7. 

Each connector should be spaced approximately one inch apart from the end of the connector 
in front of it, this allows for flexibility when traversing conduit elbows.  Connectors should only 
be taped to the Pull Cord, and not to other AOC cables in the bundle:

When finished, the taped connectors should look like this:

8. 

Wrap the excess Pull Cord around the bundle of cables.  The two ends of the Pull Cord must be 
wrapped in opposite directions, with the two sides crossing over each other as shown below:

9. 

Next, wrap electrical tape around every crosspoint on the Pull Cord as shown below.  This 
helps join the Pull Cord to the cable bundle:

4

Summary of Contents for DVI-2600-AOC-PSK

Page 1: ...it Contents The HyperLight Pull Sleeve Kit consists of the following components HyperLight Pull Sleeve HyperLight Cable Pull Cover p n DVI 2600 AOC CVR x 2 The installer will need to provide the follo...

Page 2: ...d around the cable s to be pulled and serves as a strength member that protects the cable s from undue tension The Flexible Sleeving 3 covers and protects the cable bundle from getting snagged on cond...

Page 3: ...pull it away from the exposed Pull Cord 5 Pull the sleeve back until the Pull Cord is fully exposed as shown below 6 Attach the covered connectors to the Pull Cord Starting at the side closest to the...

Page 4: ...nd not to other AOC cables in the bundle When finished the taped connectors should look like this 8 Wrap the excess Pull Cord around the bundle of cables The two ends of the Pull Cord must be wrapped...

Page 5: ...there is around 4 5 inches of pulling cord left 11 Form a termination knot with the remaining Pull Cord in order to maintain tension when pulling the bundle Start by grabbing both ends of the cord 12...

Page 6: ...the braids on the sides of the cable as shown below 15 The Pull Sleeve is now ready to go over the cable bundle Push the sleeve back over the bundle of cables If there are issues getting the sleeve t...

Page 7: ...nd right before the termination knot at the end of the Pull Cord 16 Finally wrap electrical tape around the end of the Pull Sleeve and the termination knot at the end of the Pull Cord as shown below O...

Page 8: ...Kit may be degraded if these standards are exceeded 18 Once the cable bundle has been pulled inspect the Pull Sleeve for any signs or damage If there are signs of damage on the sleeve note the locatio...

Reviews: