Dwyer Instruments AVLV Series Specifications-Installation And Operating Instructions Download Page 5

Mode Selection / Digital Dampening Menu

From  the  home  display,  pressing  the  span  and  zero  button  simultaneously  for  3 

seconds will access the Menu Security Level.  If the level is set to 0 or 1, pressing and 

holding the span button for 3 seconds, a second time, will access the Mode Selection 

Menu. The display will default to air velocity when first powered up. Pressing the zero 

button will cycle to air flow. 

Once  the  desired  mode  is  displayed,  pressing  and  holding  the  span  button  for  3 

seconds will save the selected mode and display the digital dampening or averaging 

parameter.  This  parameter  stabilizes  the  output  and  the  display  by  averaging  the 

readings.  There  are  2.5  readings  taken  each  second  and  the  user  can  select  the 

number of seconds that they would like to average, up to 240 seconds. The display 

and the output will continue to update at a rate of 2.5 updates per second, but the 

moving average is used for these updates.

Velocity Mode

K-Factor Adjustment

If the Velocity Mode was selected, pressing and holding the span after adjusting the 

digital  dampening  will  enter  the  Velocity  Mode  and  the  transmitter  will  display  the 

engineering unit that has been selected by the DIP switch. Pressing and holding the 

span button for 3 seconds will enter the K – Factor adjustment. The K – Factor can 

be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the 

span button to select the digit and pressing the zero button to increment the value of 

the digit. Pressing and holding the span button for 3 seconds will enter the Maximum 

Output Adjustment parameter.

Flow Mode

K-Factor Adjustment

If the Flow Mode was selected, pressing and holding the span after adjusting the digital 

dampening will enter the Flow Mode and the transmitter will display the engineering 

unit that has been selected by the DIP switch. Pressing and holding the span button for 

3 seconds will enter the K–Factor adjustment. The K–Factor can be adjusted between 

0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select 

the digit and pressing the zero button to increment the value of the digit. Pressing and 

holding the span button for 3 seconds will enter the Area Adjustment parameter.

Area Adjustment

For flow applications, the area is multiplied by the velocity to determine the volumetric 

air flow. The area will be listed in either CFM or m

3

/h depending on the DIP switch 

settings. The units will appear on the display at the time of adjustment. The area can 

be adjusted by pressing the span button to select the digit and pressing the zero button 

to increment the value of the digit. Pressing and holding the span button for 3 seconds 

will enter the Maximum Output Adjustment parameter.

Maximum Output Adjustment

The  maximum  output  can  be  equivalent  to  air  velocity  or  air  flow.  After  adjusting 

the K-Factor, the display will indicate if the adjustment is set for velocity or air flow.  

Pressing the zero button will toggle between the selections. Pressing and holding the 

span button for 3 seconds will enter the maximum output adjustment. The maximum 

output can be adjusted by pressing the span button to select the digit and pressing the 

zero button to increment the value of the digit. Pressing and holding the span button 

for 3 seconds will save this value and go to the Security Update Menu.

Security Update / Save Changes Menu

The Security Update Menu allows the security level to be set either higher or lower 

than the current security level setting. This security level will be displayed the next 

time the Menus are accessed from the home screen.  Pressing the zero button cycles 

through  the  security  levels.  Pressing  and  holding  the  span  button  for  3  seconds 

accepts the new security level and gives the option to save all the menu changes. 

Pressing the zero button will toggle between yes and no. Yes will save the changes 

made to all menu items and no will discard all the changes made to all menu items.  If 

the display is set to yes, pressing and holding the span will save the menu items and 

return the display to the home position.

FACTORY DEFAULT PROCEDURE

In order to reset all of the menu settings back to their factory programmed values, 

press and hold both the span and zero buttons simultaneously for 10 seconds until 

FACt

  is  displayed  on  the  LCD.  Upon  releasing  the  buttons,  the  unit  will  be  factory 

defaulted.  Since resetting the transmitter will wipe out all changes, it is necessary to 

zero (and possibly span) the transmitter before taking measurements.

