Rev. 10/98
21
949-1239-3
CFSP
Communications Fail Set Point (992): Set to desired value.
Addr
Control Address (992): Set from 1 to FF. This number (hexadeci-
mal, base 16) must match the address number used by the host
computer. Viewed only in this menu.
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to change the
lower display. Press UP ARROW or DOWN ARROW to change the value
in the upper display.
SECr
Security Code: See the Security Level Selection and the Pass-
word Table in this manual, in order to enter the correct password.
InP
Input Type: Select one of the following. The Inputs are based on
four different groups; Thermocouples, RTD’s, Current, and Volt-
age. If changing from one of these groups, the DIP switch on the
A/D circuit board will have to be changed to match that particular
group. Refer to the Input wiring section for the proper switch
settings.
J-IC
Type “J” Thermocouple
CA
Type “K” Thermocouple
E-
Type “E” Thermocouple
t-
Type “T” Thermocouple
L-
Type “L” Thermocouple
n-
Type “N” Thermocouple
r-13
Type “R” Thermocouple
S-10 Type “S” Thermocouple
b-
Type “B” Thermocouple
C-
Type “C” Thermocouple
P392 100 ohm Platinum (NIST 0.00392
Ω
/
Ω
/°C), Love
Cal. 104.
n120 120 ohm Nickel, Love Cal. 105.
P385 100 ohm Platinum (DIN 0.00385
Ω
/
Ω
/°C), Love Cal.
106.
Curr DC Current Input 0.0 to 20.0 or 4.0 to 20.0 milliam-
peres.
UoLt DC Voltage Input 0.0 to 5.0 or 1.0 to 5.0 volts.
- - - -
Reserved
OSUP
Zero Suppression: Select On or OFF. Only with Current and
Voltage input types.
OFF
The input range will start at 0 (zero) Input.
On
The input range will start at 4.00 mA or 1.00 V.