DISPLAY
No
display
lighted
FAIL
tESt
CHEC
SP1,
CHEC
SP2,
CHEC
1rt,
CHEC
1St,
CHEC
SPL
or
CHEC
SPH
CHEC
rSpt
CHEC
LorE
ArEA
MEANING
Display is blank. In-
strument is not get-
ting power, or the
supply voltage is too
low.
Fail test appears
upon power up if the
internal diagnostics
detect a failure. This
message may oc-
cur during operation
if a failure is detect-
ed. Displays flash.
This message will
appear upon power
up if SP1, SP2, 1rt,
or 1St is set outside
of the SPL or SPH
values.
This message ap-
pears at power up if
SPL or SPH values
are programmed
outside the input
range ends.
This message ap-
pears if the analog
remote set point sig-
nal is out of range.
This message ap-
pears if the Serial
C o m m u n i c a t i o n s
has timed out.
This message ap-
pears if the ambiient
temperature of the
control is near or out
of range or RJC sen-
sor is broken.
SP OUTPUTS
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm inactive
Set point
outputs inactive
Alarm active
Set point
outputs inactive
Alarm inactive
Set point
outputs active
Alarm inactive
Set point
outputs active
Alarm inactive
Set point
outputs active
Alarms active
ACTION REQUIRED
Check that the power supply is
on, or that the external fuses
are good.
The display alternate between
FAIL tESt and one of the fol-
lowing messages: FACt dFLt:
Memory may be corrupted.
Press the ENTER key and the
DOWN ARROW key to start
the factory default procedure
(Page 30). Recheck controller
programming. rEt FACt: Un-
recoverable error, return to fac-
tory for service.
Correct the SP1, etc. or adjust
the SPL or SPH values by
programming new values.
Correct the SPL or SPH val-
ues by programming new val-
ues.
The control will revert to SP1.
Correction of the analog sig-
nal allows the control to return
to the remote
Restore the communications
line and switch the LorE to
LOC.
Correct the ambient tempera-
ture conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC bro-
ken, return to factory for ser-
vice.
DIAGNOSTIC ERROR MESSAGES