21
RMO30T RMOWin-T5 Software
Press
START
button to start the test current. When the test current is stabilized press
OMEGA
button to
measure resistance in the first tap changer position. Measured resistance value is saved in current
memory location and memory location is automatically changed to the next position.
After below message is appeared pres
OK
button.
When the message “Change the tap position” is appeared on the main window, change the tap position.
When the tap position is changed the graph with the test current during the change will be displayed.
That graph represents dynamic resistance during the change from tap to tap.
Press
OMEGA
button to measure resistance in the new tap changer position. It is possible to press
OMEGA
button either on the graph window or on the main window.
Repeat this procedure until you get all results. The diagram should looks like at the figure below