Dwyer Instruments AVLV Series Specifications-Installation And Operating Instructions Download Page 7

Coils

The coil registers represent functions of the device. The value returned when reading 

a coil register indicates the status of the last function execution. If the value is 1, then 

the last time the function executed was a success. If the value is 0, then the function 

has either not been executed since power on or failed during the last execution. To 

execute a function, write 1 to the corresponding register. A response will be returned 

immediately and the value of the coil will be set to 0. Once the function completes, 

the value of the coil will be set to 1 if the operation was a success. An application 

should poll the value of the coil periodically during this time to determine if the function 

succeeded. If the coil value does not transition to 1 after at most 10 seconds, then the 

operation failed.

Coil 1 – Zero Function

The zero function will attempt to recalibrate the zero point. This may be needed if the 

sensor has drifted over time. Note that the zero function will only re-zero the sensor 

if the current air velocity is within ±2% of span air velocity of the previous zero. If the 

current air velocity is outside the valid band, the zero function will fail and the coil value 

will remain 0. If the sensor has drifted far enough that the zero function fails, then the 

unit will have to be placed in flow to bring the current air velocity closer to the current 

zero, and the zero function will have to be executed multiple times until the actual zero 

is reached.

Coil 2 – Span Function

The  span  function  will  attempt  to  recalibrate  the  maximum  air  velocity.  Note  that 

accurate span air velocity depends on an accurate zero air velocity. The span function 

will fail if the zero function has not been executed within the last 5 minutes.

Coil 3 – Reset factory Defaults Function

The reset factory defaults function resets the zero, span, Velocity K value, Area,  and 

Use Default K Value variables back to their factory default values. 

Coil 4 – Reset Device Function

The reset device function allows this device to be reset remotely from the Modbus

® 

Communication Protocol. When the reset device function coil is written with a value 

of  1,  the  device  will  immediately  respond  with  success.  The  reset  will  take  place 

approximately 5 seconds after the command was received. Writing the value 0 to this 

coil has no effect.

Multi-address Support

Multi-Address support allows a register to be read or written to using different byte 

orientations specified by the address range. For example, input register 0003 can also 

be read at 2003, 4003 and 6003 with different byte orientations as listed in Table 10. 

Registers that do not have multi-address support are only available in Big-Endian byte 

orientation (Modbus

®

 Communication Protocol standard).

APPENDIX V: Setting Modbus

®

 Communication Protocol MAC Address of Unit

The address assignment is determined by adding the values for each of the switches 

that are in the ON position. The transmitter comes from the factory with all of the DIP 

switches, except position 1, in the ON position as shown in Figure 10. The address 

of the transmitter would be 127 as it would be 64+32+16+8+4+2+1 = 127. Another 

example would be if the address desired was 008, the only DIP switch position in the 

ON position would be position 5 as shown in Figure 11

Register Description

Data Type Value Range

Multi-

Address 

Supported

0001

0002

0003

0004

Perform Zero Function

Perform Span Function

Reset Factory Defaults

Reset Device

Boolean

Boolean

Boolean

Boolean

0…1

0…1

0…1

0…1

False – True

False – True

False – True

False – True

No

No

No

No

Table 9: Coils

Float/32 Bit Values

16 Bit Values

Register 1 Register 2 Register 1

Byte Order Address Range MSB

LSB MSB

LSB

Big-Endian

Byte Swap

Word Sway

Little-Endian

1 – 2000

2001 – 4000

4001 – 6000

6001 - 8000

A

B

C

D

B

A

D

C

C

D

A

B

D

C

B

A

A

B

A

B

B

A

B

A

Table 10: Multi-address support

.

Switch Position 1

2

3

4

5

6

7

8

Address Value

128 64

32

16

8

4

2

1

Table 11: Device objects

Though the minimum possible address would be address 0 when 

all the DIP switch positions were set to OFF, and the maximum 

possible address would be address 255 when all of the DIP switches were set to ON, 

but the transmitter only has valid address from 1 to 247. Any address outside of this 

range will give an error code.

NOTICE

APPENDIX VI: Modbus

®

 Communication Protocol Registers

Register Description

Data Type

Value

Range

Multi-

Address 

Supported

0001

0002

0003

0004

0005

0006

0007 – 

0008

0009 – 

0010

0011 – 

0012

0013 – 

0014

0015 – 

0016

0017 – 

0018

0019

0020 – 

0021

8001 – 

8006

8007 – 

8012

8013 – 

8018

8019 – 

8024

Velocity (FPM)

Velocity (0.001 MPS)

Flow (CFM)

Flow (CMH)

Temperature (0.1 °F)

Temperature (0.1 °C)

Velocity (FPM)

Velocity (MPS)

Flow (CFM)

Flow (CMH)

Temperature (°F)

Temperature (°C)

Sensor Operational

Sensor 

Communication 

Errors

Modbus

®

 Application 

Firmware Version

Sensor Application 

Firmware Version

Modbus

®

 Application 

Serial Number

Sensor Application 

Serial Number

Signed 16bit 

integer

Signed 16bit 

integer

Signed 16bit 

integer

Signed 16bit 

integer

Signed 16bit 

integer

Signed 16bit 

integer

Float

Float

Float

Float

Float

Float

Unsigned 16bit 

integer

Unsigned 32bit 

integer

String

String

String

String

 

 

 

 

 

 

 

 

 

 

 

0…1

0…2

32

-1

 

 

 

 

 

 

 

 

 

 

 

False – 

True

0…232-

1

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

Table 12: Modbus

®

 communication protocol registers

Figure 10

Figure 11

ON

1

2

3

4

5

6

7

8

Summary of Contents for AVLV Series

Page 1: ...al Connections Analog Power and output four wire removable European style terminal block for 16 to 26 AWG Communication Connections BACnet MS TP or Modbus RTU ASCII three wire removable European style terminal block for 16 to 26 AWG Supported Communication Baud Rates 9600 19200 38400 57600 76800 115200 optional Device Load 1 8 unit load Electrical Entry 1 2 NPS thread Accessory Cable gland for 5 t...

Page 2: ...aximum current loop load resistance RMAX is defined by the following the equation RMAX VPS 2 0 0 02 where VPS is the power supply voltage For a 24 VDC nominal power supply this evaluates to RMAX 1100 ohms Shielded two wire cable is recommended for current output loop wiring Ground the shield at the power supply end only The maximum length of connecting wire between the current transmitter and the ...

Page 3: ...Table 2 shows the values The units will be displayed on the optional LCD display if connected The default operating mode is velocity but changes can be made such as flow mode via the menu system while an optional display or remote display accessory is connected Please refer to Appendix VI for a full menu flow chart Setting the Output Voltage Range Voltage Output can be either 0 5 VDC or 0 10 VDC d...

Page 4: ...e pressed the air velocity value is out of the range to allow a correct setting This may be due to a sensor failure Err1 The sensor is damaged PROGRAMMING MENUS Home Menu During normal operation the display will be in the Home Menu and will display the current measured pressure and the engineering units Menu Access Security While in the Home Menu press and hold the Zero and Span buttons simultaneo...

Page 5: ...s and no will discard all the changes made to all menu items If the display is set to yes pressing and holding the span will save the menu items and return the display to the home position FACTORY DEFAULT PROCEDURE In order to reset all of the menu settings back to their factory programmed values press and hold both the span and zero buttons simultaneously for 10 seconds until FACt is displayed on...

Page 6: ... then apply power The device will power up and begin examining the serial bus for communication The Red LED will repeatedly flash twice indicating that intelligent serial configuration is in progress If the device is setup offline or away from the main network it is necessary to generate Modbus Communication Protocol traffic in order to configure the serial communication Attempting to read input r...

Page 7: ...different byte orientations as listed in Table 10 Registers that do not have multi address support are only available in Big Endian byte orientation Modbus Communication Protocol standard APPENDIX V Setting Modbus Communication Protocol MAC Address of Unit The address assignment is determined by adding the values for each of the switches that are in the ON position The transmitter comes from the f...

Page 8: ...CETO NEXT DIGIT ACTIVE DIGITWILL BLINK SPAN BLINKING DIGIT ZERO SPAN HOME POSITION SECURITY LEVEL SELECTION WHILE BUTTONS ARE PRESSED WHEN BUTTONS ARE RELEASED DISPLAYS CURRENT SECURITY LEVEL ZERO SPAN HOLD 7 SECONDS TO HOME POSITION FACTORY SETTINGS RESTORED THEN RETURNS ZERO TO CHANGE SECURITY LEVEL INCREMENT SELECT ZERO SPAN DIGIT DIGIT SECURITY LEVEL SETTING 0 000 1 111 2 222 3 333 SPAN SPAN I...

Page 9: ...ASE SPAN SPAN UPON RELEASE SPAN TO UPDATE SECURITY AND SAVE MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED SELECT MAXIMUM OUTPUT SET BY PRESSURE OR ADJUSTVELOCITY OUTPUT HIGH VELOCITY K FPM M S Velocity Mode Menu ...

Page 10: ...E MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED ADJUST FLOW OUTPUT HIGH K CFM M H INCREMENT SELECT ZERO SPAN DIGIT DIGIT F AREA SQ FEET OR SQ METERS BASED ON DIP SWITCH SETTING M AREA SPAN UPON RELEASE SPAN SELECT MAXIMUM OUTPUT SET BY PRESSURE OR FLOW 3 Flow Mode Menu ...

Page 11: ...FROM UPDATE SECURITY AND SAVE MENU UPDATE SECURITY LEVEL ZERO ZERO ZERO SPAN SPAN SPAN SPAN ZERO SAVE CHANGES SPAN UPON RELEASE ZERO ZERO SPAN SPAN HOME POSITION Security Menu ...

Page 12: ...______________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ___________________________________________________...

Reviews: