CONFIGURATION MENU
DO NOT ENTER THE CONFIGURATION MENU UNLESS
YOU HAVE BEEN INSTRUCTED TO BY ANOTHER PART
OF THESE INSTRUCTIONS. INCORRECT ENTRY OF
DATA IN THE CONFIGURATION MENU MAY PREVENT
YOUR CONTROL FROM OPERATING PROPERLY.
The Configuration Menu is used to quickly configure the instrument. The
configuration for your particular model is shown on the Model / Serial label
located on the top of the instrument housing. A label found inside on the right
printed circuit board only shows the hardware configuration and options.
The numbers shown are defined as follows:
The Hardware configuration code must not be changed as it defines the
hardware for the specific instrument. All other configuration may be altered
if necessary. It is important that the codes be correctly entered in order for
the instrument to function properly. If an invalid code number is entered for
a particular configuration item, it will not be accepted and the old configura-
tion code will be retained.
If you wish to return the settings to the factory default values, follow sep 1
below to enter the configuration menu. Then skip to step 13 and follow the
directions there.
To re-configure:
1.
At power up, simultaneously press and hold the INDEX & ENTER keys
while the lamp test or self test is displayed. Hold the keys down until
Hrd1 appears. A dash appears in the upper display.
2.
If your control is equipped with the optional alarm, press the UP ARROW
until the upper display reads 1, and press ENTER.
Hardware
Options
Configuration
Model 16
Input Type
Temperature Descriptor
SP1 & SP2 Action
Alarm State
Alarm Action
Alarm Type