ALt
Alarm Type: Select AbS or dE
AbS
Absolute Alarm that may be set anywhere within the
values of SPL and SPH and is independent of SP1.
dE
Deviation Alarm that may be set as an offset from SP1.
As SP1 is changed the Alarm Point will track with SP1.
ALrE
Alarm Reset: Select OnOF or Hold.
OnOF
Automatic Reset.
Hold
Manual Reset. Acknowledge by simultaneously press-
ing the INDEX & DOWN ARROW keys for 5 sec.
ALPi
Alarm Power Interrupt: Select On or OFF.
On
Alarm Power Interrupt is ON.
OFF
Alarm Power Interrupt is OFF.
ALiH
Alarm Inhibit: Select On or OFF.
On
Alarm Inhibit is ON. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.
ALSt
Alarm Output State: Select CLOS or OPEn.
CLOS
Closes Contacts at Alarm Set Point.
OPEn
Opens Contacts at Alarm Set Point.
ALLP
Alarm Lamp: Select O on or OoFF.
O on
Alarm Lamp is ON when alarm contact is closed.
OoFF
Alarm Lamp is OFF when alarm contact is closed.
ALbr
Alarm Loop Break: Select On or OFF.
On
Loop Break Condition will cause an Alarm Condition.
OFF
Loop Break will not affect the Alarm Condition.
The following Secure menu items apply only to Options. They may not
appear in your control.
SPSA
Set Point Select Action (948): Select rE or Int.
rE
Remote (external) selection of active set point value.
Int
Internal selective of active set point value.
Addr
Control Address (992): Set from 1 to FF. This number (hexadeci-
mal, base 16) must match the address number used by the host
computer.