Table 3: Security settings

Wiring should comply with Electrical Characteristics of

Generators and Receivers for Use in Balanced Digital Multipoint

Systems, TIA/EIA-485-A-1998, Telecommunications Industry Association, 1998.

NOTICE

Wiring should comply with Modbus® Communication Protocol

over Serial Line Specification and Implementation Guide V1.02,

Modbus Organization, Inc., 2006

NOTICE

Communications wiring must be in a daisy-chain fashion. Star

connections are not permitted.

NOTICE

Cable shield must be connected to earth ground at one location

only.

NOTICE

MAINTENANCE/REPAIR

Upon  final  installation  of  the  Series  AVLV  Air  Velocity  Transmitter,  no  routine 

maintenance is required besides zeroing the transmitter occasionally. Besides routine 

calibration and installation of the LCD, the  Series AVLV is not field serviceable, and 

it is not possible to repair the unit. Field repair should not be attempted and may void 

warranty.

WARRANTY/RETURN

Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact 

customer service to receive a Return Goods Authorization number before shipping the 

product back for repair. Be sure to include a brief description of the problem plus any 

additional application notes.

APPENDIX I: Air Velocity / Air Flow Calculations

Velocity in m/s is then calculated from the equation:

Velocity (m/s) = Velocity (FPM) x 0.00508

Flow in m

3

/h is then calculated using the below equation:

Flow (CFM) = Area (ft

2

) x K-Factor x Velocity (FPM)

Flow (m

3

/h) = Flow (CFM) x 1.6992

APPENDIX II: Maximum Flow

APPENDIX III: Modbus

®

 Communication Protocol Operation

Figure 7 shows how to connect the AVLV in a network containing a common power 

supply. Use a cable containing two twisted pairs. One pair is to be used for D1(+) 

and D0(-). The other pair is to be used for power and common. This configuration is 

not suitable for AC supplies. Use a DC supply only. Care should be taken that there 

are not too many devices powered from the same supply as voltage drops will occur 

in  the  wiring.  If  you  have  many  devices,  or  have  long  cable  runs,  the  local  supply 

configuration may be a better choice. 

Figure  8  shows  how  to  connect  the AVLV  in  a  network  containing  individual  local 

supplies. Use a cable containing a twisted pair and a single conductor. The pair is to 

be used for D1(+) and D0(-). The single conductor is to be used for common. Both AC 

and DC supplies are suitable for this configuration. 

In either configuration you must use shielded cable. The AVLV has a shield terminal 

for a convenient location to make connections. It is not electrically connected to the 

AVLV. Connect the shield to earth ground at one location only to prevent ground loops.

All devices in the network should be daisy chained. Star connections and T

connections are not permitted. 

The D1(+) and D0(-) lines must be terminated at both ends with a 120 ohm resistor. If 

the AVLV is an end device it has an on-board resistor that may be used. See Modbus® 

Communication Protocol DIP Switch Settings to enable it. 

The network must be biased properly. If needed, there are bias resistors on-board the 

AVLV. No more than two sets of bias resistors should be enabled in the network.  See 

Modbus

®

 Communication Protocol DIP Switch Settings to enable them.

Security 

Level

Setting

Access

View Menu Edit Menu Span Zero

0

1

2

3

000

111

222

333

Yes

Yes

No

No

Yes

No

No

No

Yes

No

No

No

Yes

Yes

No

No

Table 4: Maximum flow values

Max Flow

Max K Factor x Area

CFM

m

3

/h

CFM Range m

3

/h Range

5885000 9999000 14712.5

1388.75

Summary of Contents for AVLV Series

Page 1: ...al Connections Analog Power and output four wire removable European style terminal block for 16 to 26 AWG Communication Connections BACnet MS TP or Modbus RTU ASCII three wire removable European style terminal block for 16 to 26 AWG Supported Communication Baud Rates 9600 19200 38400 57600 76800 115200 optional Device Load 1 8 unit load Electrical Entry 1 2 NPS thread Accessory Cable gland for 5 t...

Page 2: ...aximum current loop load resistance RMAX is defined by the following the equation RMAX VPS 2 0 0 02 where VPS is the power supply voltage For a 24 VDC nominal power supply this evaluates to RMAX 1100 ohms Shielded two wire cable is recommended for current output loop wiring Ground the shield at the power supply end only The maximum length of connecting wire between the current transmitter and the ...

Page 3: ...Table 2 shows the values The units will be displayed on the optional LCD display if connected The default operating mode is velocity but changes can be made such as flow mode via the menu system while an optional display or remote display accessory is connected Please refer to Appendix VI for a full menu flow chart Setting the Output Voltage Range Voltage Output can be either 0 5 VDC or 0 10 VDC d...

Page 4: ...e pressed the air velocity value is out of the range to allow a correct setting This may be due to a sensor failure Err1 The sensor is damaged PROGRAMMING MENUS Home Menu During normal operation the display will be in the Home Menu and will display the current measured pressure and the engineering units Menu Access Security While in the Home Menu press and hold the Zero and Span buttons simultaneo...

Page 5: ...s and no will discard all the changes made to all menu items If the display is set to yes pressing and holding the span will save the menu items and return the display to the home position FACTORY DEFAULT PROCEDURE In order to reset all of the menu settings back to their factory programmed values press and hold both the span and zero buttons simultaneously for 10 seconds until FACt is displayed on...

Page 6: ... then apply power The device will power up and begin examining the serial bus for communication The Red LED will repeatedly flash twice indicating that intelligent serial configuration is in progress If the device is setup offline or away from the main network it is necessary to generate Modbus Communication Protocol traffic in order to configure the serial communication Attempting to read input r...

Page 7: ...different byte orientations as listed in Table 10 Registers that do not have multi address support are only available in Big Endian byte orientation Modbus Communication Protocol standard APPENDIX V Setting Modbus Communication Protocol MAC Address of Unit The address assignment is determined by adding the values for each of the switches that are in the ON position The transmitter comes from the f...

Page 8: ...CETO NEXT DIGIT ACTIVE DIGITWILL BLINK SPAN BLINKING DIGIT ZERO SPAN HOME POSITION SECURITY LEVEL SELECTION WHILE BUTTONS ARE PRESSED WHEN BUTTONS ARE RELEASED DISPLAYS CURRENT SECURITY LEVEL ZERO SPAN HOLD 7 SECONDS TO HOME POSITION FACTORY SETTINGS RESTORED THEN RETURNS ZERO TO CHANGE SECURITY LEVEL INCREMENT SELECT ZERO SPAN DIGIT DIGIT SECURITY LEVEL SETTING 0 000 1 111 2 222 3 333 SPAN SPAN I...

Page 9: ...ASE SPAN SPAN UPON RELEASE SPAN TO UPDATE SECURITY AND SAVE MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED SELECT MAXIMUM OUTPUT SET BY PRESSURE OR ADJUSTVELOCITY OUTPUT HIGH VELOCITY K FPM M S Velocity Mode Menu ...

Page 10: ...E MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED ADJUST FLOW OUTPUT HIGH K CFM M H INCREMENT SELECT ZERO SPAN DIGIT DIGIT F AREA SQ FEET OR SQ METERS BASED ON DIP SWITCH SETTING M AREA SPAN UPON RELEASE SPAN SELECT MAXIMUM OUTPUT SET BY PRESSURE OR FLOW 3 Flow Mode Menu ...

Page 11: ...FROM UPDATE SECURITY AND SAVE MENU UPDATE SECURITY LEVEL ZERO ZERO ZERO SPAN SPAN SPAN SPAN ZERO SAVE CHANGES SPAN UPON RELEASE ZERO ZERO SPAN SPAN HOME POSITION Security Menu ...

Page 12: ...______________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ___________________________________________________...

Reviews: