02/17

CDC-TW-0502-1-ACB

6/20

CDC-TW-0502-1-ACB

 

English

Intended use

- Chain drive for electric opening and closing of

  windows and flaps in the facade and roof area

- Operating voltage 24 V DC

- Useable for smoke ventilation as well as daily 

natural ventilation

- Suitable for indoor mounting only

Chain type

The mounting instructions for the bracket

set must be observed before mounting.

Always observe and comply with the

information in the mounting instructions.

Attention with side bow chains SBD and SBU 

-SBD

Standard chain

-SBU

Side bow chain

Side bow chain

Features

- ACB (Advanced Communication Bus) bus 

interface with ModBus protocol for the connection 

to compatible D+H control panels or direct 

integration into building management systems, 

for example

- BSY+ electronics for reliable and accurate 

synchronous operation

- Individually programmable via software SCS

- Outstanding quiet performance thanks to 

acoustic decoupling of the drive components and 

reduced motor speed in ventilation mode

- SHEV-high speed function (fast-running feature 

in case of an alarm)

- Protection system for the main closing edge

- Connection possible from both sides

- The force can be increased at the factory up to 

2x 400 N in the seal area

- Relief of pressure on window gasket after closing

- Direct connection of additional closing edge 

protection at the drive possible (SKS option)

Technical Data

* Programmable with software SCS   ** + approx. 20 % switch-off reserve (temporary)

Opening and Closing Ranges

Type

CDC-TW-0502-0500-1-ACB

CDC-TW-0502-0800-1-ACB

Power supply
Nominal force

24 V DC / ± 15 %

2x 250 N**

Nominal current

1,6 A

2,0 A

Nominal stroke length*

500 mm ± 2 %

800mm ± 2 %

Running speed: ventilation (SHEV high-speed function)*

O1, O2
O3
C3
C2, C1

6,7 mm/s (13,6 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s (13,6 mm/s)

5 mm/s (5 mm/s)

6,7 mm/s (15,0 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s (15,0 mm/s)

5 mm/s (5 mm/s)

Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*

2x approx. 1500 N

>10.000 double strokes

30 % S6 (EN 60034-1)

Aluminium powdercoated (~ RAL 9006)

IP 32

-5 ... +75 °C

30 min / 300 °C

≤ 90 %, not condensing

LpA = 35 dB(A)

Closing edge protection = activated (3 repetitions of stroke);

Locking relief  = activated (retraction lift max. 0,2 mm)

WARNING

Read all safety warnings, instructions, illustrations 

and specifications provided with this product.

Failure to follow all instructions listed below may 

result in electric shock, fire and/or serious injury.

Save all warnings and instructions for future 

reference.

Observe maximum pressure load of the chain!

Maximum pressure load 

per chain

 is not 

automatically identical with maximum pressure 

force of the drive!

Standard

-SBD / -SBU

100

200

300

400

500

600

700

800

250

300

350

400

200
150
100

50

0

Pressure load (N)

Stroke (mm)

250

50

Pressure load diagram

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 

protection for the main closing edge. If there is an 

overload in the closing ranges C3 and C2, the drive 

runs "OPEN" for 10 seconds, then "CLOSE" again. If 

closing is not possible after three attempts, the drive 

remains in this position.

In  addition,  the  drive  is  equipped  with  passive 

protection. The closing speed in closing range C2 

and C1 is reduced to 5 mm/s.

Significantly greater forces can be

exerted at the secondary closing

edges. Danger of crushing hands and

fingers!

Scope of supply

Drive unit with 2.5 m silicone cable.

Depending on the type of window, different bracket 

sets are available separately.

Main closing edge

Beside closing edge

Beside closing edge

C1*

C2*

23 mm

2x 150 N

77 mm

2x 150 N

C3*

250 mm

2x 250 N

O1*

O2*

O3*

23 mm

2x 250 N

15 mm

2x 250 N

2x 250 N

Safety notes

Safety extra low voltage 24 V DC!

Do not connect directly to the mains supply!

-   Connection must be carried out by a certified

   electrical technician

-   Danger of crushing hands and fingers!

-   Keep people away from the operating area of the

   drive

-   Keep children away from the control

-   Observe pressure load diagram of the chain

-   Use only in dry rooms

-   Suitable for indoor mounting only. Use rain

   detector in locations if there is a risk of rain

-   Use unmodified original D+H parts only

-   Observe mounting instructions of bracket set!

Observe enclosed red safety note!

Summary of Contents for CDC-TW-0502-0500-1-ACB

Page 1: ...CDC TW 0502 1 ACB instructions Please order bracket sets separately ...

Page 2: ...f pressure on window gasket after closing Direct connection of additional closing edge protection at the drive possible SKS option WARNING Read all safety warnings instructions illustrations and specifications provided with this product Failure to follow all instructions listed below may result in electric shock fire and or serious injury Save all warnings and instructions for future reference Obs...

Page 3: ... 30 S6 EN 60034 1 Aluminium powdercoated RAL 9006 IP 32 5 75 C 30 min 300 C 90 not condensing LpA 35 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm Closing edge protection In the CLOSE direction the drive has an active protection for the main closing edge If there is an overload in the closing ranges C3 and C2 the drive runs OPEN ...

Page 4: ...n with perfect position directly from the control panel In this process all status messages such as the OPEN and CLOSED signals opening stroke and drive errors are transmitted to the control panel Functional description Wiring Is the drive wired properly See connection plans Diagnostics with SCS software The SCS software and a BSY interface is required for further troubleshooting or configuration ...

Page 5: ...22949Ammersbek Dirk Dingfelder Maik Schmees Member of the Board Authorized signatory Technical Director 21 02 2017 Maintenance and cleaning Maintenance work is only allowed when the device is in a de energized condition Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used RepairistobecarriedoutexclusivelybyD H Wipe away debri...

Page 6: ... WH 24 V DC 24 V DC 1 2 3 4 5 L 6 N 7 Z A E X a b LT Gruppe Mot a Mot b MOT BK BK OG 2x47kW En dm od ul Te rm ina l mo du le Mo du le ter mi na l EM 47 K WH BN OG YE GN GY Mot a Mot b ACB a HS BSY a BSY b ACB b CDC TW 0502 1 Junction box Monitoring SHEV fast running Normal mode ...

Page 7: ...itoring Cable according to D H table for layout of cables See instructions for use of control panel 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group Mot a Mot b MOT BK BK OG 2x47kW En dm od ul Te rm ina l mo du le Mo du le ter mi na l EM 47 K WH BN OG YE GN GY Mot a Mot b ACB a HS BSY a BSY b ACB b CDC TW 0502 1 Junction box Monitoring Connection FRA 11 BSY VLD 51 BSY VP FRA 11 BSY VLD 51 BSY Mot a Mot b BS...

Page 8: ...a BN Mot b OG ACB a HS GY ACB b GN BSY b YE BSY a WH Mot a Option Opción SKS BN Mot b OG SKS GY SKS GN BSY b YE BSY a WH Mot a BN Mot b OG ACB a HS GY ACB b GN BSY b YE BSY a WH Mot a Connection PinAssignment Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 161 491 4840 E Mail enquiry dyerenvironmental co uk www dyerenvironmental co uk ...

Reviews: