Dwyer Instruments AVLV Series Specifications-Installation And Operating Instructions Download Page 6

Modbus

®

 Communication Protocol DIP Switch Settings

Use the middle DIP Switch SW2 to configure the Modbus

®

 Communication Protocol 

address of the device. The LCD will show the address when the transmitter is powered 

on. Valid addresses range from 1 to 247. By default, the device is shipped with the 

address 127 (as shown in Figure 10). A valid and unused address should be set before 

connecting to an existing network. However, the address can be changed while the 

device is operational. If the address is changed, the device will stop responding to the 

currently configured address immediately. The device waits 15 seconds after the last 

switch change before applying the new address. The device will not function properly 

if an invalid address is set. The red LED will periodically blink once indicating an invalid 

address. The LCD will display 

A Err 

when the transmitter is powered on if the address 

is invalid. See Appendix V for setting the Modbus

®

 Communication Protocol address 

of the device. Use the right DIP Switch SW3 to configure other hardware and software 

options.

PWR GND IOUT VOUT

TO NEXT

DEVICE

D1(+)

D0(-)

PWR

COM

D1(+)

D0(-)

PWR

COM

TO PREVIOUS

DEVICE

D1(+) D0(-) COM

Figure 7: Common power supply

D1(+)

D0(-)

COM

D1(+)

D0(-)

COM

POWER

SUPPLY

+ -

PWR GND IOUT VOUT D1(+) D0(-) COM

Figure 8: Local power supply

SW2

KEY:

AUTO SERIAL

CONFIGURATION

TERMINATING

RESISTOR

BIAS

RESISTOR

128 - MSB

64

32

16

8

4

2

1 - LSB

Figure 9

Switch

On

Off

1-2 – Display Units Selection

3-4 – Reserved

5 - Intelligent Serial 

Configuration

6 – D1(+) Network resistor

7 – D0(-) Network resistor

8 – Terminating resistor

Enabled

511Ω Pull-up to 5V

511Ω Pull-down to GND

120Ω between D0(-) and 

D1(+)

Disabled

Pull-up not connected

Pull-down not 

connected

Open

Table 5: DIP switch SW3 functions

APPENDIX IV: Programming Via Modbus

®

 Communication Protocol

Intelligent Serial Configuration

Intelligent  serial  configuration  enables  the  device  to  determine  the  baud  rate,  data 

size, party, stop bits and even the Modbus

®

 Communication Protocol mode directly 

from the serial traffic. This allows the Series AVLV to be quickly and easily deployed 

after a valid Modbus

®

 Communication Protocol address is chosen. 

To activate intelligent serial configuration, set a valid Modbus

®

 Communication Protocol 

address using the left DIP switch SW2, connect the serial bus and power wires, and 

then apply power. The device will power up and begin examining the serial bus for 

communication.  The  Red  LED  will  repeatedly  flash  twice,  indicating  that  intelligent 

serial configuration is in progress. 

If  the  device  is  setup  offline  or  away  from  the  main  network,  it  is  necessary  to 

generate  Modbus

®

  Communication  Protocol  traffic  in  order  to  configure  the  serial 

communication.  Attempting  to  read  input  registers  is  a  good  method  to  generate 

Modbus

®

  Communication  Protocol  traffic.  Note  that  while  serial  configuration  is  in 

progress, the device may not respond to requests. The device may require multiple 

read requests to complete the serial configuration process. 

The intelligent serial configuration process will complete once a message addressed 

to  the  device  is  received  and  processed  successfully.  The  serial  configuration 

parameters are then saved to non-volatile storage and loaded by default each time the 

device starts. If the serial configuration of the bus changes, a power cycle of the device 

is required to restart the Intelligent Serial Configuration process.

The String data type is read as a stream of ASCII characters, with the first character 

sent in the MSB of the first register, and the second character sent in the LSB of the 

first register and so on. If the string is shorter than the allotted size, the remaining bytes 

will be zero padded.

1 - The serial configuration, no parity with one stop bit is not officially supported by the 

Modbus

®

 Communication Protocol standard. However, if this configuration is desired, 

set switch 5 on DIP switch SW3 to off. The device will configure itself in Modbus

®

 RTU 

Communication Protocol mode with a data size of 8, no parity, and 1 stop bit. The baud 

rate will still be determined automatically.

Modbus

®

 Mode Supported Baud Rates Data Size Parity Stop Bits

RTU

9600

19200

38400

57600

76800

115200

8

Even

Odd

None

1

1

None 2

ASCII

7

Even

Odd

1

None 2

Table 6: Supported Modbus

®

 communication protocol configurations

Function Name

Function Code

Read Coils

Read Holding Registers

Read Input Registers

Write Single Coil

Write Single Register

Write Multiple Registers

01

03

04

05

06

16

Table 7: Supported Modbus

®

communication protocol functions

Register Description Data Type Value

Range

Multi-

Address 

Supported

0001 – 

0002

0003 – 

0004

Register

Velocity 

Flow Area 

(ft2)

Velocity 

Flow Area 

(m2)

Description

Float

Float

Data Type

0.01…999.99

0.00093…92.9

Value

0.01…999.99

0.00093…92.9

Range

Yes

Yes

Multi-

Address 

Supported

Table 8: Holding registers

Summary of Contents for AVLV Series

Page 1: ...al Connections Analog Power and output four wire removable European style terminal block for 16 to 26 AWG Communication Connections BACnet MS TP or Modbus RTU ASCII three wire removable European style terminal block for 16 to 26 AWG Supported Communication Baud Rates 9600 19200 38400 57600 76800 115200 optional Device Load 1 8 unit load Electrical Entry 1 2 NPS thread Accessory Cable gland for 5 t...

Page 2: ...aximum current loop load resistance RMAX is defined by the following the equation RMAX VPS 2 0 0 02 where VPS is the power supply voltage For a 24 VDC nominal power supply this evaluates to RMAX 1100 ohms Shielded two wire cable is recommended for current output loop wiring Ground the shield at the power supply end only The maximum length of connecting wire between the current transmitter and the ...

Page 3: ...Table 2 shows the values The units will be displayed on the optional LCD display if connected The default operating mode is velocity but changes can be made such as flow mode via the menu system while an optional display or remote display accessory is connected Please refer to Appendix VI for a full menu flow chart Setting the Output Voltage Range Voltage Output can be either 0 5 VDC or 0 10 VDC d...

Page 4: ...e pressed the air velocity value is out of the range to allow a correct setting This may be due to a sensor failure Err1 The sensor is damaged PROGRAMMING MENUS Home Menu During normal operation the display will be in the Home Menu and will display the current measured pressure and the engineering units Menu Access Security While in the Home Menu press and hold the Zero and Span buttons simultaneo...

Page 5: ...s and no will discard all the changes made to all menu items If the display is set to yes pressing and holding the span will save the menu items and return the display to the home position FACTORY DEFAULT PROCEDURE In order to reset all of the menu settings back to their factory programmed values press and hold both the span and zero buttons simultaneously for 10 seconds until FACt is displayed on...

Page 6: ... then apply power The device will power up and begin examining the serial bus for communication The Red LED will repeatedly flash twice indicating that intelligent serial configuration is in progress If the device is setup offline or away from the main network it is necessary to generate Modbus Communication Protocol traffic in order to configure the serial communication Attempting to read input r...

Page 7: ...different byte orientations as listed in Table 10 Registers that do not have multi address support are only available in Big Endian byte orientation Modbus Communication Protocol standard APPENDIX V Setting Modbus Communication Protocol MAC Address of Unit The address assignment is determined by adding the values for each of the switches that are in the ON position The transmitter comes from the f...

Page 8: ...CETO NEXT DIGIT ACTIVE DIGITWILL BLINK SPAN BLINKING DIGIT ZERO SPAN HOME POSITION SECURITY LEVEL SELECTION WHILE BUTTONS ARE PRESSED WHEN BUTTONS ARE RELEASED DISPLAYS CURRENT SECURITY LEVEL ZERO SPAN HOLD 7 SECONDS TO HOME POSITION FACTORY SETTINGS RESTORED THEN RETURNS ZERO TO CHANGE SECURITY LEVEL INCREMENT SELECT ZERO SPAN DIGIT DIGIT SECURITY LEVEL SETTING 0 000 1 111 2 222 3 333 SPAN SPAN I...

Page 9: ...ASE SPAN SPAN UPON RELEASE SPAN TO UPDATE SECURITY AND SAVE MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED SELECT MAXIMUM OUTPUT SET BY PRESSURE OR ADJUSTVELOCITY OUTPUT HIGH VELOCITY K FPM M S Velocity Mode Menu ...

Page 10: ...E MENU INCREMENT SELECT ZERO SPAN DIGIT DIGIT INCREMENT SELECT ZERO SPAN DIGIT DIGIT ON DIP SWITCH SETTING FPM OR M S BASED ADJUST FLOW OUTPUT HIGH K CFM M H INCREMENT SELECT ZERO SPAN DIGIT DIGIT F AREA SQ FEET OR SQ METERS BASED ON DIP SWITCH SETTING M AREA SPAN UPON RELEASE SPAN SELECT MAXIMUM OUTPUT SET BY PRESSURE OR FLOW 3 Flow Mode Menu ...

Page 11: ...FROM UPDATE SECURITY AND SAVE MENU UPDATE SECURITY LEVEL ZERO ZERO ZERO SPAN SPAN SPAN SPAN ZERO SAVE CHANGES SPAN UPON RELEASE ZERO ZERO SPAN SPAN HOME POSITION Security Menu ...

Page 12: ...______________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ___________________________________________________...

Reviews: